SkyCiv Documentation

Your guide to SkyCiv software — tutorials, how-to guides and technical articles

Combined Footing Design in Accordance with ACI 318-14

A Combined footing is a single footing supporting two or more columns. Combined footings are commonly used when columns are spaced too closely, where two isolated footings would be unsatisfactory. For example, with two isolated footings that are too close to each other, the soil beneath may share portions of influence zones, leading to a required extension of either or both of the isolated footings. Depending on physical or other constraints, this may not be possible.

SkyCiv Foundation Design module includes the design of combined footings supporting two columns, conforming to the American Concrete Institute (ACI 318). The footing is meshed into plate elements supported on the soil (modeled with the subgrade modulus) and analyzed with finite element analysis (FEA). The soil pressures, shears and moments used in the design checks below come from these FEA results.

Want to try SkyCiv’s Foundation Design software? Our free tool allows users to perform load-carrying calculations without any download or installation!

Design of a Combined Foundation

Dimension Requirements

The plan dimensions and thickness of the combined footing are inputs. To size a combined footing, service or unfactored loads, such as Dead (D), Live (L), Wind (W), Seismic (E), etc. are applied using service load combinations. Whichever load combination governs is considered the design load, and is compared to the allowable soil pressure as shown in Equation 1, as required by Section 13.3.1.1 of ACI 318-14 (the base area is proportioned so that the permissible bearing pressure is not exceeded).

\(\text{q}_{\text{a}} = \frac{ \text{P1}_{\text{n}} + \text{P2}_{\text{n}} }{\text{A}} \rightarrow \) Equation 1

where:
qa = net allowable soil pressure
P1n = unfactored loads at Column 1 (left)
P2n = unfactored loads at Column 2 (right)
A = Foundation area

From Equation 1, qa is interchanged with A.

\(\text{A} = \frac{ \text{P1}_{\text{n}} + \text{P2}_{\text{n}} }{\text{q}_{\text{a}}} \rightarrow \) Equation 1a

At this point, the dimensions of the footing can be back-calculated from the required area, A, and entered in the model.

SkyCiv Foundation does not size the footing from Equation 1a. It checks the footing you entered (Soil Bearing check): the maximum soil pressure from the FEA results of the service load combinations (envelope), which includes the effect of the column moments and the eccentricity of the loads, is compared to the allowable soil bearing capacity:

\( \text{ratio} = \frac{\text{q}_{\text{sls,max}}}{\text{q}_{\text{a}}} \rightarrow \) Equation 1b

One-way Shear

The One-way shear limit state, also known as "flexural shear", extends its critical section across the width of the footing and is located at a distance "d" from the face of a column, where the Critical Plane Shear is located (Refer to Figure 1). It is checked when Perform One-Way Shear Check is enabled in the Design Settings.

Combined footing Results tab, SkyCiv Foundation: soil pressure contour, two one-way shear sections at d from column faces.

Figure 1. Critical sections of One-way shear

The One-way Shear Demand or Vu is taken from the strip average shear results of the FEA (ultimate load combinations) at the critical sections, located at the effective depth of the bottom bars in that direction from each column face (or at the edge of the footing when that distance falls outside it). The largest absolute shear at these sections, over all the ultimate load combinations, is the demand. It is taken along the x-direction (the direction joining the two columns) for the whole footing, and along the z-direction for each column. The shear diagrams used are shown in the calculation report, and can be viewed in the Results tab by opening Diagrams and choosing One-way Shear in the Diagram list.

SkyCiv Foundation Diagrams window: One-way Shear along X, Ultimate case, footing plan with critical sections and shear diagram

The calculation report shows the same diagram for each direction, followed by the shear demand, the capacity and the ratio:

SkyCiv Foundation CF01 design report, ACI 318-14 one-way shear: x-direction shear diagram, demand 225.7 kN, capacity 355.71 kN

The One-way Shear Capacity or ϕVc is the design shear strength, calculated using Equation 2 per ACI 318-14, Section 22.5.5.1:

\(\phi\text{V}_{\text{c}} = \phi _{\text{shear}} \times 2 \lambda \sqrt{\text{f’}_{\text{c}}} \times \text{b}_{\text{w}} \times \text{d} \rightarrow \) Equation 2 (ACI Eq. 22.5.5.1 English)

or

\(\phi\text{V}_{\text{c}} = \phi _{\text{shear}} \times 0.17 \lambda \sqrt{\text{f’}_{\text{c}}} \times \text{b}_{\text{w}} \times \text{d} \rightarrow \) Equation 2 (ACI Eq. 22.5.5.1 Metric)

where:
ϕshear = shear strength reduction factor, 0.75 (ACI 318-14 Table 21.2.1)
λ = modification factor for lightweight concrete, from the concrete weight type
f’c = specified concrete strength, psi or MPa
bw = width of the footing perpendicular to the direction checked (the footing dimension along z for shear along x, and along x for shear along z), in or mm
d = effective depth, taken as the average of the effective depths of the bottom reinforcement in the x and z directions, in or mm

Shear Demand and Shear Capacity must meet the following equation to meet the design requirements of ACI 318-14:

\(\text{V}_{\text{u}} \leq \phi\text{V}_{\text{c}} \rightarrow \) Equation 3 (ACI Eq. 7.5.1.1(b))

SkyCiv Foundation, in compliance of Equation 3, calculates the one-way shear unity ratio (Equation 4) by taking Shear Demand over Shear Capacity, for the x-direction and for each column along the z-direction. The largest ratio is reported.

\( \text{ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \rightarrow \) Equation 4

Get started

Want to try it for yourself?

Try SkyCiv today for free!

Sign Up Free

Two-way Shear

The Two-way Shear limit state, also known as "punching shear", extends its critical section to a distance "d/2" from the face of the column and around the perimeter of the column (ACI 318-14, Section 22.6.4.1). The Critical Shear Plane is located at that section of the footing (Refer to Figure 2). The check is done for each column.

SkyCiv Foundation combined footing Results tab: soil pressure contour with d/2 punching perimeters at Columns 1 and 2, Punching Shear 0.411

Figure 2. Critical perimeters of Two-way shear

The critical perimeter of each column can be viewed in the Results tab by opening Diagrams and choosing Punching Shear in the Diagram list:

Diagrams window in SkyCiv Foundation, Ultimate case, Punching Shear: footing plan with 0.5d critical perimeter around each column

When the distance from a column face to the edge of the footing is less than the Punching Shear Edge Factor (in the Design Settings, 0.5 by default) times d, that side of the critical section is taken at the edge of the footing and is not part of the critical perimeter, bo. The column is then classified as an interior, edge or corner column. If the column is too close to two opposite edges, the shear failure is one-way and punching shear is not checked for that column. Round columns are taken as an equivalent square column with sides equal to the diameter.

Punching shear check in SkyCiv Foundation design report: Column 2 critical shear area plan, corner coordinates, soil pressure force

The Two-way Shear Demand is calculated as a shear stress, υu, on the Critical Shear Plane, in accordance with ACI 318-14, Sections 8.4.4.2 and 22.6.4. It includes the factored column axial load reduced by the force from the soil pressure inside the critical section (the area inside the critical perimeter in Figure 2), and the shear stresses from the unbalanced moments transferred to the footing:

\( \upsilon_{u} = \frac{\text{P}_{u} – \text{F}_{q}}{\text{b}_{o} \times d} + \frac{\gamma_{v,x} \times \text{M}_{u,x} \times c_{x}}{\text{J}_{c,x}} – \frac{\gamma_{v,z} \times \text{M}_{u,z} \times c_{z}}{\text{J}_{c,z}} \rightarrow \) Equation 5

\( \gamma_{v} = 1 – \frac{1}{1 + \frac{2}{3}\sqrt{b_{1}/b_{2}}} \rightarrow \) Equation 6 (ACI 318-14, 8.4.2.3.2 and 8.4.4.2.2)

where:
Pu = factored axial load of the column
Fq = resultant of the factored soil pressure acting inside the critical section, summed over the FEA mesh elements
Mu = unbalanced moment transferred to the footing, including the column moment, the column shear times the column height plus the footing thickness, and the axial load times the eccentricity of the centroid of the critical section
γv = fraction of the unbalanced moment transferred by eccentricity of shear
b1, b2 = dimensions of the critical section perpendicular and parallel to the direction considered
c = distance from the centroid of the critical section to the point where the stress is calculated
Jc = property of the critical section analogous to the polar moment of inertia

For edge and corner columns, γv and the stresses are calculated following ACI 421.1R-20. The maximum stress around the critical section is taken as the demand.

The Shear Capacity or ϕυc is governed by the smallest value calculated using Equations 7, 8 and 9 per ACI 318-14, Table 22.6.5.2:

\(\phi\upsilon_{\text{c}} = \phi _{\text{shear}} \times \text{min} \left( \upsilon_{c,a}, \upsilon_{c,b}, \upsilon_{c,c} \right) \)

\(\upsilon_{c,a} = 4 \times \lambda \times \sqrt{\text{f’}_{\text{c}}} \rightarrow \) Equation 7 (ACI Eq. 22.6.5.2(a) English)

\(\upsilon_{c,b} = \left ( 2 + \frac{4}{\beta } \right ) \times \lambda \times \sqrt{f’_{c}} \rightarrow \) Equation 8 (ACI Eq. 22.6.5.2(b) English)

\(\upsilon_{c,c} = \left ( 2 + \frac{\alpha _{s} \times d }{b_{o}} \right ) \times \lambda \times \sqrt{f’_{c}} \rightarrow \) Equation 9 (ACI Eq. 22.6.5.2(c) English)

or

\(\upsilon_{c,a} = 0.33 \times \lambda \times \sqrt{\text{f’}_{\text{c}}} \rightarrow \) Equation 7 (ACI Eq. 22.6.5.2(a) Metric)

\(\upsilon_{c,b} = 0.17 \times \left ( 1 + \frac{2}{\beta } \right ) \times \lambda \times \sqrt{f’_{c}} \rightarrow \) Equation 8 (ACI Eq. 22.6.5.2(b) Metric)

\(\upsilon_{c,c} = 0.083 \times \left ( 2 + \frac{\alpha _{s} \times d }{b_{o}} \right ) \times \lambda \times \sqrt{f’_{c}} \rightarrow \) Equation 9 (ACI Eq. 22.6.5.2(c) Metric)

note: β is the ratio of long side to short side of the column (1.0 for round columns) and αs is given in 22.6.5.3: 40 for interior columns, 30 for edge columns and 20 for corner columns

where:
ϕshear = shear strength reduction factor, 0.75 (ACI 318-14 Table 21.2.1)
λ = modification factor to reflect the reduced mechanical properties of lightweight concrete relative to normalweight concrete of the same compressive strength
f’c = specified concrete strength, psi or MPa
bo = perimeter of the critical section, in or mm
d = effective depth, taken as the average of the effective depths of the bottom reinforcement in the x and z directions, in or mm

Shear Demand and Shear Capacity must meet the following equation to meet the design requirements of ACI 318-14:

\(\upsilon_{\text{u}} \leq \phi\upsilon_{\text{c}} \rightarrow \) Equation 10 (ACI 318-14, 8.5.1.1(d))

SkyCiv Foundation, in compliance of Equation 10, calculates the two-way shear unity ratio (Equation 11) of each column by taking Shear Demand over Shear Capacity. The larger ratio of the two columns is reported as Punching Shear.

\( \text{ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \rightarrow \) Equation 11

Get started

Want to try it for yourself?

Try SkyCiv today for free!

Sign Up Free

Flexure

Flexural isolated

Figure 3. Critical moment section of Flexure

In a hand calculation, the Flexural limit state is checked at the Critical Flexure Section, located at the face of the column on top of the footing (Refer to Figure 3). SkyCiv Foundation does not use a single critical section: it checks the top and bottom reinforcement in the x and z directions against the moments of the whole footing from the FEA.

The Flexural Demand, or Mu, is the peak Wood-Armer moment per unit width from the FEA results (ultimate load combinations, envelope), for each face (top and bottom) and each direction (x and z). For ACI 318-14, the Moment Demand Calculation in the Design Settings is set to the Peak Wood-Armer method and can’t be changed. The Wood-Armer moments can be viewed in the Results tab with the Wood Armer button.

The Flexural Capacity, or ϕMn, is calculated per unit width (12 in or 1000 mm) using Equation 12:

\( \phi\text{M}_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \rightarrow \) Equation 12

\( a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} \)

where:
ϕflexure = flexural strength reduction factor (ACI 318-14 Table 21.2.2): 0.90 when the net tensile strain εt ≥ 0.005 (tension-controlled), 0.65 when εt ≤ 0.002 (compression-controlled), interpolated in between. εt is calculated from the depth of the neutral axis, c = a/β1, with a concrete strain of 0.003
b = unit width, 12 in or 1000 mm
d = distance from extreme compression fiber to centroid of longitudinal tension reinforcement, in or mm
As = reinforcement area per unit width (bar area times the unit width divided by the bar spacing), in2 or mm2
a = depth of equivalent rectangular stress block, in or mm
fy = steel strength, psi or MPa

Moment Demand and Moment Capacity must meet the following equation to meet the design requirements of ACI 318-14:

\(\text{M}_{\text{u}} \leq \phi\text{M}_{\text{n}} \rightarrow \) Equation 13 (ACI Eq. 7.5.1.1(a))

SkyCiv Foundation, in compliance of Equation 13, calculates the flexural unity ratio (Equation 14) by taking Flexural Demand over Flexural Capacity

\( \text{ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \rightarrow \) Equation 14

The reinforcement provided is also checked against the minimum area of reinforcement per unit width: \( A_{s,min} = \text{max}\left( \frac{3\sqrt{f’_{c}}}{f_{y}}, \frac{200}{f_{y}} \right) b\,d \) (metric: \( \text{max}\left( \frac{0.25\sqrt{f’_{c}}}{f_{y}}, \frac{1.4}{f_{y}} \right) b\,d \)) per ACI 318-14 9.6.1.2 along the x-direction, and the shrinkage and temperature reinforcement of ACI 318-14 Table 8.6.1.1 along the z-direction (0.0020 Ag when fy is less than 60,000 psi or 420 MPa, otherwise the larger of 0.0018 × 60,000/fy × Ag and 0.0014 Ag, in metric 0.0018 × 420/fy × Ag). The Flexure ratio reported is the largest of the top, bottom and minimum reinforcement ratios.

Other Design Checks

Besides the checks above, the calculation report of a combined footing designed to ACI 318-14 includes the Uplift, Overturning and Sliding stability checks, Load Transfer (bearing at the column to footing interface), Development Length of the flexural bars and the column dowel bars, and Detailing. Each check gives a utilization ratio in the Design Checks Summary of the Results tab. The largest ratio governs the design, and the footing fails when it is greater than 1.0.

Combined footing Results tab in SkyCiv Foundation: Design Checks Summary utilization ratios beside a soil pressure contour map, with the Soil Pressure, Wood Armer and Diagrams buttons

Get started

Want to try it for yourself?

Try SkyCiv today for free!

Sign Up Free
Jerome Carlo San Juan Product Developer
Jerome Carlo San Juan
Product Developer
BSc (Civil), MSc (Civil)
LinkedIn

References

  1. Building Code Requirements for Structural Concrete (ACI 318-14) Commentary on Building Code Requirements for Structural Concrete (ACI 318R-14). American Concrete Institute, 2014.
  2. McCormac, Jack C., and Russell H. Brown. Design of Reinforced Concrete ACI 318-11 Code Edition. Wiley, 2014.
  3. Taylor, Andrew, et al. The Reinforced Concrete Design Handbook: a Companion to ACI-318-14. American Concrete Institute, 2015.
  4. Guide to Shear Reinforcement for Slabs (ACI 421.1R-20). American Concrete Institute, 2020.

How can we help?

×

Go to Top