This page explains how SkyCiv Foundation designs a combined footing to ACI 318-19: φέρουσα χώμα, Διαδικτυακός υπολογιστής ποδιών για επιθέματα από σκυρόδεμα, punching shear and flexure, with the equations used and the results shown in the software and the calculation report, followed by the other design checks (ανύψωση, ανατροπή, ολίσθηση, μεταφορά φορτίου, development length and detailing). Flexure is described with the default Strip average method, και το Peak wood-armer method is summarized for comparison.
ΕΝΑ συνδυασμένη βάση is a single footing supporting two columns. It is commonly used when the columns are too close to each other, or a column is too close to a property line, for two separate isolated footings. Ίδρυμα SkyCiv meshes the footing into plate elements supported on the soil (modeled with the subgrade modulus) and analyzes it with finite element analysis (ΑΣΧΗΜΟΣ). The soil pressures, shears and moments used in the design checks below come from these FEA results. To design to the 2019 έκδοση, επιλέξτε Αμερικανικό Ινστιτούτο Σκυροδέματος as the Design Code and ACI 318 (2019) as the Version when you start a new file, then pick Συνδυασμένη βάση. The same checks to the 2014 edition are described in Συνδυασμένος σχεδιασμός ποδιών σύμφωνα με το ACI 318-14.

The example shown on this page is a 3000 × 1500 × 500 mm combined footing with two 300 × 300 mm columns placed 250 mm from the ends of the footing (X-edge Distance), #5 bars at 200 mm in both directions at the top and bottom, και ένα 75 mm cover. Στήλη 1 carries a dead load of 200 kN and a live load of 100 ΚΝ, και Στήλη 2 a dead load of 250 kN and a live load of 120 ΚΝ. The x-direction is the direction joining the two columns.
Design Settings for ACI 318-19
The methods used for the checks are set in Edit Design Settings (Details tab). For ACI 318-19, ο Moment Demand Calculation offers the Strip average method (Προκαθορισμένο) και το Peak wood-armer method. The settings also hold the Perform One-Way Shear Check toggle and the Punching Shear Edge Factor (0.5 από προεπιλογή), as well as the switches of the load transfer and development length checks.

Combined Footing Design Checks to ACI 318-19
Dimension Requirements and Soil Bearing
To size a combined footing, υπηρεσία (απαράγοντας) loads such as Dead (ρε), Ζω (μεγάλο), Ανεμος (Δ) and Seismic (μι) are combined with the service load combinations. The governing combination is the design load, and the base area is proportioned so that the allowable soil pressure is not exceeded (ACI 318-19, Ενότητα 13.3.1.1):
[math] q_{a} = \frac{P1_{n} + P2_{n}}{A} \quad \text{(Eq. 1)} [math]
εένα = Επιτρεπόμενη πίεση εδάφους
Ρ1ν, Ρ2ν = Unfactored loads at Column 1 (αριστερά) και Στήλη 2 (σωστά)
A = Περιοχή ιδρύματος
Solving Equation 1 for the area gives a first estimate of the footing dimensions:
[math] A = \frac{P1_{n} + P2_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
SkyCiv Foundation does not size the footing from Equation 1a: the dimensions are inputs (Geometry tab), and the software checks them. Το Έδαφος ratio is the maximum soil pressure from the FEA results of the service load combinations (envelope), which includes the effect of the column moments and of the eccentricity of the loads, divided by the allowable soil bearing capacity entered in the Soil tab:
[math] \text{Utility Ratio} = \frac{q_{sls,max}}{q_{a}} \quad \text{(Eq. 2)} [math]
In the example, the maximum service soil pressure is 224.1 kPa, under Column 2, which carries the larger load, and the Soil Bearing ratio is 0.448. The soil pressure contour and the ratio of every check are shown in the Αποτελέσματα αυτί:

Μονόδρομη κουρά
Η μονόδρομη οριακή κατάσταση διάτμησης, γνωστή και ως διάτμηση δοκού, treats the footing like a wide beam that may fail in shear along a critical section located at a distance "d" από το πρόσωπο μιας στήλης. It is checked when Perform One-Way Shear Check is enabled in the design settings (ενεργοποιημένο από προεπιλογή).
Το One-way Shear Demand ή \( V_{u} \) is taken from the strip average shear diagrams of the FEA (ultimate load combinations): the shear forces of the plate elements are summed across the width of the footing, and the diagram is read at the critical sections, located at the effective depth of the bottom bars in that direction from each column face (or at the edge of the footing when that distance falls outside it). The largest absolute shear at these sections is the demand.
- Along x (the direction joining the columns), one diagram covers the whole footing, with the critical sections on both sides of both columns.
- Along z, each column has its own diagram, through that column.
The diagrams can be viewed in the Αποτελέσματα tab by opening Diagrams and choosing Μονόδρομη κουρά στο Diagram λίστα. In the example, the critical sections along x are 417 χιλ (the effective depth of the bottom x-bars) from the inner faces of the columns, and the demand is 158.70 ΚΝ, next to Column 2:

Φιγούρα 1. Critical sections and shear diagram of one-way shear along x (Αποτελέσματα, Diagrams button)
Το Χωρητικότητα διάτμησης μονής κατεύθυνσης ή \( \phi V_{c} \) is calculated with Equation 3 (Τραπέζι 22.5.5.1(ντο), for members without shear reinforcement). The size effect factor \( \lambda_{s} \) is neglected for footings, as permitted by Ενότητα 13.2.6.2.
[math] \phi V_{c} = \phi_{\text{shear}} \times 8 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Imperial)} [math]
ή
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.66 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Metric)} [math]
[math] \rho_{w} = \frac{n \times A_{b}}{L \times d} [math]
ϕκουρεύω = Shear strength reduction factor, 0.75 (Τραπέζι 21.2.1)
λ = Modification factor for lightweight concrete
ρβ = Ratio of the bottom bars in the direction checked
ν, ΕΝΑσι = Number and area of these bars, across the footing dimension L perpendicular to them
φά’ντο = Καθορισμένη αντοχή σκυροδέματος (psi, MPa)
σιβ = Width resisting the shear (σε, χιλ)
d = Effective depth of the bottom bars in the direction checked (σε, χιλ)
Along x, \( b_{w} \) is the full width of the footing (its dimension along z). Along z, the footing is divided into two design strips at the midpoint between the two column centres, and each column’s shear is checked against the capacity of its own strip, με \( b_{w} \) equal to the strip width. In the example, both strips are 1500 mm πλάτος.
The calculation report shows the shear diagram of each direction, followed by the demand, the capacity and the ratio. Along x, \( \phi V_{c} \) = 192.9 kN and the ratio is 158.7/192.9 = 0.823:

Η ζήτηση διάτμησης και η ικανότητα διάτμησης πρέπει να πληρούν την ακόλουθη εξίσωση για να πληρούν τις απαιτήσεις σχεδιασμού του ACI 318-19:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 4, Section 7.5.1.1(b))} [math]
Ίδρυμα SkyCiv, σε συμμόρφωση με την Εξίσωση 4, calculates the one-way shear utility ratio by taking Shear Demand over Shear Capacity, along x and for each column along z. The largest ratio is listed as Μονόδρομη διάτμηση in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 5)} [math]
Αμφίδρομη κουρά (Διάτρηση διάτρησης)
The two-way shear limit state, γνωστό και ως διάτμηση διάτρησης, has its critical section at a distance "d/2" from the faces of the column, around the perimeter of the column (Ενότητα 22.6.4.1). Its length is the critical perimeter \( b_{o} \). The check is done for each column. The critical perimeters can be viewed in the Αποτελέσματα tab by opening Diagrams and choosing Διάτρηση διάτρησης στο Diagram λίστα:

Φιγούρα 2. Critical perimeters of two-way shear (Αποτελέσματα, Diagrams button)
The effective depth d is the average of the effective depths of the bottom bars in both directions (409 mm in the example). When a column face is closer to a footing edge than the Punching Shear Edge Factor φορές d, the perimeter on that side extends to the footing edge and is not counted in \( b_{o} \). The column is then classified as an interior, edge or corner column, which sets \( \alpha_{s} \) = 40, 30 ή 20 (Ενότητα 22.6.5.3). If the column is close to two opposite edges, the punching shear check is skipped for that column, as one-way shear governs. A round column is taken as an equivalent square column with sides equal to its diameter. In the example, both columns are interior columns, με \( b_{o} \) = 4 × 709 = 2836 χιλ.
Το Two-way Shear Demand is calculated at the critical perimeter with the mesh-based method, from the finite element analysis of the footing. The upward force from the soil pressure inside the critical perimeter, \( F_{q} \), is the sum of the forces of the mesh elements in that area (the average pressure on each element times its area inside the perimeter, listed in a table of the report), and it is subtracted from the factored column load. The maximum shear stress \( v_{u} \) on the critical perimeter also includes the unbalanced moments transferred by eccentric shear (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 6)} [math]
[math] \gamma_{v} = 1 – \frac{1}{1 + \frac{2}{3}\sqrt{b_{1}/b_{2}}} \quad \text{(Eq. 7)} [math]
Πεσύ = Factored column load
φάε = Resultant of the factored soil pressure inside the critical perimeter, summed over the FEA mesh elements
γβ = Fraction of the unbalanced moment transferred by eccentric shear
Μεσύ = Unbalanced moment: column moment, plus column shear times the column height and footing thickness, minus the column load times the offset of the centroid of the critical section (edge and corner columns)
σι1, σι2 = Dimensions of the critical section perpendicular and parallel to the direction considered
ντο, Ιντο = Distance to the point considered and polar moment of inertia of the critical section
For edge and corner columns, \( \gamma_{v} \) and the stresses are calculated following ACI 421.1R-20. The maximum stress around the critical section is taken as the demand.
Το Ικανότητα διάτμησης is the punching shear stress \( \phi v_{c} \), governed by the smallest value of Equations 8, 9 και 10 ανά Ενότητα 22.6.5.2. Unlike ACI 318-14, ο 2019 edition includes the size effect factor \( \lambda_{s} \) (Ενότητα 22.5.5.1.3), which reduces the capacity of footings with an effective depth over 10 σε (250 χιλ). In the example, \( \lambda_{s} \) = 0.871 for d = 409 χιλ.
[math] \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + d/10}} \right) \quad \text{(Imperial)} \qquad \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + 0.004\,d}} \right) \quad \text{(Metric)} [math]
[math] v_{c,a} = 4 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c,b} = \left( 2 + \frac{4}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c,c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Imperial)} [math]
ή
[math] v_{c,a} = 0.33 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c,b} = \left( 0.17 + \frac{0.33}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c,c} = \left( 0.17 + \frac{0.083 \times \alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
Σημείωση: β είναι ο λόγος της μακριάς πλευράς προς τη κοντή πλευρά της στήλης (1.0 for a round column), και \( \alpha_{s} \) is given by Section 22.6.5.3. ϕκουρεύω = 0.75 (Τραπέζι 21.2.1).
λμικρό = Size effect modification factor
λ = Modification factor for lightweight concrete
φά’ντο = Καθορισμένη αντοχή σκυροδέματος (psi, MPa)
d = αποτελεσματικό βάθος, the average of the effective depths of the bottom bars in both directions (σε, χιλ)
σιο = Critical perimeter (σε, χιλ)
The calculation report shows, for each column, the plan of the critical shear area, the soil pressure force \( F_{q} \), the stresses around the perimeter, and the capacity. Για στήλη 1 of the example, \( v_{u} \) = 0.261 MPa and \( \phi v_{c} \) = 0.980 MPa:

Η ζήτηση διάτμησης και η ικανότητα διάτμησης πρέπει να πληρούν την ακόλουθη εξίσωση για να πληρούν τις απαιτήσεις σχεδιασμού του ACI 318-19:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 11, Section 7.5.1.1(b))} [math]
Ίδρυμα SkyCiv, σε συμμόρφωση με την Εξίσωση 11, calculates the two-way shear utility ratio of each column by taking Shear Demand over Shear Capacity, both as stresses. The larger ratio of the two columns is listed as Διάτρηση διάτρησης in the Design Checks Summary (0.318 in the example, from Column 2).
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 12)} [math]
Κάμψη
SkyCiv Foundation checks the top and bottom reinforcement in both directions against the moments of the whole footing from the FEA, rather than at a single critical section. In a combined footing, the top bars along x resist the hogging moment between the columns, and the bottom bars resist the sagging moments under the columns and in the transverse direction.
Moment Demand with the Strip Average Method
Με την Strip average method (η προεπιλεγμένη Moment Demand Calculation), the footing is treated like a wide beam in each direction: the Wood-Armer moments of the plate elements are summed across the width of the footing, which gives the total moment carried by that width at each section. This is done for the top and bottom layers, along x and along z, under the ultimate load combinations (envelope).
- Along x, the strip covers the full width of the footing, and one moment diagram covers both columns.
- Along z, the footing is divided into two design strips at the midpoint between the column centres, and each column has its own diagram.
- Bottom layer: \( M_{u} \) is the largest strip moment at the column faces.
- Top layer: \( M_{u} \) is the largest hogging (αρνητικός) strip moment anywhere along the strip.
The moment diagrams can be viewed in the Αποτελέσματα tab by opening Diagrams, choosing Στιγμή στο Diagram λίστα, and picking the Στρώμα και Κατεύθυνση. In the example, the top layer along x has a maximum hogging moment of 154.65 kN-m, near midway between the columns:

Φιγούρα 3. Strip average moment diagram, top layer along x (Αποτελέσματα, Diagrams button)
The calculation report shows the same diagram for each layer and direction, with a table of the maximum moment, its coordinates and the governing load combination, followed by the utility ratio:

Peak Wood-Armer Method
Με την Peak wood-armer method, \( M_{u} \) is instead the maximum Wood-Armer moment per unit width found anywhere over the footing, for the top and bottom layers in both directions, and the capacity is calculated per unit width (12 in or 1000 χιλ). Because it uses the peak moment rather than the moment spread over the width, it is usually more conservative. The Wood-Armer moments can be viewed in the Αποτελέσματα tab with the Wood Armer κουμπί, by picking the Υπόθεση, Στρώμα και Κατεύθυνση στο View Options. In the example, the peak top moment along x is 105.17 kN-m/m, while the strip average moment of 154.65 kN-m over the 1.5 m width of the footing is 103.1 kN-m/m. This method is described in Συνδυασμένος σχεδιασμός ποδιών σύμφωνα με το ACI 318-14.

Κάμψη ικανότητας
With the strip average method, ο Κάμψη ικανότητας ή \( \phi M_{n} \) is calculated for the width of the strip, with the bars of the layer across that width (along z, the share of the bars in each strip, in proportion to its width), χρησιμοποιώντας την εξίσωση 13:
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 13)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
ϕκάμψη = Flexural strength reduction factor (Τραπέζι 21.2.2)
ΕΝΑμικρό = Area of the tension bars of the layer across the strip width (σε2, χιλ2)
φάκαι = Reinforcement strength (psi, MPa)
d = Distance from the extreme compression fiber to the centroid of the tension reinforcement (σε, χιλ)
a = Depth of the equivalent rectangular stress block (σε, χιλ)
b = Strip width: the full width of the footing along x, the strip of each column along z (σε, χιλ)
The strength reduction factor depends on the net tensile strain \( \varepsilon_{t} \), found from the neutral axis depth \( c = a/\beta_{1} \) (β1 από τον πίνακα 22.2.2.4.3) and a concrete strain of 0.003. ACI 318-19 compares it with the yield strain of the reinforcement \( \varepsilon_{ty} = f_{y}/E_{s} \):
[math] \phi_{\text{flexure}} = 0.65 + 0.25 \times \frac{\varepsilon_{t} – \varepsilon_{ty}}{0.003} \quad \text{(Table 21.2.2)} [math]
with ϕ = 0.90 πότε \( \varepsilon_{t} \geq \varepsilon_{ty} + 0.003 \) (tension-controlled) and ϕ = 0.65 πότε \( \varepsilon_{t} \leq \varepsilon_{ty} \) (compression-controlled). The report shows a warning when the section is not tension-controlled. When the tension steel ratio exceeds the balanced ratio, the section is checked as doubly reinforced, with the other layer as compression steel.
In the example, ο 8 top bars along x (1608.5 mm²) with d = 417 mm give \( \phi M_{n} \) = 163.25 kN-m, and the top layer ratio along x is 154.65/163.25 = 0.947.
The provided reinforcement of each layer, προς κάθε κατεύθυνση, is also compared to the minimum area of 0.0018 ΕΝΑσολ (Ενότητα 8.6.1.1), where Aσολ is the gross area of the footing section perpendicular to the bars.
Η ζήτηση ροπής και η χωρητικότητα ροπής πρέπει να πληρούν την ακόλουθη εξίσωση για να πληρούν τις απαιτήσεις σχεδιασμού του ACI 318-19:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 14, Section 7.5.1.1(a))} [math]
Ίδρυμα SkyCiv, σε συμμόρφωση με την Εξίσωση 14, calculates the flexural utility ratio by taking Flexural Demand over Flexural Capacity, for the top and bottom layers along x and for each strip along z. Το Κάμψη ratio in the Design Checks Summary is the largest of the top, bottom and minimum reinforcement ratios (0.947 in the example).
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 15)} [math]
Other Design Checks
Besides the checks above, the calculation report of a combined footing designed to ACI 318-19 includes the stability checks, the load transfer at the column bases, the development length of the bars and a detailing check. Each one gives a utilization ratio in the Σχεδιασμός Έλεγχοι Περίληψη Αγοράστε το μοντέλο φόρτωσης τώρα Αποτελέσματα αυτί. The largest ratio governs the design, and the footing fails when it is greater than 1.0. A check that does not apply to the loads (for example sliding without horizontal loads) is shown with a dash.
Ανύψωση
The uplift check compares the upward forces with the forces holding the footing down, considering axial loads only: the column loads, the self-weights of the columns, footing and soil, and the buoyant force. When no service load combination produces uplift, the check is not needed.
Ανατροπή
Overturning is checked by summing the moments of all the forces about the toe and the heel of the footing, προς κάθε κατεύθυνση, for all the service load combinations. Η διακυβέρνηση (smallest) παράγοντας ασφάλειας, stabilising moment over overturning moment, is compared with the Ανατροπή factor of safety in the Παράγοντες Σχεδιασμού tab of the Loads. If the loads produce no overturning moment, the check is not needed.
Ολίσθηση
Sliding is checked in each direction by dividing the horizontal resisting forces by the horizontal force applied to the footing, with both taken from the same service load combination (the one with the lowest factor of safety). The resisting forces are the friction between the footing base and the soil (none under net uplift), the passive soil pressure and the cohesion of the soil. The factor of safety is compared with the Ολίσθηση factor of safety in the Παράγοντες Σχεδιασμού αυτί. If no horizontal force acts on the footing, the check is not needed.
Διπλή διάτμηση
Το Διπλή διάτμηση check verifies the bearing of each column on the footing (Ενότητα 22.8.3.2). The factored axial load of the column is compared with the design bearing strength, with ϕ = 0.65:
[math] \phi B_{n} = \min \left( \phi \times 0.85 f’_{c} A_{1} \sqrt{\frac{A_{2}}{A_{1}}}, \; \phi \times 2 \times 0.85 f’_{c} A_{1} \right) \quad \text{(Eq. 16)} [math]
ΕΝΑ1 = Loaded area (the column area)
ΕΝΑ2 = Base of the frustum with 1 κάθετη έως 2 horizontal side slopes under the column, wholly within the footing: its projection beyond the column is limited by the nearest footing edge and by 2 times the footing thickness
The larger ratio of the two columns is listed as Διπλή διάτμηση (0.560 in the example). The report also compares the area of the dowel bars of each column with the minimum of 0.005 times the column area (Ενότητα 16.3.4.1).
Διπλή διάτμηση
Το Διπλή διάτμηση check covers the column dowel bars and the flexural bars of the footing:
- Column dowel bars: the compression development length (Ενότητα 25.4.9), plus the bend of the dowel, must fit in the footing thickness.
- Flexural bars: at each column face, the force in the bars must be developed on each side of the section (Ενότητα 13.2.8.2). The tension development length of straight bars (Ενότητα 25.4.2) or hooked bars (Ενότητα 25.4.3, depending on the bar ends chosen in the Reinforcement tab) is compared with the anchorage length available from the column face to the end of the bar.
The checks can be turned on or off in the design settings (Perform dowel bars check, Perform top bars check και Perform bottom bars check). In the example, the Development Length ratio of 1.231 comes from the bottom bars along x at the outer face of Column 1: μόνο 175 mm is available (ο 250 mm X-edge Distance minus the 75 mm cover), while the hooked bars need 215.35 χιλ. Increasing the X-edge Distance of the columns gives the bars the anchorage they need. The development length checks are explained in more detail in the ACI 318 (2019) Οδηγός ελέγχου μήκους ανάπτυξης, written for isolated footings.
Λεπτομέρειες
Το Λεπτομέρειες check verifies that the footing thickness can hold the hooked ends of the top and bottom bars (90° or 180° hooks), with their bend and extension and the top and bottom covers.
Προγραμματιστής προϊόντος
BSc (Εμφύλιος), MSc (Εμφύλιος)
βιβλιογραφικές αναφορές
- Απαιτήσεις κωδικού δόμησης για δομικό σκυρόδεμα (ACI 318-19) και Σχολιασμός (ACI 318R-19). Αμερικανικό Ινστιτούτο Σκυροδέματος, 2019.
- ACI Committee 421. Guide to Shear Reinforcement for Slabs (ACI 421.1R-20). Αμερικανικό Ινστιτούτο Σκυροδέματος, 2020.