SkyCiv Load Generator calculates NBCC 2015 seismic loads for buildings with the Equivalent Static Force Procedure of the National Building Code of Canada 2015. It gets the seismic hazard values for your site in Canada, then gives you the design spectral acceleration, the specified lateral earthquake force (Basisscherung), the vertical distribution of seismic forces and the overturning moments. This page explains each input of the seismic workflow and how the calculation uses it.
Free accounts can try the workflow for up to 3 Berechnungen pro Woche. With a Professional Account or the eigenständigen Lastgeneratormoduls, you get unlimited solves, the full seismic results and the detailed seismic calculation report.
Workflow Overview
The NBCC 2015 seismic workflow follows the same top-to-bottom order as the rest of the SkyCiv Load Generator:
- Wählen NBCC 2015 as the design code.
- Im Standortdaten, wähle aus Wichtigkeitskategorie und, unter Für seismische Belastung, der Baugrundklasse, then enter an address in Canada.
- Review the Seismic Hazard Values returned for the site.
- Im Tragwerksdaten, wähle aus Gebäude structure and enter its dimensions.
- Öffnen Erdbebenlast, define the seismic parameters and the floor weights, and confirm them.
- Klicken Sie auf Lasten berechnen and review the results.
Für NBCC 2015, the seismic calculation is available for the Gebäude structure only. NBCC 2015 seismic calculations are done in metric units ( Mio., kN). If you design to the newer edition, sehen NBCC 2020 Berechnungen der Erdbebenlast.
Standortdaten: NBCC 2015 Seismic Hazard Values
Wichtigkeitskategorie
Das Wichtigkeitskategorie (Niedrig, Normal, High or Post Disaster) is selected in Site Data and is shared with the wind and snow calculations. For the seismic calculation, it sets the earthquake importance factor \(I_{E}\) of Table 4.1.8.5, used at the ultimate limit state:
| Wichtigkeitskategorie | \(I_{E}\) |
|---|---|
| Niedrig | 0.8 |
| Normal | 1.0 |
| Hoch | 1.3 |
| Post-Katastrophe | 1.5 |
Baugrundklasse
Öffnen Für seismische Belastung in Site Data and select the Baugrundklasse (Table 4.1.8.4-A of NBCC 2015):
- Ein – Hard rock
- B. – Rock
- C. – Very dense soil and soft rock
- D. – Stiff soil
- E. – Soft soil
Site Class F (soils that need a site-specific evaluation) is not available. Selecting a Site Class looks up the seismic data for the address you entered and enables the Erdbebenlast button for buildings. NBCC 2015 seismic hazard values are given for a 2% probability of exceedance in 50 Jahre (2475-year return period), so there is no probability to select.
Seismic Hazard Values
Once the location and Site Class are set, the Load Generator fills in the Seismic Hazard Values for the site:
| Eingang | Was es ist |
|---|---|
| \(S_{a}(0.2)\), \(S_{a}(0.5)\), \(S_{a}(1.0)\), \(S_{a}(2.0)\), \(S_{a}(5.0)\), \(S_{a}(10.0)\) | 5% damped spectral response acceleration at periods of 0.2, 0.5, 1.0, 2.0, 5.0 und 10.0 s, in g |
| PGA | Peak ground acceleration, in g |
| PGV | Peak ground velocity, in m/s |
All eight values are required. You can edit them, for example to use the values of the NBCC 2015 seismic hazard calculator for your site. The map pop-up also shows the values and the source they come from.
How the Site Data Is Used
The calculation turns the site hazard into the design spectral acceleration \(S(T)\) of Article 4.1.8.4:
- It sets the reference peak ground acceleration: \(PGA_{ref} = 0.8\,PGA\) Wann \(S_{a}(0.2)/PGA < 2.0\), und \(PGA_{ref} = PGA\) Andernfalls.
- It reads the site coefficients \(F(T)\), \(F(PGA)\) und \(F(PGV)\) for the selected Site Class and \(PGA_{ref}\) from Tables 4.1.8.4-B to 4.1.8.4-I, interpolating between table values.
- Es rechnet \(S(T)\) at each period from \(F(T)\) und \(S_{a}(T)\), as in Article 4.1.8.4(9).
Tragwerksdaten
Wählen Gebäude in Structure Data and enter its dimensions. The height from the ground to the top of the roof is used as the structure height \(h_{n}\) in the approximate fundamental period.

Abbildung 1. Structure Data for a building.
NBCC 2015 Parameter für seismische Belastungen
Klicken Sie auf die Erdbebenlast button to define the seismic parameters. When you confirm them with Bestätigen Sie die seismischen Parameter, the checkbox beside the button is ticked and the seismic load is included in the calculation:

Abbildung 2. Seismic Load button and checkbox.
The seismic parameters for NBCC 2015 sind:
| Eingang | Die Druckfestigkeit wird gemäß AS4600 berücksichtigt | How it is used |
|---|---|---|
| Structure System | Concrete Moment-Resisting Frame | Sets the formula for the approximate period \(T_{a}\) and the type of system used for the higher mode factor \(M_{v}\) and the overturning moment reduction factor \(J\) (Tabelle 4.1.8.11). It also selects the minimum base shear: beim \(T = 4.0\,\text{s}\) for coupled walls and wall/wall-frame systems, beim \(T = 2.0\,\text{s}\) for the others. |
| \(T_{a}\) (oder \(T_{s}\)) | Filled in from the Structure System | Fundamental lateral period of vibration of the building (Article 4.1.8.1(7)), in Sekunden. Must be between 0 und 10. |
| \(R_{d}\) | 4.0 | Ductility-related force modification factor (Tabelle 4.1.8.9). Must be between 0 und 10. |
| \(R_{o}\) | 1.0 | Overstrength-related force modification factor (Tabelle 4.1.8.9). Must be between 0 und 10. |
| Bodengewichte | Keiner | Niveau, Elevation and Weight of each floor, used for the seismic weight \(W\), the vertical distribution of the base shear and the overturning moments. |

Abbildung 3. Seismic Load parameters (shared by NBCC 2015 und NBCC 2020).
Structure System and Approximate Period
When you select a Structure System, the Load Generator fills in \(T_{a}\) from the ground to top of roof height \(h_{n}\) (in m):
| Structure System | Approximate period |
|---|---|
| Steel Moment-Resisting Frame | \(T_{a} = 0.085\,h_{n}^{0.75}\) |
| Concrete Moment-Resisting Frame | \(T_{a} = 0.075\,h_{n}^{0.75}\) |
| Momentfester Rahmen (Andere) | \(T_{a} = 0.1N\) |
| Braced Frame | \(T_{a} = 0.025\,h_{n}\) |
| Coupled Wall | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
| Wall/Wall-Frame | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
| All other structural systems | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
Für Momentfester Rahmen (Andere), \(T_{a}\) ist nicht ausgefüllt: Geben Sie es selbst ein, mit \(N\) die Anzahl der Stockwerke über dem Boden. If the field is left empty, the calculation uses the number of rows in the Floor Weights table as \(N\). You can replace \(T_{a}\) with a period from a dynamic analysis within the limits of Article 4.1.8.11(3): it changes \(S(T_{a})\) and the base shear.
Bodengewichte
Klicken Sie auf Add Floor Weights Data to add a row per level, und klar to empty the table. Each row needs a Level name, an Elevation above the base and a Weight, both greater than 0. The sum of the weights is the seismic weight \(W\) des Gebäudes (Article 4.1.4.1). At least one row is required to calculate.
Equivalent Static Force Procedure
The Load Generator calculates the specified lateral earthquake force \(V\) with the Equivalent Static Force Procedure of Article 4.1.8.11:
[math] V = \frac{S(T_{a})\,M_{v}\,I_{E}\,W}{R_{d}\,R_{o}} [math]
\(V\) is taken not less than the minimum base shear:
[math] V_{min} = \frac{S(2.0)\,M_{v}\,I_{E}\,W}{R_{d}\,R_{o}} [math]
for moment-resisting frames, braced frames and other systems (mit \(S(4.0)\) und \(M_{v}\) beim 4.0 s for walls, coupled walls and wall-frame systems). For an \(R_{d}\) von 1.5 oder mehr, \(V\) need not be more than:
[math] V_{max} = \max\left(\frac{2}{3}\,\frac{S(0.2)\,I_{E}\,W}{R_{d}\,R_{o}},\ \frac{S(0.5)\,I_{E}\,W}{R_{d}\,R_{o}}\right) [math]
\(S(T_{a})\) is interpolated from the design spectrum, und \(M_{v}\) und \(J\) come from Table 4.1.8.11 with the ratio \(S(0.2)/S(5.0)\), \(T_{a}\) and the Structure System. The base shear is then distributed over the height of the building (Article 4.1.8.11(7)):
[math] F_{x} = \frac{(V – F_{t})\,W_{x}h_{x}}{\sum W_{i}h_{i}} [math]
wobei \(F_{t} = 0.07\,T_{a}V \le 0.25V\) is a concentrated force added at the top level, und \(F_{t} = 0\) Wann \(T_{a} < 0.7\,\text{s}\). The overturning moment at each level, \(M_{x}\), is reduced by the factor \(J_{x}\) of Article 4.1.8.11(8).
Ergebnisse
Klicken Sie auf Lasten berechnen in the menu bar to run the calculation. The results show:
- The summary of the seismic parameters, darunter \(I_{E}\), \(T_{a}\), \(M_{v}\), \(J\) and the base shear \(V\).
- The vertical distribution of seismic forces, \(F_{x}\) pro Ebene.
- The overturning moments, \(M_{x}\) pro Ebene.
- The design spectral acceleration \(S(T)\) table and chart, mit \(S(T_{a})\) marked.
Kostenlose Benutzer sehen nur die seismischen Parameter. Die Mächte, overturning moments and design spectral acceleration are shown to Professional account users and to users of the standalone Load Generator module. Klicken Sie auf Bericht herunterladen beside Lasten berechnen for a summary report of the inputs and results.
Detaillierter seismischer Berechnungsbericht
Das Detaillierter seismischer Berechnungsbericht button in the results opens a step-by-step NBCC 2015 Berechnung, available to Professional account users and to users of the eigenständigen Lastgeneratormoduls. It shows every parameter, formula and code reference used: the site seismic parameters, der \(F(T)\) und \(S(T)\) Tabelle, \(M_{v}\) und \(J\), the base shear checks, the vertical distribution of forces with a diagram, the overturning moments and the design spectral acceleration chart. It is ready to attach to your design calculations.
Quellen
- Kanadische Kommission für Bau- und Brandschutzvorschriften. (2015). Erdbebenlast und Auswirkungen. Im Nationales Baugesetz von Kanada 2015 (Vol. 1, Abteilung B., Teil 4, Unterabschnitt 4.1.8). Nationaler Forschungsrat von Kanada.