A bolt in a shear connection designed to AS 4100:2020 is checked twice: once for the bolt itself shearing through (Clause 9.2.2.1) and once for the plies it passes through, which can bear or tear out at the holes (Clause 9.2.2.4). If the bolts are fully tensioned friction-type bolts (8.8/TF or 10.9/TF), a third check under Clause 9.2.3.1 makes sure the joint does not slip in service.

This page explains each of these checks and works them through with the same connection as our web side plate design example: eight M20 8.8/S bolts carrying 150 kN from a 460 UB 82.1 beam into a 10 plaque de mm. Every number comes from the calculation report that SkyCiv Connection Design produces for that connection.

Élévation de la plaque latérale: 460 UB 82.1 poutre, eight M20 8.8/S bolts at 75 mm pitch and gauge, V* = 150 kN

Which bolt checks does AS 4100 require in shear?

VérifierClauseApplies to
Boulon en cisaillement, [mathin]\phi V_{f}[mathin]9.2.2.1Every bolt category (4.6/S, 8.8/S, 8.8/tuberculose, 8.8/TF and the 10.9 ones)
Ply dans le roulement, [mathin]\phi V_{b}[mathin]9.2.2.4Every ply the bolt passes through: la plaque, the beam web, the support
Friction-type joint in service, [mathin]\phi V_{sf}[mathin]9.2.3.18.8/TF and 10.9/TF bolts

In a connection where the load is eccentric to the bolt group, the program finds the share of each bolt with the instantaneous centre of rotation method (Clause 9.3.1) and turns it into a bolt group coefficient C. The single-bolt capacities on this page are then multiplied by C. How C is found is covered step by step in calcul du groupe de boulons à l'aide d'ICOR.

Design inputs for the example

ArticleSymboleValeur
Cisaille de conception[mathin]V^{*}[mathin]150 kN
Boulons8 x M20 8.8/S, 4 lignes x 2 poteaux
Diamètre du boulon / hole diameter[mathin]d_{f},\ d_{h}[mathin]20 mm / 22 mm
Bolt minimum tensile strength[mathin]f_{uf}[mathin]830 MPa
Core area / aire de la tige[mathin]A_{c},\ A_{o}[mathin]225 mm2 / 314.16 mm2
Pas / jauge[mathin]s_{p},\ s_{g}[mathin]75 mm / 75 mm
Excentricité du groupe de boulons[mathin]e_{b}[mathin]107.5 mm
assiette[mathin]t_{i},\ f_{up}[mathin]10 mm Gr.250, 410 MPa
Distances aux bords des plaques, vertical / horizontal[mathin]l_{ev\_wp},\ l_{eh\_wp}[mathin]47.5 mm / 55 mm
Toile de poutre[mathin]t_{wb},\ f_{ub}[mathin]9.9 mm Gr.300, 440 MPa
Distance du bord horizontal de l'âme de la poutre[mathin]l_{eh\_w}[mathin]50 mm

Bolt shear capacity (Clause 9.2.2.1)

The design shear capacity of one bolt is:

[math]\phi V_{f} = \phi \times 0.62 \times f_{uf} \times k_{rd} \times k_{r} \times \left( n_{n} A_{c} + n_{x} A_{o} \right)[math]

avec [mathin]\phi = 0.8[mathin] for a bolt in shear. The terms that change from one connection to another are:

  • Threads in the shear plane, [mathin]n_{n}[mathin] et [mathin]n_{x}[mathin]. A shear plane through the threads uses the core area [mathin]A_{c}[mathin]; a plane through the plain shank uses the shank area [mathin]A_{o}[mathin]. For an M20 bolt that is 225 mm2 contre 314.16 mm2, so excluding the threads is worth 40% more capacity. The program accepts "threads excluded" only when a standard bolt length leaves the threads clear of the shear plane for the plies entered, and never for 4.6 boulons. Otherwise it designs with threads included.
  • Ductility factor [mathin]k_{rd}[mathin]. The program takes 0.83 pour 10.9 bolts with threads included in the shear plane, et 1.0 for every other case.
  • Lap length factor [mathin]k_{r}[mathin]. Long bolted lap joints lose capacity because the end bolts take more than their share. The program works out the joint length as [mathin]l_{j} = (n_{rows} – 1) s_{p}[mathin] along the force and applies:
Joint length[mathin]k_{r}[mathin]
[mathin]l_{j} \lt 300[mathin] mm1.0
300 mm à 1300 mm[mathin]1.075 – l_{j}/4000[mathin]
[mathin]l_{j} \gt 1300[mathin] mm0.75

The lap reduction is applied in flange plate connections and splices, where the force runs along a line of bolts. In beam shear connections such as the web side plate, the report shows [mathin]k_{r,bolt} = 1[mathin].

Étape 1: Capacité de cisaillement de conception d'un boulon

The 8.8/S bolts in the example have the threads in the single shear plane, donc [mathin]n_{n} = 1[mathin] et [mathin]n_{x} = 0[mathin]:

[math]\phi V_{f} = 0.8 \times 0.62 \times 830 \times 1 \times 1 \times \left( 1 \times 225 + 0 \times 314.16 \right) = 92.628\ \text{kN}[math]

Étape 2: Groupe de boulons en cisaillement (Clause 9.3.1)

Le 150 kN shear acts 107.5 mm from the centroid of the bolt group. The ICOR iteration places the instantaneous centre at [mathin]x_{ic} = -30.727\ \text{mm}[mathin] et [mathin]y_{ic} = 112.5\ \text{mm}[mathin] from Bolt No. 1 (bottom left). The vertical reactions of the eight bolts, each at its [mathin]\phi V_{f}[mathin] limite, add up to:

[math]\phi V_{df} = \sum R_{y} = 430.69\ \text{kN}, \qquad C = \frac{\phi V_{df}}{\phi V_{f}} = \frac{430.69}{92.628} = 4.6497[math]

DCR = 150 kN / 430.69 kN = 0.348 ≤ 1.0, d'accord

Étape 3: The same bolts with threads excluded

Switching the same input to threads excluded from the shear plane gives [mathin]n_{n} = 0[mathin] et [mathin]n_{x} = 1[mathin]:

[math]\phi V_{f} = 0.8 \times 0.62 \times 830 \times 1 \times 1 \times \left( 0 \times 225 + 1 \times 314.16 \right) = 129.33\ \text{kN}[math]

The bolt group capacity rises to [mathin]\phi V_{df} = 601.36\ \text{kN}[mathin], and the DCR drops from 0.348 à 0.249. The bearing checks below do not change, because they do not depend on the threads.

Ply bearing capacity (Clause 9.2.2.4)

A ply can fail at a bolt hole in two ways: the bolt crushes the material in front of it (portance), or the bolt tears out through the edge of the ply or into the next hole (arrachement). The program takes the smaller of the two:

[math]\phi V_{b} = \phi \times \min\left( 3.2\, d_{f}\, t_{p}\, f_{up},\ a_{e}\, t_{p}\, f_{up} \right)[math]

avec [mathin]\phi = 0.9[mathin] for a ply in bearing. [mathin]a_{e}[mathin] est la distance entre le bord du trou et le bord du pli, plus la moitié du diamètre du boulon, measured in the direction of the force:

  • to a free edge: [mathin]a_{e} = l_{e} – 0.5\, d_{h} + 0.5\, d_{f}[mathin]
  • to the next hole: [mathin]a_{e} = s – d_{h} + 0.5\, d_{f}[mathin]

When the bolt forces come from an ICOR analysis they act in different directions, so the program takes the least [mathin]a_{e}[mathin] in either direction for each ply.

Étape 4: Appui sur la plaque latérale de l'âme

[math]a_{e1} = 47.5 – 0.5 \times 22 + 0.5 \times 20 = 46.5\ \text{mm} \qquad a_{e2} = 75 – 22 + 0.5 \times 20 = 63\ \text{mm}[math]

[math]a_{e3} = 55 – 0.5 \times 22 + 0.5 \times 20 = 54\ \text{mm} \qquad a_{e4} = 75 – 22 + 0.5 \times 20 = 63\ \text{mm}[math]

The vertical edge distance governs, [mathin]a_{e} = 46.5\ \text{mm}[mathin]:

[math]\phi V_{b,pl} = 0.9 \times \min\left( 3.2 \times 20 \times 10 \times 410,\ 46.5 \times 10 \times 410 \right) = 171.59\ \text{kN}[math]

Tear-out governs here: [mathin]3.2 d_{f} = 64\ \text{mm}[mathin] is more than the 46.5 mm available.

Étape 5: Appui sur l'âme de la poutre

The beam web has no vertical free edge near the bolts, so only the pitch, the horizontal edge and the gauge count:

[math]a_{e5} = 75 – 22 + 0.5 \times 20 = 63\ \text{mm} \qquad a_{e6} = 50 – 0.5 \times 22 + 0.5 \times 20 = 49\ \text{mm} \qquad a_{e7} = 63\ \text{mm}[math]

[math]\phi V_{b,beam} = 0.9 \times \min\left( 3.2 \times 20 \times 9.9 \times 440,\ 49 \times 9.9 \times 440 \right) = 192.1\ \text{kN}[math]

Étape 6: Bolt group in bearing

The weaker ply governs, and the same coefficient C spreads it over the group:

[math]\phi V_{b} = \min\left( 171.59,\ 192.1 \right) \times 4.6497 = 797.82\ \text{kN}[math]

DCR = 150 kN / 797.82 kN = 0.188 ≤ 1.0, d'accord

Bolt shear governs this connection by a wide margin (0.348 contre 0.188). That is typical for 8.8 bolts in 10 mm plates; bearing tends to govern with thin plies, short edge distances or 10.9 boulons.

Friction-type bolts: aptitude au service (Clause 9.2.3.1)

With 8.8/TF bolts the joint is meant not to slip at the serviceability limit state. The report adds a check of the slip capacity of the bolt group:

[math]\phi V_{sf} = \phi\, \mu\, n_{ei}\, N_{ti}\, k_{h}\, C[math]

avec [mathin]\phi = 0.7[mathin], the slip factor [mathin]\mu = 0.35[mathin], [mathin]n_{ei}[mathin] the number of effective interfaces, [mathin]N_{ti}[mathin] the minimum bolt tension at installation (Tableau 15.2.2.2) et [mathin]k_{h}[mathin] the hole type factor, 1.0 for standard holes and 0.85 for oversize or short slotted holes. Changing the example’s bolts to M20 8.8/TF:

[math]\phi V_{sf} = 0.7 \times 0.35 \times 1 \times 145 \times 1 \times 4.6497 = 165.18\ \text{kN}[math]

DCR = 150 kN / 165.18 kN = 0.908 ≤ 1.0, d'accord

The strength checks of Steps 1 à 6 still apply to TF bolts unchanged. The serviceability check uses the design shear entered for the connection, so if your serviceability shear is lower than the strength one, the DCR shown is on the safe side.

Summary of the bolt checks

CasVérifierCapacitéDCR
8.8/S, fils inclusGroupe de boulons en cisaillement430.69 kN0.348
8.8/S, sujets exclusGroupe de boulons en cisaillement601.36 kN0.249
N'importe lequelBolt group in bearing (plate governs)797.82 kN0.188
8.8/TFSlip in service165.18 kN0.908

What to change if a bolt check fails

  • Cisaille à boulon: ajouter une rangée de boulons (it raises C), use M24 bolts or a 10.9 classe, keep the threads out of the shear plane if the bolt length allows, or move the bolts closer to the support to cut the eccentricity.
  • Bearing on a ply: increase the edge distance in the direction of the force, increase the pitch, or use a thicker ply. Si l'âme de la poutre gouverne, ajoutez des boulons ou utilisez un boulon plus gros.
  • Slip of TF bolts: ajouter des boulons, use a larger bolt for a higher [mathin]N_{ti}[mathin], or use standard holes rather than oversize or slotted ones.

For web side plates, flexible end plates, single and double angle cleats, flange plates and beam and column splices with flange and web plates, Conception automatique will try these changes for you and return a layout that passes.

Questions fréquentes

Why is the shear on one bolt not just V* divided by the number of bolts?

Because the load is eccentric to the group. Le 107.5 mm lever arm adds a moment that the bolts farthest from the instantaneous centre resist most, so the group is worth C = 4.6497 single bolts, not eight.

Does the bearing check depend on the bolt grade?

Non. Clause 9.2.2.4 uses the ply’s tensile strength [mathin]f_{up}[mathin], its thickness and the bolt diameter. The bolt grade only enters the bolt shear check.

Why does the plate govern bearing when the beam web is thinner?

The plate’s tensile strength is lower (410 MPa contre 440 MPa) and its vertical edge distance gives [mathin]a_{e} = 46.5\ \text{mm}[mathin], moins que le 49 mm that governs the beam web.

Are TF bolts checked for slip at the strength limit state?

Non. Clause 9.2.3.1 is a serviceability check. At the strength limit state a TF bolt is designed as a bearing bolt, with the same shear and ply bearing checks as an S bolt.

Check your own bolts for free

Choisissez COMME 4100:2020 and a bolted connection, set the bolt category, size and hole type, and every bolt check above comes back with its DCR and clause. Il n'y a rien à installer.