This page explains how SkyCiv Foundation designs a combined footing to ACI 318-19: soil bearing, one-way shear, punching shear and flexure, with the equations used and the results shown in the software and the calculation report, followed by the other design checks (uplift, overturning, sliding, load transfer, development length and detailing). Flexure is described with the default Strip average method, and the Peak wood-armer method is summarized for comparison.
A combined footing is a single footing supporting two columns. It is commonly used when the columns are too close to each other, or a column is too close to a property line, for two separate isolated footings. SkyCiv Foundation meshes the footing into plate elements supported on the soil (modeled with the subgrade modulus) and analyzes it with finite element analysis (FEA). The soil pressures, shears and moments used in the design checks below come from these FEA results. To design to the 2019 edition, select American Concrete Institute as the Design Code and ACI 318 (2019) as the Version when you start a new file, then pick Combined Footing. The same checks to the 2014 edition are described in Combined Footing Design in Accordance with ACI 318-14.

The example shown on this page is a 3000 × 1500 × 500 mm combined footing with two 300 × 300 mm columns placed 250 mm from the ends of the footing (X-edge Distance), #5 bars at 200 mm in both directions at the top and bottom, and a 75 mm cover. Column 1 carries a dead load of 200 kN and a live load of 100 kN, and Column 2 a dead load of 250 kN and a live load of 120 kN. The x-direction is the direction joining the two columns.
Design Settings for ACI 318-19
The methods used for the checks are set in Edit Design Settings (Details tab). For ACI 318-19, the Moment Demand Calculation offers the Strip average method (default) and the Peak wood-armer method. The settings also hold the Perform One-Way Shear Check toggle and the Punching Shear Edge Factor (0.5 by default), as well as the switches of the load transfer and development length checks.

Combined Footing Design Checks to ACI 318-19
Dimension Requirements and Soil Bearing
To size a combined footing, service (unfactored) loads such as Dead (D), Live (L), Wind (W) and Seismic (E) are combined with the service load combinations. The governing combination is the design load, and the base area is proportioned so that the allowable soil pressure is not exceeded (ACI 318-19, Section 13.3.1.1):
[math] q_{a} = \frac{P1_{n} + P2_{n}}{A} \quad \text{(Eq. 1)} [math]
qa = Allowable soil pressure
P1n, P2n = Unfactored loads at Column 1 (left) and Column 2 (right)
A = Foundation area
Solving Equation 1 for the area gives a first estimate of the footing dimensions:
[math] A = \frac{P1_{n} + P2_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
SkyCiv Foundation does not size the footing from Equation 1a: the dimensions are inputs (Geometry tab), and the software checks them. The Soil Bearing ratio is the maximum soil pressure from the FEA results of the service load combinations (envelope), which includes the effect of the column moments and of the eccentricity of the loads, divided by the allowable soil bearing capacity entered in the Soil tab:
[math] \text{Utility Ratio} = \frac{q_{sls,max}}{q_{a}} \quad \text{(Eq. 2)} [math]
In the example, the maximum service soil pressure is 224.1 kPa, under Column 2, which carries the larger load, and the Soil Bearing ratio is 0.448. The soil pressure contour and the ratio of every check are shown in the Results tab:

One-way Shear
The one-way shear limit state, also known as beam shear, treats the footing like a wide beam that may fail in shear along a critical section located at a distance "d" from the face of a column. It is checked when Perform One-Way Shear Check is enabled in the design settings (on by default).
The One-way Shear Demand or \( V_{u} \) is taken from the strip average shear diagrams of the FEA (ultimate load combinations): the shear forces of the plate elements are summed across the width of the footing, and the diagram is read at the critical sections, located at the effective depth of the bottom bars in that direction from each column face (or at the edge of the footing when that distance falls outside it). The largest absolute shear at these sections is the demand.
- Along x (the direction joining the columns), one diagram covers the whole footing, with the critical sections on both sides of both columns.
- Along z, each column has its own diagram, through that column.
The diagrams can be viewed in the Results tab by opening Diagrams and choosing One-way Shear in the Diagram list. In the example, the critical sections along x are 417 mm (the effective depth of the bottom x-bars) from the inner faces of the columns, and the demand is 158.70 kN, next to Column 2:

Figure 1. Critical sections and shear diagram of one-way shear along x (Results, Diagrams button)
The One-way Shear Capacity or \( \phi V_{c} \) is calculated with Equation 3 (Table 22.5.5.1(c), for members without shear reinforcement). The size effect factor \( \lambda_{s} \) is neglected for footings, as permitted by Section 13.2.6.2.
[math] \phi V_{c} = \phi_{\text{shear}} \times 8 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Imperial)} [math]
or
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.66 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Metric)} [math]
[math] \rho_{w} = \frac{n \times A_{b}}{L \times d} [math]
ϕshear = Shear strength reduction factor, 0.75 (Table 21.2.1)
λ = Modification factor for lightweight concrete
ρw = Ratio of the bottom bars in the direction checked
n, Ab = Number and area of these bars, across the footing dimension L perpendicular to them
f’c = Specified concrete strength (psi, MPa)
bw = Width resisting the shear (in, mm)
d = Effective depth of the bottom bars in the direction checked (in, mm)
Along x, \( b_{w} \) is the full width of the footing (its dimension along z). Along z, the footing is divided into two design strips at the midpoint between the two column centres, and each column’s shear is checked against the capacity of its own strip, with \( b_{w} \) equal to the strip width. In the example, both strips are 1500 mm wide.
The calculation report shows the shear diagram of each direction, followed by the demand, the capacity and the ratio. Along x, \( \phi V_{c} \) = 192.9 kN and the ratio is 158.7/192.9 = 0.823:

Shear Demand and Shear Capacity must meet the following equation to meet the design requirements of ACI 318-19:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 4, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, in compliance with Equation 4, calculates the one-way shear utility ratio by taking Shear Demand over Shear Capacity, along x and for each column along z. The largest ratio is listed as One-Way Shear in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 5)} [math]
Two-way Shear (Punching Shear)
The two-way shear limit state, also known as punching shear, has its critical section at a distance "d/2" from the faces of the column, around the perimeter of the column (Section 22.6.4.1). Its length is the critical perimeter \( b_{o} \). The check is done for each column. The critical perimeters can be viewed in the Results tab by opening Diagrams and choosing Punching Shear in the Diagram list:

Figure 2. Critical perimeters of two-way shear (Results, Diagrams button)
The effective depth d is the average of the effective depths of the bottom bars in both directions (409 mm in the example). When a column face is closer to a footing edge than the Punching Shear Edge Factor times d, the perimeter on that side extends to the footing edge and is not counted in \( b_{o} \). The column is then classified as an interior, edge or corner column, which sets \( \alpha_{s} \) = 40, 30 or 20 (Section 22.6.5.3). If the column is close to two opposite edges, the punching shear check is skipped for that column, as one-way shear governs. A round column is taken as an equivalent square column with sides equal to its diameter. In the example, both columns are interior columns, with \( b_{o} \) = 4 × 709 = 2836 mm.
The Two-way Shear Demand is calculated at the critical perimeter with the mesh-based method, from the finite element analysis of the footing. The upward force from the soil pressure inside the critical perimeter, \( F_{q} \), is the sum of the forces of the mesh elements in that area (the average pressure on each element times its area inside the perimeter, listed in a table of the report), and it is subtracted from the factored column load. The maximum shear stress \( v_{u} \) on the critical perimeter also includes the unbalanced moments transferred by eccentric shear (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 6)} [math]
[math] \gamma_{v} = 1 – \frac{1}{1 + \frac{2}{3}\sqrt{b_{1}/b_{2}}} \quad \text{(Eq. 7)} [math]
Pu = Factored column load
Fq = Resultant of the factored soil pressure inside the critical perimeter, summed over the FEA mesh elements
γv = Fraction of the unbalanced moment transferred by eccentric shear
Mu = Unbalanced moment: column moment, plus column shear times the column height and footing thickness, minus the column load times the offset of the centroid of the critical section (edge and corner columns)
b1, b2 = Dimensions of the critical section perpendicular and parallel to the direction considered
c, Jc = Distance to the point considered and polar moment of inertia of the critical section
For edge and corner columns, \( \gamma_{v} \) and the stresses are calculated following ACI 421.1R-20. The maximum stress around the critical section is taken as the demand.
The Shear Capacity is the punching shear stress \( \phi v_{c} \), governed by the smallest value of Equations 8, 9 and 10 per Section 22.6.5.2. Unlike ACI 318-14, the 2019 edition includes the size effect factor \( \lambda_{s} \) (Section 22.5.5.1.3), which reduces the capacity of footings with an effective depth over 10 in (250 mm). In the example, \( \lambda_{s} \) = 0.871 for d = 409 mm.
[math] \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + d/10}} \right) \quad \text{(Imperial)} \qquad \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + 0.004\,d}} \right) \quad \text{(Metric)} [math]
[math] v_{c,a} = 4 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c,b} = \left( 2 + \frac{4}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c,c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Imperial)} [math]
or
[math] v_{c,a} = 0.33 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c,b} = \left( 0.17 + \frac{0.33}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c,c} = \left( 0.17 + \frac{0.083 \times \alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
Note: β is the ratio of the long side to the short side of the column (1.0 for a round column), and \( \alpha_{s} \) is given by Section 22.6.5.3. ϕshear = 0.75 (Table 21.2.1).
λs = Size effect modification factor
λ = Modification factor for lightweight concrete
f’c = Specified concrete strength (psi, MPa)
d = Effective depth, the average of the effective depths of the bottom bars in both directions (in, mm)
bo = Critical perimeter (in, mm)
The calculation report shows, for each column, the plan of the critical shear area, the soil pressure force \( F_{q} \), the stresses around the perimeter, and the capacity. For Column 1 of the example, \( v_{u} \) = 0.261 MPa and \( \phi v_{c} \) = 0.980 MPa:

Shear Demand and Shear Capacity must meet the following equation to meet the design requirements of ACI 318-19:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 11, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, in compliance with Equation 11, calculates the two-way shear utility ratio of each column by taking Shear Demand over Shear Capacity, both as stresses. The larger ratio of the two columns is listed as Punching Shear in the Design Checks Summary (0.318 in the example, from Column 2).
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 12)} [math]
Flexure
SkyCiv Foundation checks the top and bottom reinforcement in both directions against the moments of the whole footing from the FEA, rather than at a single critical section. In a combined footing, the top bars along x resist the hogging moment between the columns, and the bottom bars resist the sagging moments under the columns and in the transverse direction.
Moment Demand with the Strip Average Method
With the Strip average method (the default Moment Demand Calculation), the footing is treated like a wide beam in each direction: the Wood-Armer moments of the plate elements are summed across the width of the footing, which gives the total moment carried by that width at each section. This is done for the top and bottom layers, along x and along z, under the ultimate load combinations (envelope).
- Along x, the strip covers the full width of the footing, and one moment diagram covers both columns.
- Along z, the footing is divided into two design strips at the midpoint between the column centres, and each column has its own diagram.
- Bottom layer: \( M_{u} \) is the largest strip moment at the column faces.
- Top layer: \( M_{u} \) is the largest hogging (negative) strip moment anywhere along the strip.
The moment diagrams can be viewed in the Results tab by opening Diagrams, choosing Moment in the Diagram list, and picking the Layer and Direction. In the example, the top layer along x has a maximum hogging moment of 154.65 kN-m, near midway between the columns:

Figure 3. Strip average moment diagram, top layer along x (Results, Diagrams button)
The calculation report shows the same diagram for each layer and direction, with a table of the maximum moment, its coordinates and the governing load combination, followed by the utility ratio:

Peak Wood-Armer Method
With the Peak wood-armer method, \( M_{u} \) is instead the maximum Wood-Armer moment per unit width found anywhere over the footing, for the top and bottom layers in both directions, and the capacity is calculated per unit width (12 in or 1000 mm). Because it uses the peak moment rather than the moment spread over the width, it is usually more conservative. The Wood-Armer moments can be viewed in the Results tab with the Wood Armer button, by picking the Case, Layer and Direction in the View Options. In the example, the peak top moment along x is 105.17 kN-m/m, while the strip average moment of 154.65 kN-m over the 1.5 m width of the footing is 103.1 kN-m/m. This method is described in Combined Footing Design in Accordance with ACI 318-14.

Flexural Capacity
With the strip average method, the Flexural Capacity or \( \phi M_{n} \) is calculated for the width of the strip, with the bars of the layer across that width (along z, the share of the bars in each strip, in proportion to its width), using Equation 13:
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 13)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
ϕflexure = Flexural strength reduction factor (Table 21.2.2)
As = Area of the tension bars of the layer across the strip width (in2, mm2)
fy = Reinforcement strength (psi, MPa)
d = Distance from the extreme compression fiber to the centroid of the tension reinforcement (in, mm)
a = Depth of the equivalent rectangular stress block (in, mm)
b = Strip width: the full width of the footing along x, the strip of each column along z (in, mm)
The strength reduction factor depends on the net tensile strain \( \varepsilon_{t} \), found from the neutral axis depth \( c = a/\beta_{1} \) (β1 from Table 22.2.2.4.3) and a concrete strain of 0.003. ACI 318-19 compares it with the yield strain of the reinforcement \( \varepsilon_{ty} = f_{y}/E_{s} \):
[math] \phi_{\text{flexure}} = 0.65 + 0.25 \times \frac{\varepsilon_{t} – \varepsilon_{ty}}{0.003} \quad \text{(Table 21.2.2)} [math]
with ϕ = 0.90 when \( \varepsilon_{t} \geq \varepsilon_{ty} + 0.003 \) (tension-controlled) and ϕ = 0.65 when \( \varepsilon_{t} \leq \varepsilon_{ty} \) (compression-controlled). The report shows a warning when the section is not tension-controlled. When the tension steel ratio exceeds the balanced ratio, the section is checked as doubly reinforced, with the other layer as compression steel.
In the example, the 8 top bars along x (1608.5 mm²) with d = 417 mm give \( \phi M_{n} \) = 163.25 kN-m, and the top layer ratio along x is 154.65/163.25 = 0.947.
The provided reinforcement of each layer, in each direction, is also compared to the minimum area of 0.0018 Ag (Section 8.6.1.1), where Ag is the gross area of the footing section perpendicular to the bars.
Moment Demand and Moment Capacity must meet the following equation to meet the design requirements of ACI 318-19:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 14, Section 7.5.1.1(a))} [math]
SkyCiv Foundation, in compliance with Equation 14, calculates the flexural utility ratio by taking Flexural Demand over Flexural Capacity, for the top and bottom layers along x and for each strip along z. The Flexure ratio in the Design Checks Summary is the largest of the top, bottom and minimum reinforcement ratios (0.947 in the example).
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 15)} [math]
Other Design Checks
Besides the checks above, the calculation report of a combined footing designed to ACI 318-19 includes the stability checks, the load transfer at the column bases, the development length of the bars and a detailing check. Each one gives a utilization ratio in the Design Checks Summary of the Results tab. The largest ratio governs the design, and the footing fails when it is greater than 1.0. A check that does not apply to the loads (for example sliding without horizontal loads) is shown with a dash.
Uplift
The uplift check compares the upward forces with the forces holding the footing down, considering axial loads only: the column loads, the self-weights of the columns, footing and soil, and the buoyant force. When no service load combination produces uplift, the check is not needed.
Overturning
Overturning is checked by summing the moments of all the forces about the toe and the heel of the footing, in each direction, for all the service load combinations. The governing (smallest) factor of safety, stabilising moment over overturning moment, is compared with the Overturning factor of safety in the Design Factors tab of the Loads. If the loads produce no overturning moment, the check is not needed.
Sliding
Sliding is checked in each direction by dividing the horizontal resisting forces by the horizontal force applied to the footing, with both taken from the same service load combination (the one with the lowest factor of safety). The resisting forces are the friction between the footing base and the soil (none under net uplift), the passive soil pressure and the cohesion of the soil. The factor of safety is compared with the Sliding factor of safety in the Design Factors tab. If no horizontal force acts on the footing, the check is not needed.
Load Transfer
The Load Transfer check verifies the bearing of each column on the footing (Section 22.8.3.2). The factored axial load of the column is compared with the design bearing strength, with ϕ = 0.65:
[math] \phi B_{n} = \min \left( \phi \times 0.85 f’_{c} A_{1} \sqrt{\frac{A_{2}}{A_{1}}}, \; \phi \times 2 \times 0.85 f’_{c} A_{1} \right) \quad \text{(Eq. 16)} [math]
A1 = Loaded area (the column area)
A2 = Base of the frustum with 1 vertical to 2 horizontal side slopes under the column, wholly within the footing: its projection beyond the column is limited by the nearest footing edge and by 2 times the footing thickness
The larger ratio of the two columns is listed as Load Transfer (0.560 in the example). The report also compares the area of the dowel bars of each column with the minimum of 0.005 times the column area (Section 16.3.4.1).
Development Length
The Development Length check covers the column dowel bars and the flexural bars of the footing:
- Column dowel bars: the compression development length (Section 25.4.9), plus the bend of the dowel, must fit in the footing thickness.
- Flexural bars: at each column face, the force in the bars must be developed on each side of the section (Section 13.2.8.2). The tension development length of straight bars (Section 25.4.2) or hooked bars (Section 25.4.3, depending on the bar ends chosen in the Reinforcement tab) is compared with the anchorage length available from the column face to the end of the bar.
The checks can be turned on or off in the design settings (Perform dowel bars check, Perform top bars check and Perform bottom bars check). In the example, the Development Length ratio of 1.231 comes from the bottom bars along x at the outer face of Column 1: only 175 mm is available (the 250 mm X-edge Distance minus the 75 mm cover), while the hooked bars need 215.35 mm. Increasing the X-edge Distance of the columns gives the bars the anchorage they need. The development length checks are explained in more detail in the ACI 318 (2019) Development Length Check Guide, written for isolated footings.
Detailing
The Detailing check verifies that the footing thickness can hold the hooked ends of the top and bottom bars (90° or 180° hooks), with their bend and extension and the top and bottom covers.
Product Developer
BSc (Civil), MSc (Civil)
References
- Building Code Requirements for Structural Concrete (ACI 318-19) and Commentary (ACI 318R-19). American Concrete Institute, 2019.
- ACI Committee 421. Guide to Shear Reinforcement for Slabs (ACI 421.1R-20). American Concrete Institute, 2020.