When a directly welded web connection carries an axial force as well as the end shear, two things change in the design to AISC 360. The welds now see a resultant force at an angle to their axis, which is larger than the shear alone but also earns the directional strength increase of Eq. J2-5. And the axial force is delivered to the column flange as a concentrated force, so the column has to be checked for flange local bending, web local yielding and, em compressão, web local crippling.

This page works the same connection as the shear-only directly welded web example, a W18x50 beam web welded to the flange of a W14x90 column with 3/16 em soldas de ângulo E70XX 15.5 in long on both sides of the web, and adds an axial force of 132 kip in tension or compression to the 38 kip end shear (LRFD). O projeto é AISC 360-16 e o Manual AISC 15ª Edição. Cada equação é escrita com seus números, na mesma ordem da planilha de cálculo que o SkyCiv Connection Design módulo produz para esta conexão.

What the axial force adds to a directly welded web connection

A beam in a braced frame or a diaphragm chord often carries an axial force along with its end reaction, for example as a strut or collector. With a directly welded web, that force has no plate or bolts to pass through: it goes straight from the web into the two fillet welds and from them into the column flange.

The member sizes, weld and the checks of the minimum weld size and the beam web in shear are the same as in the shear-only example, and give the same results. This page focuses on the weld under combined load and on the two support checks the axial force adds. The other shear connection types are on the Etapas para projetar página.

Elevação da alma diretamente soldada: W18x50 web welded to a W14x90 flange, 3/16 in E70XX fillets, Vu = 38 kip, Você = Com = kip kip

Elevação da conexão de exemplo, com o 38 cisalhamento kip e o 132 kip tension or compression at the beam end.

Guia Montagem de projeto de conexão SkyCiv: Directly Welded Web config for shear plus axial, Viga W18x50 para flange de coluna W14x90

A mesma conexão no SkyCiv Connection Design, com a configuração Directly Welded Web na guia Montagem.

Directly welded web shear and axial design: os passos em resumo

  1. Verifique o tamanho mínimo do filete de solda.
  2. Check the welds for the resultant of the shear and the axial force.
  3. Verifique a alma da viga em cisalhamento.
  4. Check the column for the axial tension: flange local bending and web local yielding.
  5. Check the column for the axial compression: web local crippling and web local yielding.

Entradas de design para este exemplo

O código de projeto é AISC 360-16 LRFD. As propriedades da seção são do Manual AISC. O kdes da coluna, usado no rendimento local da web, é 1.31 no.

ItemSímboloValor
Cisalhamento fatorado[mathin] V_{u} [mathin]38 kip
Tensão axial fatorada[mathin] T_{u} [mathin]132 kip
Compressão axial fatorada[mathin] C_{u} [mathin]132 kip
BeamMomento da carga ao vivo, A992
Profundidade do feixe / espessura da teia[mathin] d_{bm},\ t_{wb} [mathin]18 no / 0.355 no
ColunaW14x90, A992
Profundidade da coluna / espessura da teia[mathin] d_{sup},\ t_{ws} [mathin]14 no / 0.44 no
Largura do flange da coluna / grossura[mathin] b_{fs},\ t_{fs} [mathin]14.5 no / 0.71 no
Coluna kdes[mathin] k_{des} [mathin]1.31 no
Rendimento de vigas e colunas / tensão de tração[mathin] F_{y},\ F_{u} [mathin]50 ksi / 65 ksi
Módulo de elasticidade[mathin] E [mathin]29000 ksi
SoldarFilé E70XX, ambos os lados da web
Tamanho da solda / length on each side[mathin] W,\ L_{wv} [mathin]0.1875 no / 15.5 no

Passo 1: Tamanho mínimo de solda de filete (AISC 360-16 J2.2b, Tabela J2.4)

The axial force does not change this check. The thinner part joined is the 0.355 em teia de feixe, so the Table J2.4 minimum is 3/16 no, and the weld is 3/16 no.

DCR = 0.1875 no / 0.1875 em = 1.000 ≤ 1.0, OK

Passo 2: Welds under the resultant of shear and axial force (AISC 360-16 J2.4)

The base metal limit and the effective length are the same as for shear alone, half the web thickness against the column flange, and twice the weld size off each end:

[math] D_{max} = \frac{\min\left( t_{fs} F_{us},\ \frac{t_{wb}}{2} F_{ub} \right)}{3.09\ \text{kip/in}} = \frac{\min\left( (0.71\ \text{in})(65\ \text{ksi}),\ (0.1775\ \text{in})(65\ \text{ksi}) \right)}{3.09\ \text{kip/in}} = 3.7338 [math]

[math] L_{w} = 2\left[ L_{wv} – 2W \right] = 2 \times \left[ 15.5\ \text{in} – 2 \times 0.1875\ \text{in} \right] = 30.25\ \text{in} [math]

What changes is the load. The welds now carry the vertical shear along their axis and the axial force across it. The demand is the resultant of the two, at an angle to the weld axis:

[math] R_{u} = \sqrt{V_{u}^{2} + T_{u}^{2}} = \sqrt{(38\ \text{kip})^{2} + (132\ \text{kip})^{2}} = 137.36\ \text{kip} [math]

[math] \theta_{u} = \tan^{-1}\left( \frac{T_{u}}{V_{u}} \right) = \tan^{-1}\left( \frac{132}{38} \right) = 73.94^{\circ} [math]

A fillet weld loaded across its axis is stronger than one loaded along it, Estimativa da capacidade da pilha. J2-5 rewards that with the directional term:

[math] \phi R_{n} = \phi\, 0.6\, F_{EXX} \frac{\sqrt{2}}{2} \min\left( W,\ \frac{D_{max}}{16} \right) \left[ 1 + 0.5 \left( \sin\theta_{u} \right)^{1.5} \right] L_{w} [math]

[math] \phi R_{n} = (0.75) \times 0.6 \times (70\ \text{ksi}) \times \frac{\sqrt{2}}{2} \times \min\left( 0.1875\ \text{in},\ \frac{3.7338}{16} \right) \times \left[ 1 + 0.5 \left( \sin 73.94^{\circ} \right)^{1.5} \right] \times (30.25\ \text{in}) = 185.84\ \text{kip} [math]

DCR = 137.36 kip / 185.84 kip = 0.739 < 1.0, OK

Esta é a verificação governante. The same welds are good for 126.33 kip under shear alone, so the load angle adds about 47% to their strength. The demand grows faster, no entanto, a partir de 38 kip to 137.36 kip, and the ratio rises from 0.301 para 0.739. The tension and compression cases have the same resultant, so one weld check covers both.

Passo 3: Teia de viga em cisalhamento (AISC 360-16 J4.2)

The beam web still carries only the 38 kip de cisalhamento, over its full depth:

[math] \phi R_{n} = \phi\, 0.6\, F_{yb}\, d_{bm}\, t_{wb} = (1) \times 0.6 \times (50\ \text{ksi}) \times (18\ \text{in})(0.355\ \text{in}) = 191.7\ \text{kip} [math]

DCR = 38 kip / 191.7 kip = 0.198 < 1.0, OK

Passo 4: Coluna sob tensão axial (AISC 360-16 J10.1, J10.2)

The axial tension pulls on the column flange along the line of the weld. AISC 360-16 J10 covers this as a concentrated force on the flange: flexão local do flange (J10.1), where it applies, e rendimento local na web (J10.2). Incapacitação local da Web (J10.3) is for compressive forces only.

Flexão local do flange

J10.1 does not require a flange local bending check when the length of loading measured across the member flange is less than 0.15 times the flange width:

[math] 0.15\, b_{f} = 0.15\, b_{fs} = 0.15 \times (14.5\ \text{in}) = 2.175\ \text{in} [math]

The load is delivered by the beam web, so the loaded length across the column flange is the web thickness, [mathin] t_{wb} = 0.355\ \text{in} [mathin]. That is less than 2.175 no, so flange local bending need not be checked.

Escoamento local da alma

The force spreads through the column flange into the web over the weld length plus [mathin] 5k [mathin] (Eq. J10-2):

[math] \phi R_{n} = \phi\, F_{ys}\, t_{ws} \left( 5 k_{des} + L_{wv} \right) = (1) \times (50\ \text{ksi}) \times (0.44\ \text{in}) \times \left( 5 \times 1.31\ \text{in} + 15.5\ \text{in} \right) = 485.1\ \text{kip} [math]

DCR = 132 kip / 485.1 kip = 0.272 < 1.0, OK

Passo 5: Coluna sob compressão axial (AISC 360-16 J10.2, J10.3)

In compression the beam pushes on the column flange, so web local crippling joins web local yielding. Incapacitação local da Web, Eq. J10-4, with the weld length as the bearing length:

[math] \phi R_{n,wlc} = \phi\, 0.8\, t_{ws}^{2} \left[ 1 + 3\left( \frac{L_{wv}}{d_{sup}} \right) \left( \frac{t_{ws}}{t_{fs}} \right)^{1.5} \right] \sqrt{\frac{E F_{ys} t_{fs}}{t_{ws}}}\, Q_{f} [math]

[math] \phi R_{n,wlc} = (0.75) \times 0.8 \times (0.44\ \text{in})^{2} \left[ 1 + 3\left( \frac{15.5}{14} \right) \left( \frac{0.44}{0.71} \right)^{1.5} \right] \sqrt{\frac{(29000\ \text{ksi})(50\ \text{ksi})(0.71\ \text{in})}{0.44\ \text{in}}} \times (1) = 465.59\ \text{kip} [math]

Web local yielding is the same as in tension, 485.1 kip. The lower of the two governs:

[math] \phi R_{n} = \min\left( 465.59\ \text{kip},\ 485.1\ \text{kip} \right) = 465.59\ \text{kip} [math]

DCR = 132 kip / 465.59 kip = 0.284 < 1.0, OK

Both column checks pass with room to spare, so this W14x90 needs no stiffeners or web doubler for these limit states.

Resumo das verificações

Verificação de projetoDemandaCapacidadeDCRResultado
Tamanho mínimo de solda de filete0.1875 no0.1875 no1.000cdot K_a
Welds under shear and axial force137.36 kip185.84 kip0.739cdot K_a
Teia de viga em cisalhamento38 kip191.7 kip0.198cdot K_a
Coluna sob tensão axial132 kip485.1 kip0.272cdot K_a
Coluna sob compressão axial132 kip465.59 kip0.284cdot K_a

Every check in this directly welded web shear and axial connection design passes. A 1.000 proporção é o tamanho mínimo da solda de ângulo, na Relação Demanda-Capacidade ou DCR 3/16 na solda atende exatamente. Das verificações de força, as soldas governam em 0.739 debaixo de 137.36 kip resultant, contra 0.301 for the same welds under shear alone. The column checks for the axial force come next, with web local crippling in compression at 0.284.

Auto Design is available for the directly welded web connection with shear and axial load to a column flange. Ele altera as variáveis ​​de projeto da conexão até que cada verificação seja aprovada, e mantém seus membros e cargas conforme inseridos. Veja o Projeto Automático página para as preferências para as quais funciona.

O que mudar se uma verificação falhar

  • Força de soldagem: lengthen the welds, increase the weld size up to the base metal limit of the half web, ou use um eletrodo mais forte. Past that limit a larger weld adds no strength.
  • Column web local yielding or crippling: a longer weld spreads the force over more of the column web and raises both strengths. Otherwise use a column with a thicker web, or add stiffeners or a web doubler.
  • Flexão local do flange: with a directly welded web it only applies if the loaded length across the flange reaches 0.15 times the flange width.
  • Minimum weld size or beam web shear: as for shear alone, meet the Table J2.4 minimum, ou use uma viga mais pesada.

Perguntas frequentes

Why does the weld get stronger when the axial force is added?

The strength of a fillet weld depends on the direction of the load. Under pure shear the load runs along the weld, and the directional term of Eq. J2-5 é 1. Com 132 kip of axial force the resultant turns to 73.94 degrees from the weld axis, and the term rises toward its maximum of 1.5 for a load at 90 graus. Here it lifts the weld strength from 126.33 kip to 185.84 kip.

Why is only one weld check reported for both tension and compression?

The axial force is 132 kip de qualquer maneira, so the resultant on the welds is the same 137.36 kip at the same angle. The sign of the axial force matters for the column, which is why the support is checked separately for tension and compression.

Why is flange local bending not checked?

J10.1 only requires it when the force is spread across a meaningful width of the column flange. Here the force comes in through a 0.355 em teia de feixe, which is much less than 0.15 vezes o 14.5 na largura do flange, 2.175 no, so J10.1 does not require the check.

Why is web local crippling checked only in compression?

Web local crippling is the buckling of the column web under a compressive force pushed through the flange. A tensile force pulls the web straight, so J10.3 applies to compressive forces only, while web local yielding applies to both.

Como isso mudaria para AISC ASD em vez de LRFD?

Os estados limites e as resistências nominais são iguais. Com AISC ASD você compara as forças de nível de serviço com a resistência nominal dividida por um fator de segurança: 0.75 for the welds and for web local crippling becomes a safety factor of 2.00, e 1.00 for web shear yielding and web local yielding becomes 1.50.

Projete uma conexão web diretamente soldada gratuitamente

Cada número nesta página vem de uma solução. Pick the directly welded web configuration with shear and axial load, entre no seu raio, Importará o modelo estrutural, weld and forces, e a calculadora gratuita executa cada uma dessas verificações no seu navegador sem nada para instalar.

O módulo SkyCiv Connection Design é o software de design de conexão por trás deste exemplo. Fornece o relatório de cálculo completo com todas as equações e seus números, como as etapas acima, além de todas as capacidades e DCR, para AISC 360-22 e AISC 360-16 (LRFD e ASD) e a norma AS 4100:2020. A calculadora de solda cobre grupos de solda em ângulo por conta própria.