Sample Model 3D Roof Frame

Dakframe

Overzicht

The purpose of this test case is to validate some of the analysis results of a 3D frame, specifiek:

  • Doorbuiging
  • Krachten/Momenten
  • Lineaire analyse

De structurele 3D-resultaten werden vergeleken met analysesoftware van derden.

Evaluatiepunten: 3
Oplossen:: Lineaire analyse

Model instellen

The structure is a 29-node, 28-member tower, that are predominantly fixed connections, supported by a series of pinned supports. The tower consists of 6.35mm x 6.35mm section for the main supporting elements, and a 1.5875mm x 1.5875mm section for the web members. Each section is composed of two different custom material.

 

Analyse resultaten

Resultaat Plaats SkyCiv Derde partij Verschil
Moment Z Lid 17, Startknooppunt -5.4670 kN-m -5.4726 kN-m 0.10%
Schuintrekken Y Lid 23, Eindknooppunt -4.3390 kN -4.3390 kN 0.00%
Reactie Y Knooppunt 9 16.03 kN 16.05 kN -0.12%
doorbuiging X Knooppunt 6 -0.0973 mm -0.0974 mm -0.10%
doorbuiging Y Knooppunt 15 -0.3227 mm -0.3229 mm -0.06%
Deflection Z Knooppunt 4 0.1104 mm 0.1094 mm 0.91%

Roof Frame Deflection

Ontwerpresultaten

Resultaat Plaats SkyCiv Derde partij Verschil
Moment Capacity UR Lid 1 (K=1.0) 0.093 0.093 0.00%
Shear Capacity UR Lid 17 (K=1.0) 0.039 0.039 0.00%
Gecombineerd Axiaal Lid 22 (K=1.0) 0.079 0.079 0.00%
Gecombineerd Axiaal Lid 14 (K=1.0) 0.027 0.027 0.00%

Roof Frame Design