SkyCiv Load Generator calculates NBCC 2015 seismic loads for buildings with the Equivalent Static Force Procedure of the National Building Code of Canada 2015. It gets the seismic hazard values for your site in Canada, then gives you the design spectral acceleration, the specified lateral earthquake force (ベースせん断), the vertical distribution of seismic forces and the overturning moments. This page explains each input of the seismic workflow and how the calculation uses it.
Free accounts can try the workflow for up to 3 週ごとに解決します. With a Professional Account or the スタンドアロンの負荷ジェネレータモジュール, you get unlimited solves, the full seismic results and the detailed seismic calculation report.
Workflow Overview
The NBCC 2015 seismic workflow follows the same top-to-bottom order as the rest of the SkyCiv Load Generator:
- 選択する NBCC 2015 as the design code.
- に サイトデータ, を選択 重要性カテゴリー と, 下 For Seismic Load, の サイトクラス, then enter an address in Canada.
- Review the Seismic Hazard Values returned for the site.
- に 構造データ, を選択 建物 structure and enter its dimensions.
- 開いた 地震荷重, define the seismic parameters and the floor weights, and confirm them.
- クリック 荷重の計算 and review the results.
NBCC用 2015, the seismic calculation is available for the 建物 structure only. NBCC 2015 seismic calculations are done in metric units (メートル, kN). If you design to the newer edition, 見る NBCC 2020 地震荷重の計算.
サイトデータ: NBCC 2015 Seismic Hazard Values
重要性カテゴリー
重要性カテゴリー (低, 正常, High or Post Disaster) is selected in Site Data and is shared with the wind and snow calculations. For the seismic calculation, it sets the earthquake importance factor \(I_{E}\) of Table 4.1.8.5, used at the ultimate limit state:
| 重要性カテゴリー | \(I_{E}\) |
|---|---|
| 低 | 0.8 |
| 正常 | 1.0 |
| 高い | 1.3 |
| Post Disaster | 1.5 |
サイトクラス
開いた For Seismic Load in Site Data and select the サイトクラス (Table 4.1.8.4-A of NBCC 2015):
- あ – Hard rock
- B – Rock
- C – Very dense soil and soft rock
- D – Stiff soil
- E – Soft soil
Site Class F (soils that need a site-specific evaluation) is not available. Selecting a Site Class looks up the seismic data for the address you entered and enables the 地震荷重 button for buildings. NBCC 2015 seismic hazard values are given for a 2% probability of exceedance in 50 年 (2475-year return period), so there is no probability to select.
Seismic Hazard Values
Once the location and Site Class are set, the Load Generator fills in the Seismic Hazard Values for the site:
| 入力 | それは何ですか |
|---|---|
| \(S_{a}(0.2)\), \(S_{a}(0.5)\), \(S_{a}(1.0)\), \(S_{a}(2.0)\), \(S_{a}(5.0)\), \(S_{a}(10.0)\) | 5% damped spectral response acceleration at periods of 0.2, 0.5, 1.0, 2.0, 5.0 と 10.0 s, in g |
| PGA | Peak ground acceleration, in g |
| PGV | Peak ground velocity, m/sで |
All eight values are required. You can edit them, for example to use the values of the NBCC 2015 seismic hazard calculator for your site. The map pop-up also shows the values and the source they come from.
How the Site Data Is Used
The calculation turns the site hazard into the design spectral acceleration \(S(T)\) of Article 4.1.8.4:
- It sets the reference peak ground acceleration: \(PGA_{ref} = 0.8\,PGA\) いつ \(S_{a}(0.2)/PGA < 2.0\), と \(PGA_{ref} = PGA\) さもないと.
- It reads the site coefficients \(F(T)\), \(F(PGA)\) と \(F(PGV)\) for the selected Site Class and \(PGA_{ref}\) from Tables 4.1.8.4-B to 4.1.8.4-I, interpolating between table values.
- 計算します \(S(T)\) at each period from \(F(T)\) と \(S_{a}(T)\), as in Article 4.1.8.4(9).
構造データ
選択する 建物 in Structure Data and enter its dimensions. The height from the ground to the top of the roof is used as the structure height \(h_{n}\) in the approximate fundamental period.

図 1. Structure Data for a building.
NBCC 2015 地震荷重パラメータ
クリック 地震荷重 button to define the seismic parameters. When you confirm them with Confirm Seismic Parameters, the checkbox beside the button is ticked and the seismic load is included in the calculation:

図 2. Seismic Load button and checkbox.
The seismic parameters for NBCC 2015 それは:
| 入力 | デフォルト | How it is used |
|---|---|---|
| Structure System | Concrete Moment-Resisting Frame | Sets the formula for the approximate period \(T_{a}\) and the type of system used for the higher mode factor \(M_{v}\) and the overturning moment reduction factor \(J\) (テーブル 4.1.8.11). It also selects the minimum base shear: で \(T = 4.0\,\text{s}\) for coupled walls and wall/wall-frame systems, で \(T = 2.0\,\text{s}\) for the others. |
| \(T_{a}\) (または \(T_{s}\)) | Filled in from the Structure System | Fundamental lateral period of vibration of the building (Article 4.1.8.1(7)), すぐに. Must be between 0 と 10. |
| \(R_{d}\) | 4.0 | Ductility-related force modification factor (テーブル 4.1.8.9). Must be between 0 と 10. |
| \(R_{o}\) | 1.0 | Overstrength-related force modification factor (テーブル 4.1.8.9). Must be between 0 と 10. |
| フロアウェイト | なし | レベル, Elevation and Weight of each floor, used for the seismic weight \(W\), the vertical distribution of the base shear and the overturning moments. |

図 3. Seismic Load parameters (shared by NBCC 2015 およびNBCC 2020).
Structure System and Approximate Period
When you select a Structure System, the Load Generator fills in \(T_{a}\) from the ground to top of roof height \(h_{n}\) (in m):
| Structure System | Approximate period |
|---|---|
| Steel Moment-Resisting Frame | \(T_{a} = 0.085\,h_{n}^{0.75}\) |
| Concrete Moment-Resisting Frame | \(T_{a} = 0.075\,h_{n}^{0.75}\) |
| Moment-Resisting Frame (その他) | \(T_{a} = 0.1N\) |
| Braced Frame | \(T_{a} = 0.025\,h_{n}\) |
| Coupled Wall | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
| Wall/Wall-Frame | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
| All other structural systems | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
ために Moment-Resisting Frame (その他), \(T_{a}\) is not filled in: enter it yourself, と \(N\) the number of storeys above ground level. If the field is left empty, the calculation uses the number of rows in the Floor Weights table as \(N\). You can replace \(T_{a}\) with a period from a dynamic analysis within the limits of Article 4.1.8.11(3): it changes \(S(T_{a})\) and the base shear.
フロアウェイト
クリック Add Floor Weights Data to add a row per level, と 晴れ to empty the table. Each row needs a Level name, an Elevation above the base and a Weight, both greater than 0. The sum of the weights is the seismic weight \(W\) 建物の (Article 4.1.4.1). At least one row is required to calculate.
Equivalent Static Force Procedure
The Load Generator calculates the specified lateral earthquake force \(V\) with the Equivalent Static Force Procedure of Article 4.1.8.11:
[math] V = \frac{S(T_{a})\,M_{v}\,I_{E}\,W}{R_{d}\,R_{o}} [math]
\(V\) is taken not less than the minimum base shear:
[math] V_{min} = \frac{S(2.0)\,M_{v}\,I_{E}\,W}{R_{d}\,R_{o}} [math]
for moment-resisting frames, braced frames and other systems (と \(S(4.0)\) と \(M_{v}\) で 4.0 s for walls, coupled walls and wall-frame systems). For an \(R_{d}\) の 1.5 以上, \(V\) need not be more than:
[math] V_{max} = \max\left(\frac{2}{3}\,\frac{S(0.2)\,I_{E}\,W}{R_{d}\,R_{o}},\ \frac{S(0.5)\,I_{E}\,W}{R_{d}\,R_{o}}\right) [math]
\(S(T_{a})\) is interpolated from the design spectrum, と \(M_{v}\) と \(J\) come from Table 4.1.8.11 with the ratio \(S(0.2)/S(5.0)\), \(T_{a}\) and the Structure System. The base shear is then distributed over the height of the building (Article 4.1.8.11(7)):
[math] F_{x} = \frac{(V – F_{t})\,W_{x}h_{x}}{\sum W_{i}h_{i}} [math]
どこ \(F_{t} = 0.07\,T_{a}V \le 0.25V\) is a concentrated force added at the top level, と \(F_{t} = 0\) いつ \(T_{a} < 0.7\,\text{s}\). The overturning moment at each level, \(M_{x}\), is reduced by the factor \(J_{x}\) of Article 4.1.8.11(8).
結果
クリック 荷重の計算 in the menu bar to run the calculation. The results show:
- The summary of the seismic parameters, 含む \(I_{E}\), \(T_{a}\), \(M_{v}\), \(J\) and the base shear \(V\).
- The vertical distribution of seismic forces, \(F_{x}\) レベルごと.
- The overturning moments, \(M_{x}\) レベルごと.
- The design spectral acceleration \(S(T)\) table and chart, と \(S(T_{a})\) マークされた.
Free users see the seismic parameters only. 力, overturning moments and design spectral acceleration are shown to Professional account users and to users of the standalone Load Generator module. クリック レポートをダウンロード beside 荷重の計算 for a summary report of the inputs and results.
Detailed Seismic Calculation Report
Detailed Seismic Calculation Report button in the results opens a step-by-step NBCC 2015 計算, available to Professional account users and to users of the スタンドアロンの負荷ジェネレータモジュール. It shows every parameter, formula and code reference used: the site seismic parameters, の \(F(T)\) と \(S(T)\) 表, \(M_{v}\) と \(J\), the base shear checks, the vertical distribution of forces with a diagram, the overturning moments and the design spectral acceleration chart. It is ready to attach to your design calculations.
参考文献
- カナダ建築消防法委員会. (2015). 地震荷重と影響. に カナダの建築基準法 2015 (巻. 1, ディビジョンB, 部 4, サブセクション 4.1.8). カナダ国立研究評議会.