To design a bolted column splice to AS 4100, you first raise the design actions to the minimums of Clause 9.1.4, share them between the flanges and the web, and then check each load path: the flange plates and their bolts for the flange forces, the web plates and their bolts for the shear and the web share of the axial force, and the column itself at the bolt holes. The detailing limits on pitch and edge distance come first, because the capacity equations assume a layout that can be built.
This page works through one example from start to finish: a 310 UC 137 column spliced to another 310 UC 137, with ends prepared for full contact, 16 mm flange plates on 14 M24 8.8/S bolts each side of the joint and two 12 mm web plates, designed to AS 4100:2020. Every equation is written out with its numbers, in the same order as the calculation report that the SkyCiv Connection Design module produces for it. The scope and conventions of the AS 4100 module are on the design of steel connections using AS 4100:2020 page.
What is a bolted column splice?
A column splice joins two lengths of column, usually a little above a floor level, so that a multi-storey column can be delivered and erected in practical lengths. In this bolted form, a cover plate on the outside of each flange and a pair of plates on the web are bolted through to both columns. The flange plates carry the flange forces from the axial force and the bending moment, and the web plates carry the shear.
Where the column ends are machined or sawn square and prepared for full contact, compression passes from one column to the other in direct bearing, and the bolts only have to carry tension, the shear and a minimum share of the compression. That is the case in this example. You can check a splice of your own directly in the column splice calculator.
In this example both columns are 310 UC 137. Each flange plate has two lines of seven bolts on each side of the joint, and each web plate has one line of three bolts across the web on each side.

Elevation of the example splice. The column ends are prepared for full contact, and each flange plate has seven bolt rows at 75 mm on a 190 mm gauge each side of the joint.

Section A-A. A 12 mm web plate sits on each side of the column web, with three bolts at 75 mm across the web on each side of the joint.

The same splice in SkyCiv Connection Design, with the flange plate selected on the Assembly tab.
Column splice design: the steps at a glance
- Raise the design actions to the Clause 9.1.4 minimums and share them between the flanges and the web (Clause 9.1.3).
- Check the flange plate detailing limits.
- Check the flange bolt group in shear.
- Check the flange bolts in bearing on the flange plate and the column flange.
- Check the flange plate and the column flange in block shear.
- Check the flange plate and the column flange in tension.
- Check the section moment capacity of the column at the flange holes, reduced for axial force.
- Check the web plate detailing limits.
- Check the web bolt group in shear, by the instantaneous centre of rotation, and in bearing.
- Check the web plates in tension, bending, shear and block shear.
- Check the column web in block shear under axial tension.
The report runs the same checks for the lower and the upper column. Both are 310 UC 137 with the same bolts and distances, so the results are identical and this page shows the lower column.
Design inputs for this example
The design code is AS 4100:2020, with section properties from the Australian section database. The yield strength of each part follows its grade and thickness: the 21.7 mm column flange gives 280 MPa, the 16 mm flange plate 300 MPa and the 12 mm web plates 310 MPa.
| Item | Symbol | Value |
|---|---|---|
| Lower and upper column | 310 UC 137, AS/NZS 3679.1 Gr.300 | |
| Column depth / web thickness | [mathin] d_{c},\ t_{wc} [mathin] | 321 mm / 13.8 mm |
| Column flange width / thickness | [mathin] b_{fc},\ t_{fc} [mathin] | 309 mm / 21.7 mm |
| Column gross area | [mathin] A_{g} [mathin] | 17500 mm² |
| Plastic section modulus (major axis) | [mathin] S_{x} [mathin] | 2.3 x 10⁶ mm³ |
| Column yield / tensile strength | [mathin] f_{yc},\ f_{uc} [mathin] | 280 MPa / 440 MPa |
| Column ends | Prepared for full contact, gap c = 0 mm |
| Item | Symbol | Value |
|---|---|---|
| Flange plates (one on each flange) | PL 16 x 300 x 1090, AS/NZS 3678 Gr.300 | |
| Flange plate width / length / thickness | [mathin] b_{p},\ l_{p},\ t_{p} [mathin] | 300 mm / 1090 mm / 16 mm |
| Flange plate yield / tensile strength | [mathin] f_{yp},\ f_{up} [mathin] | 300 MPa / 430 MPa |
| Web plates (one on each side of the web) | 2 x PL 12 x 180 x 240, AS/NZS 3678 Gr.300 | |
| Web plate width / depth / thickness | [mathin] b_{i},\ d_{i},\ t_{i} [mathin] | 180 mm / 240 mm / 12 mm |
| Web plate yield / tensile strength | [mathin] f_{yp},\ f_{up} [mathin] | 310 MPa / 430 MPa |
| Bolts | M24 8.8/S, threads included in the shear plane | |
| Bolt diameter / minimum tensile strength | [mathin] d_{f},\ f_{uf} [mathin] | 24 mm / 830 MPa |
| Bolt core / shank area | [mathin] A_{c},\ A_{o} [mathin] | 324 mm² / 452.39 mm² |
| Holes | [mathin] d_{h} [mathin] | Nominal, 26 mm |
| Geometry (each column) | Symbol | Value |
|---|---|---|
| Flange bolts: rows / row pitch | [mathin] n_{p},\ s_{p} [mathin] | 7 / 75 mm |
| Flange bolts: columns / gauge | [mathin] n_{g},\ s_{g} [mathin] | 2 / 190 mm |
| Flange bolts per column, per flange | [mathin] n_{b} [mathin] | 14 |
| End distance on the column flange (to the column end) | [mathin] l_{ev\_f} [mathin] | 45 mm |
| End distance on the flange plate | [mathin] l_{ev\_fp} [mathin] | 50 mm |
| Edge distance on the flange plate | [mathin] l_{eh\_fp} [mathin] | 55 mm |
| Edge distance on the column flange | [mathin] l_{eh\_f} [mathin] | 59.5 mm |
| Web bolts: rows across the web / pitch | [mathin] n_{p},\ s_{p} [mathin] | 3 / 75 mm |
| Web bolts: columns | [mathin] n_{g} [mathin] | 1 |
| End distance on the column web (to the column end) | [mathin] l_{ev\_w} [mathin] | 45 mm |
| Edge distances on the web plate | [mathin] l_{eh\_wp},\ l_{ev\_wp} [mathin] | 45 mm / 45 mm |
The design actions entered are a shear of 165 kN, an axial tension and an axial compression of 1062 kN, and a major axis bending moment of 160 kN m. In the SkyCiv load combination these are Fz = 165 kN, Fy = 1062 kN in tension and in compression, and Mx = 160 kN m.
Design actions (AS 4100 Clauses 9.1.4 and 9.1.3)
AS 4100 Clause 9.1.4 sets minimum design actions for splices. The bending moment and the axial tension are not taken less than 0.3 times the corresponding section capacities of the column:
[math] M_{x}^{*} = \max\left( M_{x}^{*},\ 0.3\, \phi\, f_{yc}\, S_{x} \right) = \max\left( 160\ \text{kN m},\ 0.3 \times 0.9 \times (280\ \text{MPa}) \times (2.3 \times 10^{6}\ \text{mm}^{3}) \right) = 173.88\ \text{kN m} [math]
[math] N_{t}^{*} = \max\left( N_{t}^{*},\ 0.3\, \phi\, A_{g}\, f_{yc} \right) = \max\left( 1062\ \text{kN},\ 0.3 \times 0.9 \times (17500\ \text{mm}^{2}) \times (280\ \text{MPa}) \right) = 1323\ \text{kN} [math]
The column ends bear in full contact, so the compression passes in bearing and the bolts take only a minimum compression:
[math] N_{c,min}^{*} = 0.15\, \phi\, A_{g}\, f_{yc} = 0.15 \times 0.9 \times (17500\ \text{mm}^{2}) \times (280\ \text{MPa}) = 661.5\ \text{kN} [math]
Under Clause 9.1.3 the axial force is shared between the flanges and the web in proportion to their areas, and the moment is taken by the flanges as a couple:
[math] A_{w} = \left( d_{c} – 2\, t_{fc} \right) t_{wc} = (321\ \text{mm} – 2 \times 21.7\ \text{mm}) \times (13.8\ \text{mm}) = 3830.9\ \text{mm}^{2} [math]
[math] A = 2\, b_{fc}\, t_{fc} + A_{w} = 2 \times (309\ \text{mm}) \times (21.7\ \text{mm}) + 3830.9\ \text{mm}^{2} = 17241\ \text{mm}^{2} [math]
[math] k_{w} = \frac{A_{w}}{A} = \frac{3830.9}{17241} = 0.22219, \quad k_{f} = \frac{1 – k_{w}}{2} = \frac{1 – 0.22219}{2} = 0.38891 [math]
[math] N_{ft}^{*} = \frac{M_{x}^{*}}{d_{c} – t_{fc}} + k_{f}\, N_{t}^{*} = \frac{173.88\ \text{kN m}}{321\ \text{mm} – 21.7\ \text{mm}} + 0.38891 \times (1323\ \text{kN}) = 1095.5\ \text{kN} [math]
With the ends in full contact, the compression flange force on the bolts is [mathin] N_{fc}^{*} = 0 [mathin]. The flange bolts must still carry their share of the minimum compression:
[math] N_{fb}^{*} = k_{f}\, N_{c,min}^{*} = 0.38891 \times (661.5\ \text{kN}) = 257.26\ \text{kN} [math]
[math] N_{f}^{*} = \max\left( N_{ft}^{*},\ N_{fb}^{*} \right) = \max\left( 1095.5\ \text{kN},\ 257.26\ \text{kN} \right) = 1095.5\ \text{kN} [math]
This flange force, [mathin] N_{f}^{*} = 1095.5\ \text{kN} [mathin] (1095.48 kN in the summary), is the design action effect for every flange check. The web checks use the shear and the web share of the axial force, worked out in Step 10.
Step 1: Flange plate detailing limitations (AS 4100 Clause 9.5)
The minimum pitch is [mathin] 2.5\, d_{f} = 2.5 \times 24\ \text{mm} = 60\ \text{mm} [mathin] and the minimum edge distance for an M24 bolt is [mathin] 1.75\, d_{f} = 42\ \text{mm} [mathin] from Table 9.5.2. The maximum edge distance is the lesser of 12 times the plate thickness and 150 mm, and the maximum bolt column pitch is 200 mm. The report lists the 164 mm maximum row pitch as the software’s limit.
| Detailing limit (flange plate) | Limit (mm) | Actual (mm) | DCR | Result |
|---|---|---|---|---|
| Minimum bolt row pitch on flange plate | 60.000 | 75.000 | 0.800 | PASS |
| Maximum bolt row pitch on flange plate | 164.000 | 75.000 | 0.457 | PASS |
| Minimum bolt column pitch on flange plate | 60.000 | 190.000 | 0.316 | PASS |
| Maximum bolt column pitch on flange plate | 200.000 | 190.000 | 0.950 | PASS |
| Minimum horizontal edge distance on flange plate | 42.000 | 55.000 | 0.764 | PASS |
| Minimum horizontal edge distance on column flange | 42.000 | 59.500 | 0.706 | PASS |
| Minimum vertical edge distance on flange plate | 42.000 | 50.000 | 0.840 | PASS |
| Minimum vertical edge distance on column flange | 42.000 | 45.000 | 0.933 | PASS |
| Maximum edge distance | 150.000 | 55.000 | 0.367 | PASS |
For a minimum limit the ratio is limit over actual, and for a maximum it is actual over limit. The governing row is the 190 mm gauge against the 200 mm maximum:
[math] DCR = \frac{190\ \text{mm}}{200\ \text{mm}} = 0.95 [math]
DCR = 190 mm / 200 mm = 0.950 ≤ 1.0, OK
Step 2: Flange bolt group in shear (AS 4100 Clauses 9.2.2.1 and 9.3.1)
The flange force passes from the column flange to the flange plate through the bolts in single shear. The bolt group is a long lap joint, seven rows at 75 mm, so the bolt capacity is reduced for the length of the joint:
[math] l_{j} = \left( n_{p} – 1 \right) s_{p} = (7 – 1) \times (75\ \text{mm}) = 450\ \text{mm} [math]
[math] k_{r} = 1.075 – \frac{l_{j}}{4000\ \text{mm}} = 1.075 – \frac{450\ \text{mm}}{4000\ \text{mm}} = 0.9625 [math]
The threads are included in the one shear plane, so the core area is used:
[math] \phi V_{f} = \phi\, 0.62\, f_{uf}\, k_{rd}\, k_{r} \left( n_{n} A_{c} + n_{x} A_{o} \right) = 0.8 \times 0.62 \times (830\ \text{MPa}) \times 1 \times 0.9625 \times \left( 1 \times 324\ \text{mm}^{2} + 0 \times 452.39\ \text{mm}^{2} \right) = 128.38\ \text{kN} [math]
[math] \phi V_{df} = n_{b}\, \phi V_{f} = 14 \times (128.38\ \text{kN}) = 1797.4\ \text{kN} [math]
[math] N_{f}^{*} = 1095.5\ \text{kN} \le \phi V_{df} = 1797.4\ \text{kN} [math]
DCR = 1095.5 kN / 1797.4 kN = 0.609 ≤ 1.0, OK
Step 3: Flange bolts in bearing on the flange plate and column flange (AS 4100 Clause 9.2.2.4)
Each ply is checked at the end bolts, using the distance to the end of the ply, and at the inner bolts, using the distance to the next hole. With [mathin] \phi = 0.9 [mathin], the bearing capacity of a bolt on a ply is:
[math] \phi V_{b} = \phi\, \min\left( 3.2\, d_{f}\, t_{p}\, f_{up},\ a_{e}\, t_{p}\, f_{up} \right) [math]
For the flange plate, at the end bolts and the inner bolts:
[math] a_{e1} = 50\ \text{mm} – 13\ \text{mm} + 12\ \text{mm} = 49\ \text{mm}, \quad \phi V_{b} = 0.9 \min\left( 3.2 \times 24 \times 16 \times 430,\ 49 \times 16 \times 430 \right) = 303.41\ \text{kN} [math]
[math] a_{e2} = 75\ \text{mm} – 26\ \text{mm} + 12\ \text{mm} = 61\ \text{mm}, \quad \phi V_{b} = 377.71\ \text{kN} [math]
[math] \phi V_{b,p} = 2 \left[ 303.41\ \text{kN} + 6 \times 377.71\ \text{kN} \right] = 5139.4\ \text{kN} [math]
For the column flange, 21.7 mm thick with 440 MPa tensile strength:
[math] a_{e3} = 45\ \text{mm} – 13\ \text{mm} + 12\ \text{mm} = 44\ \text{mm}, \quad \phi V_{b} = 378.1\ \text{kN}; \quad a_{e4} = 61\ \text{mm}, \quad \phi V_{b} = 524.19\ \text{kN} [math]
[math] \phi V_{b,f} = 2 \left[ 378.1\ \text{kN} + 6 \times 524.19\ \text{kN} \right] = 7046.4\ \text{kN} [math]
[math] \phi V_{b} = \min\left( 5139.4\ \text{kN},\ 7046.4\ \text{kN} \right) = 5139.4\ \text{kN} [math]
DCR = 1095.5 kN / 5139.4 kN = 0.213 ≤ 1.0, OK
Step 4: Flange plate in block shear (AS 4100 Clause 9.1.9)
Three tear-out patterns are checked, with [mathin] \phi = 0.75 [mathin] and [mathin] k_{bs} = 1 [mathin] for a uniform tension stress:
[math] \phi R_{bs} = \phi\, \min\left( 0.6\, f_{u}\, A_{nv} + k_{bs}\, f_{u}\, A_{nt},\ 0.6\, f_{y}\, A_{gv} + k_{bs}\, f_{u}\, A_{nt} \right) [math]
Patterns 1 and 2 shear along both bolt lines, over the end distance and the length of the joint:
[math] A_{gv} = 2 \left[ 50\ \text{mm} + 450\ \text{mm} \right] \times 16\ \text{mm} = 16000\ \text{mm}^{2}, \quad A_{nv} = 2 \left[ 50 + 450 – 6.5 \times 26 \right] \times 16 = 10592\ \text{mm}^{2} [math]
Pattern 1 (U pattern) tears across the plate between the two bolt lines, and pattern 2 (2L pattern) tears out to both plate edges:
[math] A_{nt,1} = \left[ 190\ \text{mm} – 26\ \text{mm} \right] \times 16\ \text{mm} = 2624\ \text{mm}^{2}, \quad \phi R_{bs,1} = 2895.8\ \text{kN} [math]
[math] A_{nt,2} = \left( 2 \times 55\ \text{mm} – 26\ \text{mm} \right) \times 16\ \text{mm} = 1344\ \text{mm}^{2}, \quad \phi R_{bs,2} = 2483\ \text{kN} [math]
Pattern 3 (L pattern) shears along one bolt line and tears across both lines to one edge:
[math] A_{nt,3} = \left[ 55 + 190 – 1.5 \times 26 \right] \times 16 = 3296\ \text{mm}^{2}, \quad A_{gv} = 8000\ \text{mm}^{2}, \quad A_{nv} = 5296\ \text{mm}^{2} [math]
[math] \phi R_{bs,3} = 0.75 \min\left( 0.6 \times 430 \times 5296 + 430 \times 3296,\ 0.6 \times 300 \times 8000 + 430 \times 3296 \right) = 2087.7\ \text{kN} [math]
DCR = 1095.5 kN / 2087.7 kN = 0.525 ≤ 1.0, OK
Step 5: Column flange in block shear (AS 4100 Clause 9.1.9)
The column flange can tear out from its two edges around the bolt group, shearing along both bolt lines from the column end:
[math] A_{nt} = \left( 2 \times 59.5\ \text{mm} – 26\ \text{mm} \right) \times 21.7\ \text{mm} = 2018.1\ \text{mm}^{2} [math]
[math] A_{gv} = 2 \left[ 45 + 450 \right] \times 21.7 = 21483\ \text{mm}^{2}, \quad A_{nv} = 2 \left[ 45 + 450 – 6.5 \times 26 \right] \times 21.7 = 14148\ \text{mm}^{2} [math]
[math] \phi R_{bs} = 0.75 \min\left( 0.6 \times 440 \times 14148 + 440 \times 2018.1,\ 0.6 \times 280 \times 21483 + 440 \times 2018.1 \right) = 3372.8\ \text{kN} [math]
DCR = 1095.5 kN / 3372.8 kN = 0.325 ≤ 1.0, OK
Step 6: Flange plate in tension (AS 4100 Clauses 7.2 and 9.1.10)
The flange plate carries the full flange force in tension across its gross section and across a bolt row, with [mathin] k_{t} = 1 [mathin] (Clause 7.3):
[math] A_{g} = 300\ \text{mm} \times 16\ \text{mm} = 4800\ \text{mm}^{2}, \quad A_{n} = \left( 300\ \text{mm} – 2 \times 26\ \text{mm} \right) \times 16\ \text{mm} = 3968\ \text{mm}^{2} [math]
[math] \phi N_{t} = \phi\, \min\left( A_{g}\, f_{yp},\ 0.85\, k_{t}\, A_{n}\, f_{up} \right) = 0.9 \min\left( 4800 \times 300,\ 0.85 \times 1 \times 3968 \times 430 \right) = 1296\ \text{kN} [math]
[math] N_{f}^{*} = 1095.5\ \text{kN} \le \phi N_{t} = 1296\ \text{kN} [math]
DCR = 1095.5 kN / 1296 kN = 0.845 ≤ 1.0, OK
This is the governing strength check of the splice. Gross yielding governs, so a wider or thicker flange plate is the direct way to raise it.
Step 7: Column flange in tension (AS 4100 Clauses 7.2 and 9.1.10)
[math] A_{g} = 309\ \text{mm} \times 21.7\ \text{mm} = 6705.3\ \text{mm}^{2}, \quad A_{n} = \left( 309\ \text{mm} – 52\ \text{mm} \right) \times 21.7\ \text{mm} = 5576.9\ \text{mm}^{2} [math]
[math] \phi N_{t} = 0.9 \min\left( 6705.3 \times 280,\ 0.85 \times 5576.9 \times 440 \right) = 1689.7\ \text{kN} [math]
DCR = 1095.5 kN / 1689.7 kN = 0.648 ≤ 1.0, OK
Step 8: Section moment capacity of the column at the flange holes (AS 4100 Clauses 5.2 and 8.3.2)
The bolt holes in the column flanges reduce the section where the splice moment is carried, so the column is checked there for the design moment, reduced for the axial force. First, the elastic section modulus of the column:
[math] Z_{x} = \frac{b_{fc}\, d_{c}^{3} – \left( b_{fc} – t_{wc} \right) \left( d_{c} – 2\, t_{fc} \right)^{3}}{6\, d_{c}} = 2.0278 \times 10^{6}\ \text{mm}^{3} [math]
Clause 5.2.6 checks whether the holes reduce the flange enough to matter:
[math] \Delta A_{f} = 100\, \frac{n_{g}\, d_{h}}{b_{fc}} = 100 \times \frac{2 \times 26\ \text{mm}}{309\ \text{mm}} = 16.828 \le \Delta A_{lim} = 100 \left( 1 – \frac{f_{yc}}{0.85\, f_{uc}} \right) = 25.134 [math]
So the gross section moduli are used. For the section slenderness (Clause 5.2.2 and Table 5.2):
[math] \lambda_{ef} = \frac{147.6\ \text{mm}}{21.7\ \text{mm}} \sqrt{\frac{280}{250}} = 7.1984, \quad \lambda_{ew} = \frac{277.6\ \text{mm}}{13.8\ \text{mm}} \sqrt{\frac{280}{250}} = 21.289 [math]
The flange outstand limits are [mathin] \lambda_{ep} = 9,\ \lambda_{ey} = 16 [mathin] (hot-rolled) and the web limits [mathin] 82,\ 115 [mathin]. The flange ratio, 7.2/16 = 0.45, is higher than the web’s, 0.19, so the flange sets the section slenderness, and [mathin] \lambda_{s} = 7.1984 \le \lambda_{sp} = 9 [mathin]: the section is compact (Clause 5.2.3).
[math] Z_{e} = \min\left( S_{x},\ 1.5\, Z_{x} \right) = \min\left( 2.3 \times 10^{6},\ 1.5 \times 2.0278 \times 10^{6} \right) = 2.3 \times 10^{6}\ \text{mm}^{3} [math]
[math] \phi M_{s} = \phi\, f_{yc}\, Z_{e} = 0.9 \times (280\ \text{MPa}) \times (2.3 \times 10^{6}\ \text{mm}^{3}) = 579.6\ \text{kN m} [math]
The axial capacities use the net section at the flange holes and the nearest line of web holes:
[math] A_{n} = A_{g} – 2\, n_{g}\, d_{h}\, t_{fc} = 17500 – 2 \times 2 \times 26 \times 21.7 = 15243\ \text{mm}^{2}, \quad A_{nw} = A_{n} – n_{p}\, d_{h}\, t_{wc} = 15243 – 3 \times 26 \times 13.8 = 14167\ \text{mm}^{2} [math]
[math] \phi N_{t} = 0.9 \min\left( 17500 \times 280,\ 0.85 \times 1 \times 14167 \times 440 \right) = 4410\ \text{kN} [math]
In compression the bolt holes are filled, so no hole reduction is made. The effective widths equal the clear widths, [mathin] b_{ef} = 147.6\ \text{mm} [mathin] and [mathin] b_{ew} = 277.6\ \text{mm} [mathin] (Clause 6.2.4), so [mathin] A_{e} = 17500\ \text{mm}^{2} [mathin] and [mathin] k_{f} = 1 [mathin]:
[math] \phi N_{s} = \phi\, k_{f}\, A_{g}\, f_{yc} = 0.9 \times 1 \times (17500\ \text{mm}^{2}) \times (280\ \text{MPa}) = 4410\ \text{kN} [math]
Clause 8.3.2(a) then reduces the moment capacity for the axial tension and, separately, for the axial compression entered:
[math] \phi M_{rx,t} = \min\left[ 1.18\, \phi M_{s} \left( 1 – \frac{N_{t}^{*}}{\phi N_{t}} \right),\ \phi M_{s} \right] = \min\left[ 1.18 \times 579.6 \times \left( 1 – \frac{1323}{4410} \right),\ 579.6 \right] = 478.75\ \text{kN m} [math]
[math] \phi M_{rx,c} = \min\left[ 1.18 \times 579.6 \times \left( 1 – \frac{1062}{4410} \right),\ 579.6 \right] = 519.23\ \text{kN m} [math]
[math] \phi M_{rx} = \min\left( 478.75\ \text{kN m},\ 519.23\ \text{kN m} \right) = 478.75\ \text{kN m} [math]
DCR = 173.88 kN m / 478.75 kN m = 0.363 ≤ 1.0, OK
Step 9: Web plate detailing limitations (AS 4100 Clause 9.5)
The same 60 mm minimum pitch and 42 mm minimum edge distance apply. The maximum edge distance is 12 times the 12 mm web plate, 144 mm, and the web plates must fit on the flat of the column web between the root radii, 244.6 mm. The report lists the 148 mm maximum row pitch as the software’s limit.
| Detailing limit (web plates) | Limit (mm) | Actual (mm) | DCR | Result |
|---|---|---|---|---|
| Minimum bolt row pitch on web plate | 60.000 | 75.000 | 0.800 | PASS |
| Maximum bolt row pitch on web plate | 148.000 | 75.000 | 0.507 | PASS |
| Minimum horizontal edge distance on web plate | 42.000 | 45.000 | 0.933 | PASS |
| Minimum vertical edge distance on web plate | 42.000 | 45.000 | 0.933 | PASS |
| Minimum vertical edge distance on column web | 42.000 | 45.000 | 0.933 | PASS |
| Maximum edge distance | 144.000 | 45.000 | 0.313 | PASS |
| Maximum web plate depth | 244.600 | 240.000 | 0.981 | PASS |
[math] DCR = \frac{240\ \text{mm}}{244.6\ \text{mm}} = 0.98119 [math]
DCR = 240 mm / 244.6 mm = 0.981 ≤ 1.0, OK
This ratio is high because the 240 mm plate fills almost all of the flat of the web. It is a fit limit, not a strength problem.
Step 10: Web bolt group in shear (AS 4100 Clauses 9.1.4, 9.1.3, 9.2.2.1 and 9.3.1)
Clause 9.1.4 also sets a minimum design shear for the splice, 0.15 times the shear capacity of the column, but not less than 40 kN:
[math] \phi V_{vo} = \phi\, 0.6\, f_{yc}\, d_{c}\, t_{wc} = 0.9 \times 0.6 \times (280\ \text{MPa}) \times (321\ \text{mm}) \times (13.8\ \text{mm}) = 669.79\ \text{kN} [math]
[math] V_{min}^{*} = \max\left( 0.15 \times 669.79\ \text{kN},\ 40\ \text{kN} \right) = 100.47\ \text{kN}, \quad V_{w}^{*} = \max\left( 165\ \text{kN},\ 100.47\ \text{kN} \right) = 165\ \text{kN} [math]
The web takes its share of the axial force, [mathin] k_{w} = 0.22219 [mathin]. With the ends in full contact [mathin] N_{wc}^{*} = 0 [mathin], and the minimum compression on the web bolts is checked as well:
[math] N_{wt}^{*} = k_{w}\, N_{t}^{*} = 0.22219 \times (1323\ \text{kN}) = 293.96\ \text{kN}, \quad N_{wb}^{*} = k_{w}\, N_{c,min}^{*} = 146.98\ \text{kN} [math]
[math] N_{w}^{*} = 293.96\ \text{kN}, \quad R_{w}^{*} = \sqrt{V_{w}^{*2} + N_{w}^{*2}} = \sqrt{165^{2} + 293.96^{2}} = 337.1\ \text{kN} [math]
The resultant acts at 60.69° from the horizontal. Either sense of the axial force gives the same result, as the bolt group is symmetric. Each bolt passes through both web plates, so it is in double shear:
[math] \phi V_{f} = 0.8 \times 0.62 \times (830\ \text{MPa}) \times 1 \times 1 \times \left( 2 \times 324\ \text{mm}^{2} + 0 \right) = 266.77\ \text{kN} [math]
The bolt group capacity is found by the instantaneous centre of rotation method. The resultant acts at the centre of the splice, at [mathin] e_{d} = c/2 + l_{ev\_w} = 0 + 45\ \text{mm} = 45\ \text{mm} [mathin] from the line of web bolts. The bolt coordinates, with x along the column and y across it:
| Bolt | x (mm) | y (mm) |
|---|---|---|
| 1 | 0.00 | 0.00 |
| 2 | 0.00 | 75.00 |
| 3 | 0.00 | 150.00 |
The instantaneous centre, found by iteration, is at [mathin] x_{ic} = -33.432\ \text{mm} [mathin] and [mathin] y_{ic} = 163.49\ \text{mm} [mathin] from bolt 1. The bolt reactions are:
| Bolt | R (kN) | Rx (kN) | Ry (kN) | Mn (kN-mm) |
|---|---|---|---|---|
| 1 | 261.83 | 256.52 | 52.46 | 43691.83 |
| 2 | 244.65 | 228.87 | 86.47 | 23141.81 |
| 3 | 186.18 | 69.65 | 172.67 | 6711.55 |
[math] \sum R_{x} = 555.04\ \text{kN}, \quad \sum R_{y} = 311.59\ \text{kN}, \quad \phi V_{df} = \sqrt{555.04^{2} + 311.59^{2}} = 636.52\ \text{kN} [math]
[math] C = \frac{\phi V_{df}}{\phi V_{f}} = \frac{636.52}{266.77} = 2.386 [math]
DCR = 337.1 kN / 636.52 kN = 0.530 ≤ 1.0, OK
Step 11: Web bolts in bearing on the web plates and column web (AS 4100 Clauses 9.2.2.4 and 9.3.1)
The bolt forces from the ICOR analysis act in different directions, so the least distance in either direction governs each ply. For the web plates the distances are 44 mm to the plate edges, 61 mm to the adjacent hole and 76 mm to the hole across the splice, so 44 mm governs. Each bolt bears on both web plates:
[math] \phi V_{b,wp} = 2 \times 0.9 \min\left( 3.2 \times 24 \times 12 \times 430,\ 44 \times 12 \times 430 \right) = 408.67\ \text{kN} [math]
For the column web the distances are 44 mm to the column end and 61 mm to the adjacent hole:
[math] \phi V_{b,w} = 0.9 \min\left( 3.2 \times 24 \times 13.8 \times 440,\ 44 \times 13.8 \times 440 \right) = 240.45\ \text{kN} [math]
[math] \phi V_{b} = \min\left( \phi V_{b,wp},\ \phi V_{b,w} \right) C = 240.45\ \text{kN} \times 2.386 = 573.72\ \text{kN} [math]
DCR = 337.1 kN / 573.72 kN = 0.588 ≤ 1.0, OK
Step 12: Web plates in tension (AS 4100 Clauses 7.2 and 9.1.10)
[math] A_{g} = 2 \times 240\ \text{mm} \times 12\ \text{mm} = 5760\ \text{mm}^{2}, \quad A_{n} = 2 \left( 240\ \text{mm} – 3 \times 26\ \text{mm} \right) \times 12\ \text{mm} = 3888\ \text{mm}^{2} [math]
[math] \phi N_{t} = 0.9 \min\left( 5760 \times 310,\ 0.85 \times 3888 \times 430 \right) = 1279\ \text{kN} [math]
DCR = 293.96 kN / 1279 kN = 0.230 ≤ 1.0, OK
Step 13: Web plates in bending (AS 4100 Clauses 9.1.3, 5.2 and 8.3.2)
The web shear acts at the centre of the splice, so the web plates carry a moment at the bolt group:
[math] M_{w}^{*} = V_{w}^{*}\, e_{d} = 165\ \text{kN} \times 45\ \text{mm} = 7.425\ \text{kN m} [math]
[math] S_{i} = \frac{t_{i}\, d_{i}^{2}}{4} = \frac{12 \times 240^{2}}{4} = 172800\ \text{mm}^{3}, \quad Z_{i} = \frac{t_{i}\, d_{i}^{2}}{6} = 115200\ \text{mm}^{3} [math]
The plate slenderness is [mathin] \lambda_{s} = \frac{240}{12} \sqrt{\frac{310}{250}} = 22.271 \le \lambda_{sp} = 82 [mathin], so the plate is compact and [mathin] Z_{ei} = \min\left( S_{i},\ 1.5\, Z_{i} \right) = 172800\ \text{mm}^{3} [mathin].
[math] \phi M_{wd} = 2\, \phi\, f_{yp}\, Z_{ei} = 2 \times 0.9 \times (310\ \text{MPa}) \times (172800\ \text{mm}^{3}) = 96.422\ \text{kN m} [math]
[math] \phi M_{wr} = \phi M_{wd} \left( 1 – \frac{N_{wt}^{*}}{\phi N_{t}} \right) = 96.422 \times \left( 1 – \frac{293.96}{1279} \right) = 74.261\ \text{kN m} [math]
DCR = 7.425 kN m / 74.261 kN m = 0.100 ≤ 1.0, OK
Step 14: Web plates in shear (AS 4100 Clauses 5.11.3 and 5.12.3)
The shear stress in a solid rectangular plate is not uniform, so Clause 5.11.3 gives the capacity on 0.5 fy:
[math] \phi V_{vd} = 2 \times 0.9 \times 0.5 \times (310\ \text{MPa}) \times (240\ \text{mm}) \times (12\ \text{mm}) = 803.52\ \text{kN} [math]
Under Clause 5.12.3, [mathin] M_{w}^{*} = 7.42\ \text{kN m} \le 0.75\, \phi M_{wd} = 72.32\ \text{kN m} [mathin], so the shear capacity is not reduced for bending.
DCR = 165 kN / 803.52 kN = 0.205 ≤ 1.0, OK
Step 15: Web plates in block shear (AS 4100 Clause 9.1.9)
Under the shear, each web plate can tear out along the line of bolts and across to its edge (L pattern):
[math] A_{nt} = \left[ 45\ \text{mm} – 13\ \text{mm} \right] \times 12\ \text{mm} = 384\ \text{mm}^{2}, \quad A_{gv} = 195\ \text{mm} \times 12\ \text{mm} = 2340\ \text{mm}^{2}, \quad A_{nv} = \left[ 195 – 65 \right] \times 12 = 1560\ \text{mm}^{2} [math]
[math] \phi R_{bs} = 2 \times 0.75 \min\left( 0.6 \times 430 \times 1560 + 430 \times 384,\ 0.6 \times 310 \times 2340 + 430 \times 384 \right) = 851.4\ \text{kN} [math]
DCR = 165 kN / 851.4 kN = 0.194 ≤ 1.0, OK
Step 16: Web plates in block shear under axial tension (AS 4100 Clause 9.1.9)
Under the web tension the plates can tear out along the outer bolt rows, either between them (pattern 1) or to the plate edges (pattern 2):
[math] A_{gv} = 2 \times 45\ \text{mm} \times 12\ \text{mm} = 1080\ \text{mm}^{2}, \quad A_{nv} = 2 \times 32\ \text{mm} \times 12\ \text{mm} = 768\ \text{mm}^{2} [math]
[math] A_{nt,1} = \left[ 150 – 52 \right] \times 12 = 1176\ \text{mm}^{2}, \quad \phi R_{bs,1} = 1055.7\ \text{kN} [math]
[math] A_{nt,2} = \left( 90 – 26 \right) \times 12 = 768\ \text{mm}^{2}, \quad \phi R_{bs,2} = 792.58\ \text{kN} [math]
DCR = 293.96 kN / 792.58 kN = 0.371 ≤ 1.0, OK
Step 17: Column web in block shear under axial tension (AS 4100 Clause 9.1.9)
[math] A_{gv} = 2 \times 45 \times 13.8 = 1242\ \text{mm}^{2}, \quad A_{nv} = 883.2\ \text{mm}^{2}, \quad A_{nt} = \left[ 150 – 52 \right] \times 13.8 = 1352.4\ \text{mm}^{2} [math]
[math] \phi R_{bs} = 0.75 \min\left( 0.6 \times 440 \times 883.2 + 440 \times 1352.4,\ 0.6 \times 280 \times 1242 + 440 \times 1352.4 \right) = 602.78\ \text{kN} [math]
DCR = 293.96 kN / 602.78 kN = 0.488 ≤ 1.0, OK
Summary of checks
The results for the lower column are below. The upper column gives the same values.
| Design check | Design action effect | Design capacity | DCR | Result |
|---|---|---|---|---|
| Flange: detailing limitations | 190 mm | 200 mm | 0.950 | PASS |
| Flange: bolt group in shear | 1095.48 kN | 1797.35 kN | 0.609 | PASS |
| Flange: bolt bearing on flange plate and column flange | 1095.48 kN | 5139.36 kN | 0.213 | PASS |
| Flange plate in block shear | 1095.48 kN | 2087.74 kN | 0.525 | PASS |
| Column flange in block shear | 1095.48 kN | 3372.83 kN | 0.325 | PASS |
| Flange plate in tension | 1095.48 kN | 1296 kN | 0.845 | PASS |
| Column flange in tension | 1095.48 kN | 1689.74 kN | 0.648 | PASS |
| Column section moment capacity at the flange holes | 173.88 kN m | 478.75 kN m | 0.363 | PASS |
| Web: detailing limitations | 240 mm | 244.6 mm | 0.981 | PASS |
| Web: bolt group in shear | 337.099 kN | 636.519 kN | 0.530 | PASS |
| Web: bolt bearing on web plates and column web | 337.099 kN | 573.725 kN | 0.588 | PASS |
| Web plates in tension | 293.957 kN | 1278.96 kN | 0.230 | PASS |
| Web plates in bending | 7.425 kN m | 74.2606 kN m | 0.100 | PASS |
| Web plates in shear | 165 kN | 803.52 kN | 0.205 | PASS |
| Web plates in block shear | 165 kN | 851.4 kN | 0.194 | PASS |
| Web plates in block shear under axial tension | 293.957 kN | 792.576 kN | 0.371 | PASS |
| Column web in block shear under axial tension | 293.957 kN | 602.784 kN | 0.488 | PASS |
The splice passes every check. The highest ratio, 0.981, is the web plate depth against the flat of the column web, a fit limit rather than a strength check. Of the checks that compare a design action with a design capacity, the flange plate in tension governs at 0.845, followed by the column flange in tension at 0.648. The flange force behind these is the raised Clause 9.1.4 minimum, not the 160 kN m entered.
Auto Design is available for the column splice with flange and web plates in the AS 4100 module. It changes the bolts and plates until every check passes, and keeps your columns and design actions as entered. See the Auto Design page for the AS 4100 preferences it works to.
What to change if a check fails
- Detailing limits: adjust the pitch, gauge or edge distances to the limits in Steps 1 and 9. If the web plates are too deep for the flat of the web, use fewer rows across the web or a smaller pitch.
- Flange bolt group in shear or bearing: add bolt rows, use a larger bolt or a higher grade. A longer joint lowers k_r once it passes 300 mm, so extra rows add a little less than their share.
- Flange plate in tension or block shear: use a wider or thicker flange plate, or a higher grade.
- Column flange in tension or block shear, or the moment at the holes: these depend on the column, so reduce the holes (smaller bolts or a narrower gauge) or use a heavier section.
- Web bolt group: add a bolt row across the web, or use a larger bolt.
- Web plates: use thicker or deeper plates, within the flat of the web.
Frequently asked questions
Why is the design moment 173.88 kN m when 160 kN m was entered?
Clause 9.1.4 asks for a splice to be designed for at least 0.3 times the design section capacity of the member. For the 310 UC 137 that is 0.3 x 0.9 x 280 MPa x 2.3 x 10⁶ mm³ = 173.88 kN m, which is more than the 160 kN m entered. The axial tension is raised the same way, from 1062 kN to 1323 kN.
What does full contact change?
With the ends prepared for full contact, the compression passes from column to column in bearing. The compression flange force on the bolts is then zero, and the bolts are only checked for a minimum compression of 0.15 times the column’s capacity (661.5 kN). That is why the report has no flange plate or web plate compression checks for this splice.
Why do the flanges carry most of the axial force?
Clause 9.1.3 lets the axial force be shared between the flanges and the web in proportion to their areas. For the 310 UC 137 each flange has 38.9% of the area and the web 22.2%, so each flange takes 0.38891 of the axial force on top of its share of the moment couple.
Why are the web bolts designed for a 45 mm eccentricity?
The web shear is taken at the centre of the splice, and the web bolts on each column sit 45 mm from the column end. The instantaneous centre method finds a coefficient C of 2.386 for the three bolts under the combined shear, axial force and moment, rather than three times the single bolt capacity.
Is the upper column checked?
Yes. The report runs every check for the upper column as well. Here both columns are the same section with the same bolts, so the results are identical.
Design a column splice for free
Every number on this page comes from one solve. Pick AS 4100:2020 and the column splice, enter your columns, plates, bolts and design actions, and see each of these checks in your browser. There is nothing to install.
The SkyCiv Connection Design module is the connection design software behind this example. It gives you the full calculation report with every equation and your numbers in it, like the steps above, plus every design capacity and DCR, for AS 4100:2020 shear connections, moment connections and splices. The bolt calculator and weld calculator cover the bolt group and weld checks on their own.
References
- AS 4100:2020, Steel Structures: Clauses 5.2.1, 5.2.2, 5.2.3, 5.2.6, 5.11.2, 5.11.3, 5.12.3, 6.2.1, 6.2.2, 6.2.4, 7.2, 7.3, 8.3.2, 9.1.3, 9.1.4, 9.1.9, 9.1.10, 9.2.2.1, 9.2.2.4, 9.3.1, 9.5; Tables 5.2, 6.2.4 and 9.5.2.
- Design of steel connections using AS 4100:2020
- Auto Design in SkyCiv Connection Design