A walkthrough of the calculations to design an isolated footing (ACI 318-14)
The foundation is an essential building system that transfers column and wall forces to the supporting soil. The engineer might opt for a shallow or deep foundation system based on the soil characteristics and building loads.
SkyCiv Foundation Design Module includes analyzing and designing isolated footings (pad footings) conforming to the American code ACI 318-14. To use it, select American Concrete Institute as the Design Code and ACI 318 (2014) as the Version when you start a new file, then pick Pad Footing. For the 2019 edition, which adds the strip average method for flexure, see the Isolated Footing Design Walkthrough with ACI 318-19.

Want to try SkyCiv’s Foundation Design software? Our tool allows users to perform Foundation Design calculations without downloading or installing!
A Step-by-Step Guide to Designing an Isolated Footing
Dimension Requirements
To determine the dimensions of an isolated footing, service or unfactored loads, such as Dead (D), Live (L), Wind (W), Seismic (E), etc. are combined using the Load Combinations of ACI 318-14 (Table 5.3.1). Whichever Load Combination governs is considered the design load, and is compared to the allowable soil pressure as shown in Equation 1, as required by Section 13.3.1.1 of ACI 318-14.
[math] q_{a} = \frac{P_{n}}{A} \quad \text{(Eq. 1)} [math]
qa = Allowable soil pressure
Pn = Unfactored design load
A = Foundation area
The footing dimensions can be initially estimated by solving the foundation area (A) using Equation 1.
[math] A = \frac{P_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
In SkyCiv Foundation, the footing dimensions are inputs (Geometry tab). The software checks them with the soil pressures from the finite element analysis, as described in Soil Pressure.
One-way Shear
The one-way shear limit state, also known as beam shear, recognizes that the footing may fail in shear similar to a wide beam along a critical shear plane located at a distance "d" from the face of the column (Figure 1). SkyCiv Foundation checks it in both directions (along x and along z). It can be turned off with Perform One-Way Shear Check in the design settings (on by default).

Figure 1. One-way shear diagram (Results, Diagrams button)

Figure 1a. Critical sections for one-way shear, at d from the column faces
The One-way Shear Demand or \( V_{u} \) is the factored shear at the critical section, obtained from the finite element analysis of the footing: the soil pressure acting on the part of the footing beyond the critical section, cantilevered away from the column (Figure 1). The larger value of the two critical sections in each direction is used.
The One-way Shear Capacity or \( \phi V_{c} \) is calculated using Equation 2 per Section 22.5.5.1, with the full width of the footing perpendicular to the direction checked.
[math] \phi V_{c} = \phi_{\text{shear}} \times 2 \lambda \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 2, Section 22.5.5.1, Imperial)} [math]
or
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.17 \lambda \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 2, Section 22.5.5.1, Metric)} [math]
ϕshear = Shear strength reduction factor, 0.75 (Table 21.2.1)
λ = Modification factor for lightweight concrete
f’c = Specified concrete strength, (psi, MPa)
bw = Width of the footing perpendicular to the direction checked, (in, mm)
d = Effective depth, the average of the effective depths of the bottom bars in both directions, (in, mm)
Shear Demand and Shear Capacity must meet the following equation to meet the design requirements of ACI 318-14:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 3, Section 7.5.1.1(b))} [math]
SkyCiv Foundation Design Module, in compliance with Equation 3, calculates the one-way shear utility ratio (Equation 4) by taking Shear Demand over Shear Capacity.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 4)} [math]
Two-way Shear (Punching Shear)
The Two-way Shear limit state, also known as punching shear, has its critical section at a distance "d/2" from the faces of the column, around the perimeter of the column (Figure 2). Its length is the critical perimeter \( b_{o} \) (Section 22.6.4.1).

Figure 2. Critical perimeter of two-way shear (Results, Diagrams button)
When a column face is closer to a footing edge than the Punching Shear Edge Factor times d (design settings, 0.5 by default), the perimeter on that side extends to the footing edge and is not counted in \( b_{o} \). The column is then classified as an interior, edge or corner column, which sets \( \alpha_{s} \) = 40, 30 or 20 (Section 22.6.5.3). If the column is close to two opposite edges, the punching shear check is skipped, as one-way shear governs.
The Two-way Shear Demand is calculated at the critical perimeter with the mesh-based method, from the finite element analysis of the footing. The upward force from the soil pressure inside the critical perimeter, \( F_{q} \), is the sum of the forces of the mesh elements in that area, and it is subtracted from the factored column load. The maximum shear stress \( v_{u} \) on the critical perimeter also includes the unbalanced moments transferred by eccentric shear (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 5)} [math]
Pu = Factored column load
γv = Fraction of the unbalanced moment transferred by eccentric shear
Mu = Unbalanced moment (column moment, plus column shear times the column height and footing thickness)
c, Jc = Distance to the point considered and polar moment of inertia of the critical section
The Shear Capacity is the punching shear stress \( \phi v_{c} \), governed by the smallest value of Equations 6, 7 and 8 per Section 22.6.5.2.
[math] v_{c} = 4 \lambda \sqrt{f’_{c}} \quad \text{(Eq. 6, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c} = \left( 2 + \frac{4}{\beta} \right) \lambda \sqrt{f’_{c}} \quad \text{(Eq. 7, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(c), Imperial)} [math]
or
[math] v_{c} = 0.33 \lambda \sqrt{f’_{c}} \quad \text{(Eq. 6, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c} = 0.17 \left( 1 + \frac{2}{\beta} \right) \lambda \sqrt{f’_{c}} \quad \text{(Eq. 7, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c} = 0.083 \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
Note: β is the ratio of the long side to the short side of the column (1.0 for a round column, which is treated as an equivalent square), and \( \alpha_{s} \) is given by Section 22.6.5.3. ϕshear = 0.75.
λ = Modification factor to reflect the reduced mechanical properties of lightweight concrete relative to normal concrete of the same compressive strength
f’c = Specified compressive concrete strength (psi, MPa)
d = Effective depth, the average of the effective depths of the bottom bars in both directions, (in, mm)
bo = Critical perimeter (in, mm)
Shear Demand and Shear Capacity must meet the following equation to meet the design requirements of ACI 318-14:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 9, Section 7.5.1.1(b))} [math]
SkyCiv Foundation Design Module, in compliance with Equation 9, calculates the two-way shear utility ratio (Equation 10) by taking Shear Demand over Shear Capacity, both as stresses. The result is listed as Punching Shear in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 10)} [math]
Flexure
The Flexural Demand or \( M_{u} \) comes from the finite element analysis of the footing. For ACI 318-14, SkyCiv Foundation uses the Peak wood-armer method (the Moment Demand Calculation design setting is fixed to it for this code): \( M_{u} \) is the maximum Wood-Armer moment per unit width over the footing, under the ultimate load combinations, for the top and bottom layers in both directions (Figure 3).

Figure 3. Ultimate Wood-Armer moments (Results, Wood Armer button)
The Flexural Capacity or \( \phi M_{n} \) is calculated per unit width (12 in or 1000 mm) using Equation 11.
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 11)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
ϕflexure = flexural strength reduction factor, from 0.65 (compression-controlled) to 0.90 (tension-controlled) depending on the net tensile strain (Table 21.2.2)
As = reinforcement area per unit width (in2, mm2)
fy = reinforcement strength, (psi, MPa)
d = distance from extreme compression fiber to centroid of longitudinal tension reinforcement (in, mm)
a = depth of equivalent rectangular stress block (in, mm)
b = unit width (12 in, 1000 mm)
The provided reinforcement is also compared to the minimum area of Table 8.6.1.1 (0.0020 Ag for fy below 60,000 psi or 420 MPa, otherwise the larger of 0.0018 × 60,000/fy × Ag and 0.0014 Ag). Without top bars, the top face is checked as plain concrete.
Moment Demand and Moment Capacity must meet the following equation to meet the design requirements of ACI 318-14:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 12, Section 7.5.1.1(a))} [math]
SkyCiv Foundation Design Module, in compliance with Equation 12, calculates the flexural utility ratio (Equation 13) by taking Flexural Demand over Flexural Capacity. The Flexure ratio in the Design Checks Summary is the largest of the top, bottom and minimum reinforcement ratios.
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 13)} [math]
Additional Verifications
Other verifications not mentioned by the code, including soil pressure checks, uplift, and other stability checks are also verified.
Soil Pressure
The determination of base pressure or the interaction between the soil and footing primarily relies on the footing dimensions and the resulting eccentricity of the applied loads. Depending on the positioning of this resulting eccentricity, the base pressure can induce full or partial compression on the footing. This assessment enables us to confirm whether the underlying soil can sustain the entirety of the loads transmitted from the footing. SkyCiv Foundation takes the soil pressures from the finite element analysis of the footing.

For a detailed guide for manually calculating the soil pressure, please refer to this link: Pressure Distribution Under a Rectangular Concrete Footing
The utility ratio is evaluated by comparing the maximum soil pressure (serviceability state) with the Gross Allowable Soil Bearing Capacity entered in the Soil tab. It is listed as Soil Bearing in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Max. Soil Pressure}}{\text{Gross Allowable Soil Bearing Capacity}} \quad \text{(Eq. 14)} [math]
Uplift
Checks the governing axial load acting on the footing, considering axial loads only. Sums all vertical loads including the user load and self-weights of the column, footing slab, soil, and buoyant force. If the column experiences an upward force, the self-weights specified must counterbalance the upward force; otherwise, the design risks failure due to instability. When no service load combination produces uplift, the check is not needed.
Overturning
Overturning of the footing is checked by summing up all moments about the toe and the heel of the footing in each direction, including all the forces acting on it. All service load combinations are considered to find the governing overturning moment. The factor of safety (stabilising moment over overturning moment) is compared with the Overturning factor of safety in the Design Factors tab (2.0 by default). If the applied loads produce no overturning moment, the check is not needed.
Sliding
To check for sliding in each direction, the sum of the horizontal resisting forces is divided by the horizontal force applied to the footing, taken from the governing service load combination.
- Resisting forces:
- Friction between the footing base and the soil (coefficient of friction times the axial force on the base; none under net uplift)
- Passive soil pressure
- Cohesion of the soil
- Sliding force:
- The horizontal (shear) load applied to the column
The resulting factor of safety is compared with the Sliding factor of safety in the Design Factors tab (1.5 by default). If no horizontal force is acting on the footing, checking for sliding is not required.
SkyCiv Foundation Design Module
SkyCiv’s Foundation Design Module is integrated with Finite Element Analysis (FEA), delivering more accurate soil pressure analysis and introducing Wood-Armer analysis for detailed flexural design checks.
Shear and moment diagrams are also generated directly from the FEA results using the strip average method, providing a clearer picture of internal forces across the footing. Open them with the Diagrams button of the Results tab, and pick the Diagram (One-way Shear, Punching Shear or Moment), the case, the load combination, the layer and the direction.

The module supports advanced footing configurations, including column offsets in any direction for both isolated and combined footings. Loads and moments can also be applied in any direction, allowing for accurate modeling of real-world foundation conditions.
Not a SkyCiv User? Sign up for a Free 14 Day Trial to get started!
Product Developer
BSc (Civil), MSc (Civil)