When a directly welded web connection carries an axial force as well as the end shear, two things change in the design to AISC 360. The welds now see a resultant force at an angle to their axis, which is larger than the shear alone but also earns the directional strength increase of Eq. J2-5. And the axial force is delivered to the column flange as a concentrated force, so the column has to be checked for flange local bending, web local yielding and, in compression, web local crippling.
This page works the same connection as the shear-only directly welded web example, a W18x50 beam web welded to the flange of a W14x90 column with 3/16 in E70XX fillet welds 15.5 in long on both sides of the web, and adds an axial force of 132 kip in tension or compression to the 38 kip end shear (LRFD). The design is to AISC 360-16 and the AISC Manual 15th Edition. Every equation is written out with its numbers, in the same order as the calc sheet that the SkyCiv Connection Design module produces for this connection.
What the axial force adds to a directly welded web connection
A beam in a braced frame or a diaphragm chord often carries an axial force along with its end reaction, for example as a strut or collector. With a directly welded web, that force has no plate or bolts to pass through: it goes straight from the web into the two fillet welds and from them into the column flange.
The member sizes, weld and the checks of the minimum weld size and the beam web in shear are the same as in the shear-only example, and give the same results. This page focuses on the weld under combined load and on the two support checks the axial force adds. The other shear connection types are on the shear connections page.

Elevation of the example connection, with the 38 kip shear and the 132 kip tension or compression at the beam end.

The same connection in SkyCiv Connection Design, with the Directly Welded Web config on the Assembly tab.
Directly welded web shear and axial design: the steps at a glance
- Check the minimum fillet weld size.
- Check the welds for the resultant of the shear and the axial force.
- Check the beam web in shear.
- Check the column for the axial tension: flange local bending and web local yielding.
- Check the column for the axial compression: web local crippling and web local yielding.
Design inputs for this example
The design code is AISC 360-16 LRFD. Section properties are from the AISC Manual. The column’s kdes, used in web local yielding, is 1.31 in.
| Item | Symbol | Value |
|---|---|---|
| Factored shear | [mathin] V_{u} [mathin] | 38 kip |
| Factored axial tension | [mathin] T_{u} [mathin] | 132 kip |
| Factored axial compression | [mathin] C_{u} [mathin] | 132 kip |
| Beam | W18x50, A992 | |
| Beam depth / web thickness | [mathin] d_{bm},\ t_{wb} [mathin] | 18 in / 0.355 in |
| Column | W14x90, A992 | |
| Column depth / web thickness | [mathin] d_{sup},\ t_{ws} [mathin] | 14 in / 0.44 in |
| Column flange width / thickness | [mathin] b_{fs},\ t_{fs} [mathin] | 14.5 in / 0.71 in |
| Column kdes | [mathin] k_{des} [mathin] | 1.31 in |
| Beam and column yield / tensile stress | [mathin] F_{y},\ F_{u} [mathin] | 50 ksi / 65 ksi |
| Modulus of elasticity | [mathin] E [mathin] | 29000 ksi |
| Weld | E70XX fillet, both sides of the web | |
| Weld size / length on each side | [mathin] W,\ L_{wv} [mathin] | 0.1875 in / 15.5 in |
Step 1: Minimum fillet weld size (AISC 360-16 J2.2b, Table J2.4)
The axial force does not change this check. The thinner part joined is the 0.355 in beam web, so the Table J2.4 minimum is 3/16 in, and the weld is 3/16 in.
DCR = 0.1875 in / 0.1875 in = 1.000 ≤ 1.0, OK
Step 2: Welds under the resultant of shear and axial force (AISC 360-16 J2.4)
The base metal limit and the effective length are the same as for shear alone, half the web thickness against the column flange, and twice the weld size off each end:
[math] D_{max} = \frac{\min\left( t_{fs} F_{us},\ \frac{t_{wb}}{2} F_{ub} \right)}{3.09\ \text{kip/in}} = \frac{\min\left( (0.71\ \text{in})(65\ \text{ksi}),\ (0.1775\ \text{in})(65\ \text{ksi}) \right)}{3.09\ \text{kip/in}} = 3.7338 [math]
[math] L_{w} = 2\left[ L_{wv} – 2W \right] = 2 \times \left[ 15.5\ \text{in} – 2 \times 0.1875\ \text{in} \right] = 30.25\ \text{in} [math]
What changes is the load. The welds now carry the vertical shear along their axis and the axial force across it. The demand is the resultant of the two, at an angle to the weld axis:
[math] R_{u} = \sqrt{V_{u}^{2} + T_{u}^{2}} = \sqrt{(38\ \text{kip})^{2} + (132\ \text{kip})^{2}} = 137.36\ \text{kip} [math]
[math] \theta_{u} = \tan^{-1}\left( \frac{T_{u}}{V_{u}} \right) = \tan^{-1}\left( \frac{132}{38} \right) = 73.94^{\circ} [math]
A fillet weld loaded across its axis is stronger than one loaded along it, and Eq. J2-5 rewards that with the directional term:
[math] \phi R_{n} = \phi\, 0.6\, F_{EXX} \frac{\sqrt{2}}{2} \min\left( W,\ \frac{D_{max}}{16} \right) \left[ 1 + 0.5 \left( \sin\theta_{u} \right)^{1.5} \right] L_{w} [math]
[math] \phi R_{n} = (0.75) \times 0.6 \times (70\ \text{ksi}) \times \frac{\sqrt{2}}{2} \times \min\left( 0.1875\ \text{in},\ \frac{3.7338}{16} \right) \times \left[ 1 + 0.5 \left( \sin 73.94^{\circ} \right)^{1.5} \right] \times (30.25\ \text{in}) = 185.84\ \text{kip} [math]
DCR = 137.36 kip / 185.84 kip = 0.739 < 1.0, OK
This is the governing check. The same welds are good for 126.33 kip under shear alone, so the load angle adds about 47% to their strength. The demand grows faster, though, from 38 kip to 137.36 kip, and the ratio rises from 0.301 to 0.739. The tension and compression cases have the same resultant, so one weld check covers both.
Step 3: Beam web in shear (AISC 360-16 J4.2)
The beam web still carries only the 38 kip shear, over its full depth:
[math] \phi R_{n} = \phi\, 0.6\, F_{yb}\, d_{bm}\, t_{wb} = (1) \times 0.6 \times (50\ \text{ksi}) \times (18\ \text{in})(0.355\ \text{in}) = 191.7\ \text{kip} [math]
DCR = 38 kip / 191.7 kip = 0.198 < 1.0, OK
Step 4: Column under the axial tension (AISC 360-16 J10.1, J10.2)
The axial tension pulls on the column flange along the line of the weld. AISC 360-16 J10 covers this as a concentrated force on the flange: flange local bending (J10.1), where it applies, and web local yielding (J10.2). Web local crippling (J10.3) is for compressive forces only.
Flange local bending
J10.1 does not require a flange local bending check when the length of loading measured across the member flange is less than 0.15 times the flange width:
[math] 0.15\, b_{f} = 0.15\, b_{fs} = 0.15 \times (14.5\ \text{in}) = 2.175\ \text{in} [math]
The load is delivered by the beam web, so the loaded length across the column flange is the web thickness, [mathin] t_{wb} = 0.355\ \text{in} [mathin]. That is less than 2.175 in, so flange local bending need not be checked.
Web local yielding
The force spreads through the column flange into the web over the weld length plus [mathin] 5k [mathin] (Eq. J10-2):
[math] \phi R_{n} = \phi\, F_{ys}\, t_{ws} \left( 5 k_{des} + L_{wv} \right) = (1) \times (50\ \text{ksi}) \times (0.44\ \text{in}) \times \left( 5 \times 1.31\ \text{in} + 15.5\ \text{in} \right) = 485.1\ \text{kip} [math]
DCR = 132 kip / 485.1 kip = 0.272 < 1.0, OK
Step 5: Column under the axial compression (AISC 360-16 J10.2, J10.3)
In compression the beam pushes on the column flange, so web local crippling joins web local yielding. Web local crippling, Eq. J10-4, with the weld length as the bearing length:
[math] \phi R_{n,wlc} = \phi\, 0.8\, t_{ws}^{2} \left[ 1 + 3\left( \frac{L_{wv}}{d_{sup}} \right) \left( \frac{t_{ws}}{t_{fs}} \right)^{1.5} \right] \sqrt{\frac{E F_{ys} t_{fs}}{t_{ws}}}\, Q_{f} [math]
[math] \phi R_{n,wlc} = (0.75) \times 0.8 \times (0.44\ \text{in})^{2} \left[ 1 + 3\left( \frac{15.5}{14} \right) \left( \frac{0.44}{0.71} \right)^{1.5} \right] \sqrt{\frac{(29000\ \text{ksi})(50\ \text{ksi})(0.71\ \text{in})}{0.44\ \text{in}}} \times (1) = 465.59\ \text{kip} [math]
Web local yielding is the same as in tension, 485.1 kip. The lower of the two governs:
[math] \phi R_{n} = \min\left( 465.59\ \text{kip},\ 485.1\ \text{kip} \right) = 465.59\ \text{kip} [math]
DCR = 132 kip / 465.59 kip = 0.284 < 1.0, OK
Both column checks pass with room to spare, so this W14x90 needs no stiffeners or web doubler for these limit states.
Summary of checks
| Design check | Demand | Capacity | DCR | Result |
|---|---|---|---|---|
| Minimum fillet weld size | 0.1875 in | 0.1875 in | 1.000 | PASS |
| Welds under shear and axial force | 137.36 kip | 185.84 kip | 0.739 | PASS |
| Beam web in shear | 38 kip | 191.7 kip | 0.198 | PASS |
| Column under axial tension | 132 kip | 485.1 kip | 0.272 | PASS |
| Column under axial compression | 132 kip | 465.59 kip | 0.284 | PASS |
Every check in this directly welded web shear and axial connection design passes. The 1.000 ratio is the minimum fillet weld size, which the 3/16 in weld meets exactly. Of the strength checks, the welds govern at 0.739 under the 137.36 kip resultant, against 0.301 for the same welds under shear alone. The column checks for the axial force come next, with web local crippling in compression at 0.284.
Auto Design is available for the directly welded web connection with shear and axial load to a column flange. It changes the connection’s design variables until every check passes, and keeps your members and loads as entered. See the Auto Design page for the preferences it works to.
What to change if a check fails
- Weld strength: lengthen the welds, increase the weld size up to the base metal limit of the half web, or use a stronger electrode. Past that limit a larger weld adds no strength.
- Column web local yielding or crippling: a longer weld spreads the force over more of the column web and raises both strengths. Otherwise use a column with a thicker web, or add stiffeners or a web doubler.
- Flange local bending: with a directly welded web it only applies if the loaded length across the flange reaches 0.15 times the flange width.
- Minimum weld size or beam web shear: as for shear alone, meet the Table J2.4 minimum, or use a heavier beam.
Frequently asked questions
Why does the weld get stronger when the axial force is added?
The strength of a fillet weld depends on the direction of the load. Under pure shear the load runs along the weld, and the directional term of Eq. J2-5 is 1. With 132 kip of axial force the resultant turns to 73.94 degrees from the weld axis, and the term rises toward its maximum of 1.5 for a load at 90 degrees. Here it lifts the weld strength from 126.33 kip to 185.84 kip.
Why is only one weld check reported for both tension and compression?
The axial force is 132 kip either way, so the resultant on the welds is the same 137.36 kip at the same angle. The sign of the axial force matters for the column, which is why the support is checked separately for tension and compression.
Why is flange local bending not checked?
J10.1 only requires it when the force is spread across a meaningful width of the column flange. Here the force comes in through a 0.355 in beam web, which is much less than 0.15 times the 14.5 in flange width, 2.175 in, so J10.1 does not require the check.
Why is web local crippling checked only in compression?
Web local crippling is the buckling of the column web under a compressive force pushed through the flange. A tensile force pulls the web straight, so J10.3 applies to compressive forces only, while web local yielding applies to both.
How would this change for AISC ASD instead of LRFD?
The limit states and nominal strengths are the same. With AISC ASD you compare service-level forces against the nominal strength divided by a safety factor: 0.75 for the welds and for web local crippling becomes a safety factor of 2.00, and 1.00 for web shear yielding and web local yielding becomes 1.50.
Design a directly welded web connection for free
Every number on this page comes from one solve. Pick the directly welded web configuration with shear and axial load, enter your beam, support, weld and forces, and the free calculator runs each of these checks in your browser without anything to install.
The SkyCiv Connection Design module is the connection design software behind this example. It gives you the full calculation report with every equation and your numbers in it, like the steps above, plus every capacity and DCR, for AISC 360-22 and AISC 360-16 (LRFD and ASD) and AS 4100:2020. The weld calculator covers fillet weld groups on their own.
References
- AISC 360-16, Specification for Structural Steel Buildings: J2.2b (Table J2.4), J2.4 (Eq. J2-4, J2-5), J4.2 (Eq. J4-3), J10.1, J10.2 (Eq. J10-2), J10.3 (Eq. J10-4).
- AISC Steel Construction Manual, 15th Edition: Part 9 (Eq. 9-2), Part 10 (effective weld length).