A bolt in a shear connection designed to AS 4100:2020 is checked twice: once for the bolt itself shearing through (Clause 9.2.2.1) and once for the plies it passes through, which can bear or tear out at the holes (Clause 9.2.2.4). If the bolts are fully tensioned friction-type bolts (8.8/TF or 10.9/TF), a third check under Clause 9.2.3.1 makes sure the joint does not slip in service.
This page explains each of these checks and works them through with the same connection as our web side plate design example: eight M20 8.8/S bolts carrying 150 kN from a 460 UB 82.1 beam into a 10 mm plate. Every number comes from the calculation report that SkyCiv Connection Design produces for that connection.

Which bolt checks does AS 4100 require in shear?
| Check | Clause | Applies to |
|---|---|---|
| Bolt in shear, [mathin]\phi V_{f}[mathin] | 9.2.2.1 | Every bolt category (4.6/S, 8.8/S, 8.8/TB, 8.8/TF and the 10.9 ones) |
| Ply in bearing, [mathin]\phi V_{b}[mathin] | 9.2.2.4 | Every ply the bolt passes through: the plate, the beam web, the support |
| Friction-type joint in service, [mathin]\phi V_{sf}[mathin] | 9.2.3.1 | 8.8/TF and 10.9/TF bolts |
In a connection where the load is eccentric to the bolt group, the program finds the share of each bolt with the instantaneous centre of rotation method (Clause 9.3.1) and turns it into a bolt group coefficient C. The single-bolt capacities on this page are then multiplied by C. How C is found is covered step by step in bolt group calculation using ICOR.
Design inputs for the example
| Item | Symbol | Value |
|---|---|---|
| Design shear | [mathin]V^{*}[mathin] | 150 kN |
| Bolts | 8 x M20 8.8/S, 4 rows x 2 columns | |
| Bolt diameter / hole diameter | [mathin]d_{f},\ d_{h}[mathin] | 20 mm / 22 mm |
| Bolt minimum tensile strength | [mathin]f_{uf}[mathin] | 830 MPa |
| Core area / shank area | [mathin]A_{c},\ A_{o}[mathin] | 225 mm2 / 314.16 mm2 |
| Pitch / gauge | [mathin]s_{p},\ s_{g}[mathin] | 75 mm / 75 mm |
| Bolt group eccentricity | [mathin]e_{b}[mathin] | 107.5 mm |
| Plate | [mathin]t_{i},\ f_{up}[mathin] | 10 mm Gr.250, 410 MPa |
| Plate edge distances, vertical / horizontal | [mathin]l_{ev\_wp},\ l_{eh\_wp}[mathin] | 47.5 mm / 55 mm |
| Beam web | [mathin]t_{wb},\ f_{ub}[mathin] | 9.9 mm Gr.300, 440 MPa |
| Beam web horizontal edge distance | [mathin]l_{eh\_w}[mathin] | 50 mm |
Bolt shear capacity (Clause 9.2.2.1)
The design shear capacity of one bolt is:
[math]\phi V_{f} = \phi \times 0.62 \times f_{uf} \times k_{rd} \times k_{r} \times \left( n_{n} A_{c} + n_{x} A_{o} \right)[math]
with [mathin]\phi = 0.8[mathin] for a bolt in shear. The terms that change from one connection to another are:
- Threads in the shear plane, [mathin]n_{n}[mathin] and [mathin]n_{x}[mathin]. A shear plane through the threads uses the core area [mathin]A_{c}[mathin]; a plane through the plain shank uses the shank area [mathin]A_{o}[mathin]. For an M20 bolt that is 225 mm2 against 314.16 mm2, so excluding the threads is worth 40% more capacity. The program accepts "threads excluded" only when a standard bolt length leaves the threads clear of the shear plane for the plies entered, and never for 4.6 bolts. Otherwise it designs with threads included.
- Ductility factor [mathin]k_{rd}[mathin]. The program takes 0.83 for 10.9 bolts with threads included in the shear plane, and 1.0 for every other case.
- Lap length factor [mathin]k_{r}[mathin]. Long bolted lap joints lose capacity because the end bolts take more than their share. The program works out the joint length as [mathin]l_{j} = (n_{rows} – 1) s_{p}[mathin] along the force and applies:
| Joint length | [mathin]k_{r}[mathin] |
|---|---|
| [mathin]l_{j} \lt 300[mathin] mm | 1.0 |
| 300 mm to 1300 mm | [mathin]1.075 – l_{j}/4000[mathin] |
| [mathin]l_{j} \gt 1300[mathin] mm | 0.75 |
The lap reduction is applied in flange plate connections and splices, where the force runs along a line of bolts. In beam shear connections such as the web side plate, the report shows [mathin]k_{r,bolt} = 1[mathin].
Step 1: Design shear capacity of one bolt
The 8.8/S bolts in the example have the threads in the single shear plane, so [mathin]n_{n} = 1[mathin] and [mathin]n_{x} = 0[mathin]:
[math]\phi V_{f} = 0.8 \times 0.62 \times 830 \times 1 \times 1 \times \left( 1 \times 225 + 0 \times 314.16 \right) = 92.628\ \text{kN}[math]
Step 2: Bolt group in shear (Clause 9.3.1)
The 150 kN shear acts 107.5 mm from the centroid of the bolt group. The ICOR iteration places the instantaneous centre at [mathin]x_{ic} = -30.727\ \text{mm}[mathin] and [mathin]y_{ic} = 112.5\ \text{mm}[mathin] from Bolt No. 1 (bottom left). The vertical reactions of the eight bolts, each at its [mathin]\phi V_{f}[mathin] limit, add up to:
[math]\phi V_{df} = \sum R_{y} = 430.69\ \text{kN}, \qquad C = \frac{\phi V_{df}}{\phi V_{f}} = \frac{430.69}{92.628} = 4.6497[math]
DCR = 150 kN / 430.69 kN = 0.348 ≤ 1.0, OK
Step 3: The same bolts with threads excluded
Switching the same input to threads excluded from the shear plane gives [mathin]n_{n} = 0[mathin] and [mathin]n_{x} = 1[mathin]:
[math]\phi V_{f} = 0.8 \times 0.62 \times 830 \times 1 \times 1 \times \left( 0 \times 225 + 1 \times 314.16 \right) = 129.33\ \text{kN}[math]
The bolt group capacity rises to [mathin]\phi V_{df} = 601.36\ \text{kN}[mathin], and the DCR drops from 0.348 to 0.249. The bearing checks below do not change, because they do not depend on the threads.
Ply bearing capacity (Clause 9.2.2.4)
A ply can fail at a bolt hole in two ways: the bolt crushes the material in front of it (bearing), or the bolt tears out through the edge of the ply or into the next hole (tear-out). The program takes the smaller of the two:
[math]\phi V_{b} = \phi \times \min\left( 3.2\, d_{f}\, t_{p}\, f_{up},\ a_{e}\, t_{p}\, f_{up} \right)[math]
with [mathin]\phi = 0.9[mathin] for a ply in bearing. [mathin]a_{e}[mathin] is the distance from the edge of the hole to the edge of the ply, plus half the bolt diameter, measured in the direction of the force:
- to a free edge: [mathin]a_{e} = l_{e} – 0.5\, d_{h} + 0.5\, d_{f}[mathin]
- to the next hole: [mathin]a_{e} = s – d_{h} + 0.5\, d_{f}[mathin]
When the bolt forces come from an ICOR analysis they act in different directions, so the program takes the least [mathin]a_{e}[mathin] in either direction for each ply.
Step 4: Bearing on the web side plate
[math]a_{e1} = 47.5 – 0.5 \times 22 + 0.5 \times 20 = 46.5\ \text{mm} \qquad a_{e2} = 75 – 22 + 0.5 \times 20 = 63\ \text{mm}[math]
[math]a_{e3} = 55 – 0.5 \times 22 + 0.5 \times 20 = 54\ \text{mm} \qquad a_{e4} = 75 – 22 + 0.5 \times 20 = 63\ \text{mm}[math]
The vertical edge distance governs, [mathin]a_{e} = 46.5\ \text{mm}[mathin]:
[math]\phi V_{b,pl} = 0.9 \times \min\left( 3.2 \times 20 \times 10 \times 410,\ 46.5 \times 10 \times 410 \right) = 171.59\ \text{kN}[math]
Tear-out governs here: [mathin]3.2 d_{f} = 64\ \text{mm}[mathin] is more than the 46.5 mm available.
Step 5: Bearing on the beam web
The beam web has no vertical free edge near the bolts, so only the pitch, the horizontal edge and the gauge count:
[math]a_{e5} = 75 – 22 + 0.5 \times 20 = 63\ \text{mm} \qquad a_{e6} = 50 – 0.5 \times 22 + 0.5 \times 20 = 49\ \text{mm} \qquad a_{e7} = 63\ \text{mm}[math]
[math]\phi V_{b,beam} = 0.9 \times \min\left( 3.2 \times 20 \times 9.9 \times 440,\ 49 \times 9.9 \times 440 \right) = 192.1\ \text{kN}[math]
Step 6: Bolt group in bearing
The weaker ply governs, and the same coefficient C spreads it over the group:
[math]\phi V_{b} = \min\left( 171.59,\ 192.1 \right) \times 4.6497 = 797.82\ \text{kN}[math]
DCR = 150 kN / 797.82 kN = 0.188 ≤ 1.0, OK
Bolt shear governs this connection by a wide margin (0.348 against 0.188). That is typical for 8.8 bolts in 10 mm plates; bearing tends to govern with thin plies, short edge distances or 10.9 bolts.
Friction-type bolts: serviceability (Clause 9.2.3.1)
With 8.8/TF bolts the joint is meant not to slip at the serviceability limit state. The report adds a check of the slip capacity of the bolt group:
[math]\phi V_{sf} = \phi\, \mu\, n_{ei}\, N_{ti}\, k_{h}\, C[math]
with [mathin]\phi = 0.7[mathin], the slip factor [mathin]\mu = 0.35[mathin], [mathin]n_{ei}[mathin] the number of effective interfaces, [mathin]N_{ti}[mathin] the minimum bolt tension at installation (Table 15.2.2.2) and [mathin]k_{h}[mathin] the hole type factor, 1.0 for standard holes and 0.85 for oversize or short slotted holes. Changing the example’s bolts to M20 8.8/TF:
[math]\phi V_{sf} = 0.7 \times 0.35 \times 1 \times 145 \times 1 \times 4.6497 = 165.18\ \text{kN}[math]
DCR = 150 kN / 165.18 kN = 0.908 ≤ 1.0, OK
The strength checks of Steps 1 to 6 still apply to TF bolts unchanged. The serviceability check uses the design shear entered for the connection, so if your serviceability shear is lower than the strength one, the DCR shown is on the safe side.
Summary of the bolt checks
| Case | Check | Capacity | DCR |
|---|---|---|---|
| 8.8/S, threads included | Bolt group in shear | 430.69 kN | 0.348 |
| 8.8/S, threads excluded | Bolt group in shear | 601.36 kN | 0.249 |
| Any | Bolt group in bearing (plate governs) | 797.82 kN | 0.188 |
| 8.8/TF | Slip in service | 165.18 kN | 0.908 |
What to change if a bolt check fails
- Bolt shear: add a bolt row (it raises C), use M24 bolts or a 10.9 grade, keep the threads out of the shear plane if the bolt length allows, or move the bolts closer to the support to cut the eccentricity.
- Bearing on a ply: increase the edge distance in the direction of the force, increase the pitch, or use a thicker ply. If the beam web governs, add bolts or use a larger bolt.
- Slip of TF bolts: add bolts, use a larger bolt for a higher [mathin]N_{ti}[mathin], or use standard holes rather than oversize or slotted ones.
For web side plates, flexible end plates, single and double angle cleats, flange plates and beam and column splices with flange and web plates, Auto Design will try these changes for you and return a layout that passes.
Frequently asked questions
Why is the shear on one bolt not just V* divided by the number of bolts?
Because the load is eccentric to the group. The 107.5 mm lever arm adds a moment that the bolts farthest from the instantaneous centre resist most, so the group is worth C = 4.6497 single bolts, not eight.
Does the bearing check depend on the bolt grade?
No. Clause 9.2.2.4 uses the ply’s tensile strength [mathin]f_{up}[mathin], its thickness and the bolt diameter. The bolt grade only enters the bolt shear check.
Why does the plate govern bearing when the beam web is thinner?
The plate’s tensile strength is lower (410 MPa against 440 MPa) and its vertical edge distance gives [mathin]a_{e} = 46.5\ \text{mm}[mathin], less than the 49 mm that governs the beam web.
Are TF bolts checked for slip at the strength limit state?
No. Clause 9.2.3.1 is a serviceability check. At the strength limit state a TF bolt is designed as a bearing bolt, with the same shear and ply bearing checks as an S bolt.
Check your own bolts for free
Pick AS 4100:2020 and a bolted connection, set the bolt category, size and hole type, and every bolt check above comes back with its DCR and clause. There is nothing to install.
The SkyCiv Connection Design module gives you the full calculation report with every equation and your numbers in it, for AS 4100:2020 shear connections, moment connections and splices. The bolt calculator is a quick way to check a single bolt group.
References
- AS 4100:2020, Steel Structures: Clauses 9.2.2.1, 9.2.2.4, 9.2.3.1, 9.3.1; Table 15.2.2.2.
- Web side plate connection design example to AS 4100
- Bolt group calculation using ICOR
- Design of steel connections using AS 4100:2020