Directly welded web connection design to AISC 360 is short, because the load path is short. The beam web is fillet welded straight to the support, with no plate, angle or bolts in between, so the end shear goes from the web into the welds and from the welds into the column flange. The design checks the minimum fillet weld size, the strength of the welds with the base metal on both sides of them, and the beam web in shear.
This page works one example from start to finish: a W18x50 beam whose web is welded to the flange of a W14x90 column with 3/16 in E70XX fillet welds on both sides of the web, 15.5 in long, carrying a factored end shear of 38 kip (LRFD). The design is to AISC 360-16 and the AISC Manual 15th Edition. Every equation is written out with its numbers, in the same order as the calc sheet that the SkyCiv Connection Design module produces for this connection.
What is a directly welded web connection?
In a directly welded web connection the end of the beam web is fillet welded to the supporting member, one weld on each side of the web. The beam flanges are not welded, so the connection carries the end shear and is treated as a simple connection. With nothing between the beam and the support, it needs no plates, angles or bolts, and all of the work is welding.
It is the most compact of the shear connections. The other types, such as the single plate, double angle and end plate connections, add a connecting element that can be bolted on site; you can compare them on the shear connections page. In this example the welds run 15.5 in along the web on each side.

Elevation of the example connection, with the 3/16 in E70XX fillet weld on both sides of the beam web and the 38 kip shear.

The same connection in SkyCiv Connection Design, with the Directly Welded Web config on the Assembly tab.
Directly welded web connection design: the steps at a glance
- Check the minimum fillet weld size.
- Check the design strength of the welds, including the base metal on both sides.
- Check the beam web in shear.
Design inputs for this example
The design code is AISC 360-16 LRFD. Section properties are from the AISC Manual.
| Item | Symbol | Value |
|---|---|---|
| Factored shear | [mathin] V_{u} [mathin] | 38 kip |
| Beam | W18x50, A992 | |
| Beam depth / web thickness | [mathin] d_{bm},\ t_{wb} [mathin] | 18 in / 0.355 in |
| Beam flange width / thickness | [mathin] b_{fb},\ t_{fb} [mathin] | 7.5 in / 0.57 in |
| Column | W14x90, A992 | |
| Column depth / web thickness | [mathin] d_{sup},\ t_{ws} [mathin] | 14 in / 0.44 in |
| Column flange width / thickness | [mathin] b_{fs},\ t_{fs} [mathin] | 14.5 in / 0.71 in |
| Beam and column yield / tensile stress | [mathin] F_{y},\ F_{u} [mathin] | 50 ksi / 65 ksi |
| Weld | E70XX fillet, both sides of the web | |
| Weld size / filler metal strength | [mathin] W,\ F_{EXX} [mathin] | 0.1875 in / 70 ksi |
| Weld length on each side | [mathin] L_{wv} [mathin] | 15.5 in |
Step 1: Minimum fillet weld size (AISC 360-16 J2.2b, Table J2.4)
A fillet weld that is too small for the parts it joins cools too fast and can crack, so Table J2.4 sets a minimum size from the thinner part joined. Here that is the 0.355 in beam web, which falls in the range over 1/4 in to 1/2 in, so the minimum is 3/16 in.
| Detailing limit | Limit (in) | Actual (in) | DCR | Result |
|---|---|---|---|---|
| Minimum fillet weld size | 0.188 | 0.188 | 1.000 | PASS |
[math] DCR = \frac{0.1875\ \text{in}}{0.1875\ \text{in}} = 1 [math]
DCR = 1.000 ≤ 1.0, OK
The 3/16 in weld was chosen at the minimum size, so the check sits on its limit. It is a detailing check, not a strength problem.
Step 2: Design strength of the welds (AISC 360-16 J2.4, AISC Manual Parts 9 and 10)
The weld strength is capped by the base metal on each side of it (Manual Eq. 9-2). On the support side that is the column flange. On the beam side the web is shared by the two welds, one on each face, so each weld gets half the web thickness:
[math] D_{max} = \frac{\min\left( t_{fs} F_{us},\ \frac{t_{wb}}{2} F_{ub} \right)}{3.09\ \text{kip/in}} = \frac{\min\left( (0.71\ \text{in})(65\ \text{ksi}),\ (0.1775\ \text{in})(65\ \text{ksi}) \right)}{3.09\ \text{kip/in}} = 3.7338 [math]
[mathin] D_{max} [mathin] is in sixteenths of an inch. It is more than the 3 sixteenths of the 3/16 in weld, so the full weld size is effective. The effective length deducts twice the weld size at the ends (AISC Manual Part 10), for both welds:
[math] L_{w} = 2\left[ L_{wv} – 2W \right] = 2 \times \left[ 15.5\ \text{in} – 2 \times 0.1875\ \text{in} \right] = 30.25\ \text{in} [math]
The load is pure shear, parallel to the welds, so the angle of loading is [mathin] \theta = 0 [mathin] and the directional strength term of Eq. J2-5 is 1:
[math] \phi R_{n} = \phi\, 0.6\, F_{EXX} \frac{\sqrt{2}}{2} \min\left( W,\ \frac{D_{max}}{16} \right) \left[ 1 + 0.5 \left( \sin\theta \right)^{1.5} \right] L_{w} [math]
[math] \phi R_{n} = (0.75) \times 0.6 \times (70\ \text{ksi}) \times \frac{\sqrt{2}}{2} \times \min\left( 0.1875\ \text{in},\ \frac{3.7338}{16} \right) \times \left[ 1 + 0.5 \left( \sin 0 \right)^{1.5} \right] \times (30.25\ \text{in}) = 126.33\ \text{kip} [math]
DCR = 38 kip / 126.33 kip = 0.301 < 1.0, OK
This is the governing strength check. The 3/16 in welds are well within their strength, so the minimum size from Step 1 is what sets the weld.
Step 3: Beam web in shear (AISC 360-16 J4.2)
The beam is not coped, so the full depth of the web carries the shear into the welds:
[math] A_{gv} = d_{bm}\, t_{wb} = (18\ \text{in}) \times (0.355\ \text{in}) = 6.39\ \text{in}^{2} [math]
[math] \phi R_{n} = \phi\, 0.6\, F_{yb} A_{gv} = (1) \times 0.6 \times (50\ \text{ksi}) \times (6.39\ \text{in}^{2}) = 191.7\ \text{kip} [math]
DCR = 38 kip / 191.7 kip = 0.198 < 1.0, OK
Summary of checks
| Design check | Demand | Capacity | DCR | Result |
|---|---|---|---|---|
| Minimum fillet weld size | 0.1875 in | 0.1875 in | 1.000 | PASS |
| Design strength of the welds | 38 kip | 126.33 kip | 0.301 | PASS |
| Beam web in shear | 38 kip | 191.7 kip | 0.198 | PASS |
Every check in this directly welded web connection design passes. The 1.000 ratio is the minimum fillet weld size, which the 3/16 in weld meets exactly. Of the strength checks, the welds govern at 0.301, followed by the beam web in shear at 0.198.
Auto Design is available for the directly welded web connection to a column flange. It changes the connection’s design variables until every check passes, and keeps your members and loads as entered. See the Auto Design page for the preferences it works to.
What to change if a check fails
- Minimum fillet weld size: increase the weld to the Table J2.4 minimum for the thinner part joined.
- Weld strength: increase the weld size or the weld length, or use a stronger electrode. Once the weld size passes the base metal limit of the half web, a larger weld adds no strength, so lengthen the weld instead.
- Beam web in shear: this depends only on the beam, so use a heavier section.
Frequently asked questions
Why is only half the beam web thickness used in the base metal check?
There is a fillet weld on each face of the web, and both welds load the same web. Each weld can only count on its share of the web, so the report takes half the web thickness, 0.1775 in, against the full 0.71 in column flange. The web side governs.
Why is the weld length reduced by twice the weld size?
The report deducts twice the weld size from each weld, following the AISC Manual Part 10, to allow for the ends of the weld. With two 15.5 in welds of 3/16 in, the effective length is 30.25 in.
Why does the weld strength not get the directional increase?
The directional strength term of Eq. J2-5 depends on the angle between the load and the weld axis. Here the end shear runs along the welds, so the angle is zero and the term is 1. When the beam also carries an axial force, the load turns toward the perpendicular and the term rises, as the shear and axial version of this example shows.
Is the column checked for the shear in this design?
For a shear-only connection to a column flange, the column enters through the base metal check of the weld, using the flange thickness and tensile strength. The report has no separate check of the column for the end shear.
How would this change for AISC ASD instead of LRFD?
The limit states and nominal strengths are the same. With AISC ASD you compare service-level forces against the nominal strength divided by a safety factor: 0.75 for the welds becomes a safety factor of 2.00, and 1.00 for shear yielding of the web becomes 1.50.
Design a directly welded web connection for free
Every number on this page comes from one solve. Pick the directly welded web configuration, enter your beam, support, weld and shear, and the free calculator runs each of these checks in your browser without anything to install.
The SkyCiv Connection Design module is the connection design software behind this example. It gives you the full calculation report with every equation and your numbers in it, like the steps above, plus every capacity and DCR, for AISC 360-22 and AISC 360-16 (LRFD and ASD) and AS 4100:2020. The weld calculator covers fillet weld groups on their own.
References
- AISC 360-16, Specification for Structural Steel Buildings: J2.2b (Table J2.4), J2.4 (Eq. J2-4, J2-5), J4.2 (Eq. J4-3).
- AISC Steel Construction Manual, 15th Edition: Part 9 (Eq. 9-2), Part 10 (effective weld length).
- Design of steel connections using AISC 360-16