This page explains how SkyCiv Foundation designs a combined footing to ACI 318-19: rodamiento del suelo, cortante en una dirección, punching shear and flexure, with the equations used and the results shown in the software and the calculation report, followed by the other design checks (levantamiento, volcamiento, deslizamiento, transferencia de carga, development length and detailing). Flexure is described with the default Strip average method, y el Método del armador de madera pico is summarized for comparison.
A zapata combinada is a single footing supporting two columns. It is commonly used when the columns are too close to each other, or a column is too close to a property line, for two separate isolated footings. SkyCiv Foundation meshes the footing into plate elements supported on the soil (modeled with the subgrade modulus) and analyzes it with finite element analysis (FEA). The soil pressures, shears and moments used in the design checks below come from these FEA results. To design to the 2019 edición, seleccione Instituto Americano del Concreto como el Código de Diseño y ACI 318 (2019) como la versión cuando inicias un nuevo archivo, luego elige Zapata combinada. The same checks to the 2014 edition are described in Diseño de zapata combinada de acuerdo con ACI 318-14.

The example shown on this page is a 3000 × 1500 × 500 mm combined footing with two 300 × 300 mm columns placed 250 mm from the ends of the footing (X-edge Distance), #5 bars at 200 mm in both directions at the top and bottom, y un 75 mm cover. Columna 1 carries a dead load of 200 kN and a live load of 100 kN, y columna 2 a dead load of 250 kN and a live load of 120 kN. The x-direction is the direction joining the two columns.
Design Settings for ACI 318-19
The methods used for the checks are set in Edit Design Settings (Details tab). Para ACI 318-19, la Cálculo de la demanda de momento offers the Strip average method (defecto) y el Método del armador de madera pico. The settings also hold the Realice una verificación de corte unidireccional toggle and the Factor de borde de corte de punzonamiento (0.5 por defecto), as well as the switches of the load transfer and development length checks.

Combined Footing Design Checks to ACI 318-19
Dimension Requirements and Soil Bearing
To size a combined footing, Servicio (sin factorizar) loads such as Dead (re), En Vivo (L), Viento (W) and Seismic (E) are combined with the service load combinations. The governing combination is the design load, and the base area is proportioned so that the allowable soil pressure is not exceeded (ACI 318-19, Sección de 13.3.1.1):
[math] q_{a} = \frac{P1_{n} + P2_{n}}{A} \quad \text{(Eq. 1)} [math]
qa = Presión admisible del suelo
P1norte, P2norte = Unfactored loads at Column 1 (izquierda) y columna 2 (derecha)
A = área de cimentación
Solving Equation 1 for the area gives a first estimate of the footing dimensions:
[math] A = \frac{P1_{n} + P2_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
SkyCiv Foundation does not size the footing from Equation 1a: the dimensions are inputs (Pestaña Geometría), and the software checks them. El Rodamiento del suelo ratio is the maximum soil pressure from the FEA results of the service load combinations (sobre), which includes the effect of the column moments and of the eccentricity of the loads, divided by the allowable soil bearing capacity entered in the Soil tab:
[math] \text{Utility Ratio} = \frac{q_{sls,max}}{q_{a}} \quad \text{(Eq. 2)} [math]
In the example, the maximum service soil pressure is 224.1 kPa, under Column 2, which carries the larger load, and the Soil Bearing ratio is 0.448. The soil pressure contour and the ratio of every check are shown in the Resultados lengüeta:

Cortante en una dirección
El estado límite de corte unidireccional, también conocido como corte de viga, treats the footing like a wide beam that may fail in shear along a critical section located at a distance "d" de la cara de una columna. It is checked when Realice una verificación de corte unidireccional is enabled in the design settings (activado de forma predeterminada).
El Demanda de corte unidireccional o \( V_{u} \) is taken from the strip average shear diagrams of the FEA (ultimate load combinations): the shear forces of the plate elements are summed across the width of the footing, and the diagram is read at the critical sections, located at the effective depth of the bottom bars in that direction from each column face (or at the edge of the footing when that distance falls outside it). The largest absolute shear at these sections is the demand.
- Along x (the direction joining the columns), one diagram covers the whole footing, with the critical sections on both sides of both columns.
- Along z, each column has its own diagram, through that column.
The diagrams can be viewed in the Resultados tab by opening Diagramas and choosing Cortante en una dirección en el Diagrama lista. In the example, the critical sections along x are 417 mm (the effective depth of the bottom x-bars) from the inner faces of the columns, and the demand is 158.70 kN, next to Column 2:

Figura 1. Critical sections and shear diagram of one-way shear along x (Resultados, Botón de diagramas)
El Capacidad de corte unidireccional o \( \phi V_{c} \) is calculated with Equation 3 (Tabla 22.5.5.1(c), for members without shear reinforcement). The size effect factor \( \lambda_{s} \) is neglected for footings, as permitted by Sección de 13.2.6.2.
[math] \phi V_{c} = \phi_{\text{shear}} \times 8 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Imperial)} [math]
o
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.66 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Metric)} [math]
[math] \rho_{w} = \frac{n \times A_{b}}{L \times d} [math]
ϕel cortante = Factor de reducción de la resistencia al corte, 0.75 (Tabla 21.2.1)
λ = Factor de modificación para hormigón ligero
ρw = Ratio of the bottom bars in the direction checked
norte, Ab = Number and area of these bars, across the footing dimension L perpendicular to them
F’c = Resistencia del hormigón especificada (psi, MPa)
bw = Width resisting the shear (in, mm)
d = Effective depth of the bottom bars in the direction checked (in, mm)
Along x, \( b_{w} \) is the full width of the footing (its dimension along z). Along z, the footing is divided into two design strips at the midpoint between the two column centres, and each column’s shear is checked against the capacity of its own strip, con \( b_{w} \) equal to the strip width. In the example, both strips are 1500 mm de ancho.
The calculation report shows the shear diagram of each direction, followed by the demand, the capacity and the ratio. Along x, \( \phi V_{c} \) = 192.9 kN and the ratio is 158.7/192.9 = 0.823:

La demanda de corte y la capacidad de corte deben cumplir con la siguiente ecuación para cumplir con los requisitos de diseño de ACI 318-19:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 4, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, de acuerdo con la Ecuación 4, calculates the one-way shear utility ratio by taking Shear Demand over Shear Capacity, along x and for each column along z. The largest ratio is listed as Cizalla unidireccional en el Resumen de comprobaciones de diseño.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 5)} [math]
Cortante en dos direcciones (Cizalla punzonadora)
The two-way shear limit state, también conocido como punzonamiento, has its critical section at a distance "d/2" de las caras de la columna, alrededor del perímetro de la columna (Sección de 22.6.4.1). Su longitud es el perímetro crítico. \( b_{o} \). The check is done for each column. The critical perimeters can be viewed in the Resultados tab by opening Diagramas and choosing Cizalla punzonadora en el Diagrama lista:

Figura 2. Critical perimeters of two-way shear (Resultados, Botón de diagramas)
The effective depth d is the average of the effective depths of the bottom bars in both directions (409 mm in the example). Cuando la cara de una columna está más cerca del borde de una zapata que la Factor de borde de corte de punzonamiento veces d, el perímetro de ese lado se extiende hasta el borde de la zapata y no se cuenta en \( b_{o} \). La columna se clasifica entonces como interior., columna de borde o esquina, que establece \( \alpha_{s} \) = 40, 30 o 20 (Sección de 22.6.5.3). Si la columna está cerca de dos bordes opuestos, the punching shear check is skipped for that column, como gobierna el corte unidireccional. A round column is taken as an equivalent square column with sides equal to its diameter. In the example, both columns are interior columns, con \( b_{o} \) = 4 × 709 = 2836 mm.
El Demanda de corte bidireccional se calcula en el perímetro crítico con el método basado en malla, del análisis de elementos finitos de la zapata. La fuerza ascendente proveniente de la presión del suelo dentro del perímetro crítico., \( F_{q} \), es la suma de las fuerzas de los elementos de la malla en esa área (the average pressure on each element times its area inside the perimeter, listed in a table of the report), y se resta de la carga factorizada de la columna. El esfuerzo cortante máximo \( v_{u} \) en el perímetro crítico también incluye los momentos de desequilibrio transferidos por corte excéntrico (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 6)} [math]
[math] \gamma_{v} = 1 – \frac{1}{1 + \frac{2}{3}\sqrt{b_{1}/b_{2}}} \quad \text{(Eq. 7)} [math]
PAGtu = Carga de columna factorizada
Fq = Resultant of the factored soil pressure inside the critical perimeter, summed over the FEA mesh elements
Cv = Fracción del momento de desequilibrio transferido por cortante excéntrico
Mtu = Momento desequilibrado: momento de la columna, más el corte de la columna multiplicado por la altura de la columna y el espesor de la zapata, minus the column load times the offset of the centroid of the critical section (edge and corner columns)
b1, b2 = Dimensions of the critical section perpendicular and parallel to the direction considered
c, Jc = Distancia al punto considerado y momento polar de inercia de la sección crítica
For edge and corner columns, \( \gamma_{v} \) and the stresses are calculated following ACI 421.1R-20. The maximum stress around the critical section is taken as the demand.
El Capacidad a cortante es el esfuerzo cortante de punzonamiento \( \phi v_{c} \), regido por el valor más pequeño de las ecuaciones 8, 9 y 10 por Sección de 22.6.5.2. Unlike ACI 318-14, la 2019 edition includes the size effect factor \( \lambda_{s} \) (Sección de 22.5.5.1.3), which reduces the capacity of footings with an effective depth over 10 in (250 mm). In the example, \( \lambda_{s} \) = 0.871 for d = 409 mm.
[math] \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + d/10}} \right) \quad \text{(Imperial)} \qquad \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + 0.004\,d}} \right) \quad \text{(Metric)} [math]
[math] v_{c,a} = 4 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c,b} = \left( 2 + \frac{4}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c,c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Imperial)} [math]
o
[math] v_{c,a} = 0.33 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c,b} = \left( 0.17 + \frac{0.33}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c,c} = \left( 0.17 + \frac{0.083 \times \alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
Nota: β es la relación entre el lado largo y el lado corto de la columna (1.0 para una columna redonda), y \( \alpha_{s} \) viene dado por la sección 22.6.5.3. ϕel cortante = 0.75 (Tabla 21.2.1).
λs = Size effect modification factor
λ = Factor de modificación para hormigón ligero
F’c = Resistencia del hormigón especificada (psi, MPa)
d = Altura efectiva, el promedio de las profundidades efectivas de las barras inferiores en ambas direcciones (in, mm)
blos = Perímetro crítico (in, mm)
The calculation report shows, for each column, the plan of the critical shear area, the soil pressure force \( F_{q} \), the stresses around the perimeter, and the capacity. Para columna 1 of the example, \( v_{u} \) = 0.261 MPa and \( \phi v_{c} \) = 0.980 MPa:

La demanda de corte y la capacidad de corte deben cumplir con la siguiente ecuación para cumplir con los requisitos de diseño de ACI 318-19:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 11, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, de acuerdo con la Ecuación 11, calculates the two-way shear utility ratio of each column by taking Shear Demand over Shear Capacity, tanto como tensiones. The larger ratio of the two columns is listed as Cizalla punzonadora en el Resumen de comprobaciones de diseño (0.318 in the example, from Column 2).
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 12)} [math]
Flexión
SkyCiv Foundation checks the top and bottom reinforcement in both directions against the moments of the whole footing from the FEA, rather than at a single critical section. In a combined footing, the top bars along x resist the hogging moment between the columns, and the bottom bars resist the sagging moments under the columns and in the transverse direction.
Moment Demand with the Strip Average Method
Con el Strip average method (el valor por defecto Cálculo de la demanda de momento), the footing is treated like a wide beam in each direction: the Wood-Armer moments of the plate elements are summed across the width of the footing, which gives the total moment carried by that width at each section. This is done for the top and bottom layers, a lo largo de x y a lo largo de z, bajo las combinaciones de carga finales (sobre).
- Along x, the strip covers the full width of the footing, and one moment diagram covers both columns.
- Along z, the footing is divided into two design strips at the midpoint between the column centres, and each column has its own diagram.
- Bottom layer: \( M_{u} \) is the largest strip moment at the column faces.
- Top layer: \( M_{u} \) is the largest hogging (negativo) strip moment anywhere along the strip.
The moment diagrams can be viewed in the Resultados tab by opening Diagramas, choosing Momento en el Diagrama lista, and picking the Capa y Dirección. In the example, the top layer along x has a maximum hogging moment of 154.65 kN-m, near midway between the columns:

Figura 3. Strip average moment diagram, top layer along x (Resultados, Botón de diagramas)
The calculation report shows the same diagram for each layer and direction, with a table of the maximum moment, its coordinates and the governing load combination, followed by the utility ratio:

Peak Wood-Armer Method
Con el Método del armador de madera pico, \( M_{u} \) is instead the maximum Wood-Armer moment per unit width found anywhere over the footing, para las capas superior e inferior en ambas direcciones, and the capacity is calculated per unit width (12 en o 1000 mm). Because it uses the peak moment rather than the moment spread over the width, it is usually more conservative. The Wood-Armer moments can be viewed in the Resultados tab with the Wood Armer ,, by picking the Caso, Capa y Dirección en el View Options. In the example, the peak top moment along x is 105.17 kN-m / m, while the strip average moment of 154.65 kN-m over the 1.5 m width of the footing is 103.1 kN-m / m. This method is described in Diseño de zapata combinada de acuerdo con ACI 318-14.

Capacidad de flexión
With the strip average method, la Capacidad de flexión o \( \phi M_{n} \) is calculated for the width of the strip, with the bars of the layer across that width (along z, the share of the bars in each strip, in proportion to its width), usando la ecuación 13:
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 13)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
ϕflexura = Flexural strength reduction factor (Tabla 21.2.2)
As = Area of the tension bars of the layer across the strip width (in2, mm2)
Fy = Reinforcement strength (psi, MPa)
d = Distance from the extreme compression fiber to the centroid of the tension reinforcement (in, mm)
a = Depth of the equivalent rectangular stress block (in, mm)
b = Strip width: the full width of the footing along x, the strip of each column along z (in, mm)
The strength reduction factor depends on the net tensile strain \( \varepsilon_{t} \), found from the neutral axis depth \( c = a/\beta_{1} \) (si1 de la tabla 22.2.2.4.3) and a concrete strain of 0.003. ACI 318-19 compares it with the yield strain of the reinforcement \( \varepsilon_{ty} = f_{y}/E_{s} \):
[math] \phi_{\text{flexure}} = 0.65 + 0.25 \times \frac{\varepsilon_{t} – \varepsilon_{ty}}{0.003} \quad \text{(Table 21.2.2)} [math]
with ϕ = 0.90 cuando \( \varepsilon_{t} \geq \varepsilon_{ty} + 0.003 \) (controlado por tensión) and ϕ = 0.65 cuando \( \varepsilon_{t} \leq \varepsilon_{ty} \) (controlado por compresión). The report shows a warning when the section is not tension-controlled. When the tension steel ratio exceeds the balanced ratio, the section is checked as doubly reinforced, with the other layer as compression steel.
In the example, la 8 top bars along x (1608.5 mm²) with d = 417 mm give \( \phi M_{n} \) = 163.25 kN-m, and the top layer ratio along x is 154.65/163.25 = 0.947.
The provided reinforcement of each layer, en cada dirección, is also compared to the minimum area of 0.0018 Agramo (Sección de 8.6.1.1), where Agramo is the gross area of the footing section perpendicular to the bars.
La demanda de momento y la capacidad de momento deben cumplir con la siguiente ecuación para cumplir con los requisitos de diseño de ACI 318-19:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 14, Section 7.5.1.1(a))} [math]
SkyCiv Foundation, de acuerdo con la Ecuación 14, calculates the flexural utility ratio by taking Flexural Demand over Flexural Capacity, for the top and bottom layers along x and for each strip along z. El Flexión ratio in the Design Checks Summary is the largest of the top, proporciones de refuerzo inferior y mínimo (0.947 in the example).
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 15)} [math]
Other Design Checks
Besides the checks above, the calculation report of a combined footing designed to ACI 318-19 includes the stability checks, the load transfer at the column bases, the development length of the bars and a detailing check. Each one gives a utilization ratio in the Resumen de verificaciones de diseño del Resultados lengüeta. The largest ratio governs the design, and the footing fails when it is greater than 1.0. A check that does not apply to the loads (for example sliding without horizontal loads) is shown with a dash.
Levantamiento
The uplift check compares the upward forces with the forces holding the footing down, considerando solo cargas axiales: the column loads, the self-weights of the columns, footing and soil, and the buoyant force. Cuando ninguna combinación de carga de servicio produce elevación, el cheque no es necesario.
Vuelco
Overturning is checked by summing the moments of all the forces about the toe and the heel of the footing, en cada dirección, for all the service load combinations. el gobernante (smallest) factor de seguridad, momento de estabilización sobre el momento de vuelco, se compara con el Vuelco factor de seguridad en el Factores de diseño tab of the Loads. If the loads produce no overturning moment, el cheque no es necesario.
Deslizamiento
Sliding is checked in each direction by dividing the horizontal resisting forces by the horizontal force applied to the footing, with both taken from the same service load combination (the one with the lowest factor of safety). The resisting forces are the friction between the footing base and the soil (ninguno bajo elevación neta), the passive soil pressure and the cohesion of the soil. The factor of safety is compared with the Deslizamiento factor de seguridad en el Factores de diseño lengüeta. If no horizontal force acts on the footing, el cheque no es necesario.
Transferencia de carga
El Transferencia de carga check verifies the bearing of each column on the footing (Sección de 22.8.3.2). The factored axial load of the column is compared with the design bearing strength, with ϕ = 0.65:
[math] \phi B_{n} = \min \left( \phi \times 0.85 f’_{c} A_{1} \sqrt{\frac{A_{2}}{A_{1}}}, \; \phi \times 2 \times 0.85 f’_{c} A_{1} \right) \quad \text{(Eq. 16)} [math]
A1 = Loaded area (the column area)
A2 = Base of the frustum with 1 vertical a 2 horizontal side slopes under the column, wholly within the footing: its projection beyond the column is limited by the nearest footing edge and by 2 times the footing thickness
The larger ratio of the two columns is listed as Transferencia de carga (0.560 in the example). The report also compares the area of the dowel bars of each column with the minimum of 0.005 times the column area (Sección de 16.3.4.1).
Longitud de desarrollo
El Longitud de desarrollo check covers the column dowel bars and the flexural bars of the footing:
- Column dowel bars: the compression development length (Sección de 25.4.9), plus the bend of the dowel, must fit in the footing thickness.
- Flexural bars: at each column face, the force in the bars must be developed on each side of the section (Sección de 13.2.8.2). The tension development length of straight bars (Sección de 25.4.2) or hooked bars (Sección de 25.4.3, depending on the bar ends chosen in the Reinforcement tab) is compared with the anchorage length available from the column face to the end of the bar.
The checks can be turned on or off in the design settings (Perform dowel bars check, Perform top bars check y Perform bottom bars check). In the example, the Development Length ratio of 1.231 comes from the bottom bars along x at the outer face of Column 1: solo 175 mm is available (la 250 mm X-edge Distance minus the 75 mm cover), while the hooked bars need 215.35 mm. Increasing the X-edge Distance of the columns gives the bars the anchorage they need. The development length checks are explained in more detail in the ACI 318 (2019) Guía de comprobación de la longitud de desarrollo, written for isolated footings.
Detallando
El Detallando check verifies that the footing thickness can hold the hooked ends of the top and bottom bars (90° or 180° hooks), with their bend and extension and the top and bottom covers.
Desarrollador de productos
licenciatura (Civil), maestría (Civil)
Referencias
- Requisitos del Código de Construcción para Hormigón Estructural (ACI 318-19) y comentario (ACI 318R-19). Instituto Americano del Concreto, 2019.
- Comité ACI 421. Guía de refuerzo de corte para losas (ACI 421.1R-20). Instituto Americano del Concreto, 2020.