SkyCiv Load Generator calculates NBCC 2015 seismic loads for buildings with the Equivalent Static Force Procedure of the National Building Code of Canada 2015. It gets the seismic hazard values for your site in Canada, then gives you the design spectral acceleration, the specified lateral earthquake force (base shear), the vertical distribution of seismic forces and the overturning moments. This page explains each input of the seismic workflow and how the calculation uses it.
Free accounts can try the workflow for up to 3 calcoli a settimana. With a Professional Account or the modulo Load Generator autonomo, you get unlimited solves, the full seismic results and the detailed seismic calculation report.
Workflow Overview
The NBCC 2015 seismic workflow follows the same top-to-bottom order as the rest of the SkyCiv Load Generator:
- Selezionare NBCC 2015 as the design code.
- Nel Dati del sito, seleziona il Categoria di importanza e, sotto For Seismic Load, il Classe del sito, then enter an address in Canada.
- Review the Seismic Hazard Values returned for the site.
- Nel Dati della struttura, seleziona il Costruzione structure and enter its dimensions.
- fai clic sulla scheda e ti verrà presentata una nuova barra multifunzione di strumenti come mostrato di seguito Carico sismico, define the seismic parameters and the floor weights, and confirm them.
- Fai clic su Calcola i carichi and review the results.
Per NBCC 2015, the seismic calculation is available for the Costruzione structure only. NBCC 2015 seismic calculations are done in metric units (m, kN). If you design to the newer edition, vedere NBCC 2020 Calcoli del carico sismico.
Dati del sito: NBCC 2015 Seismic Hazard Values
Categoria di importanza
Il Categoria di importanza (Basso, Normale, Alto o post-disastro) is selected in Site Data and is shared with the wind and snow calculations. For the seismic calculation, it sets the earthquake importance factor \(I_{E}\) of Table 4.1.8.5, used at the ultimate limit state:
| Categoria di importanza | \(I_{E}\) |
|---|---|
| Basso | 0.8 |
| Normale | 1.0 |
| Alto | 1.3 |
| Post Disaster | 1.5 |
Classe del sito
fai clic sulla scheda e ti verrà presentata una nuova barra multifunzione di strumenti come mostrato di seguito For Seismic Load in Site Data and select the Classe del sito (Table 4.1.8.4-A of NBCC 2015):
- A – Hard rock
- B – Rock
- C – Very dense soil and soft rock
- D – Stiff soil
- E – Soft soil
Site Class F (soils that need a site-specific evaluation) is not available. Selecting a Site Class looks up the seismic data for the address you entered and enables the Carico sismico button for buildings. NBCC 2015 seismic hazard values are given for a 2% probability of exceedance in 50 anni (2475-year return period), so there is no probability to select.
Seismic Hazard Values
Once the location and Site Class are set, the Load Generator fills in the Seismic Hazard Values for the site:
| Ingresso | Cos'è |
|---|---|
| \(S_{a}(0.2)\), \(S_{a}(0.5)\), \(S_{a}(1.0)\), \(S_{a}(2.0)\), \(S_{a}(5.0)\), \(S_{a}(10.0)\) | 5% damped spectral response acceleration at periods of 0.2, 0.5, 1.0, 2.0, 5.0 e 10.0 S, in g |
| PGA | Peak ground acceleration, in g |
| PGV | Peak ground velocity, in m/s |
All eight values are required. You can edit them, for example to use the values of the NBCC 2015 seismic hazard calculator for your site. The map pop-up also shows the values and the source they come from.
How the Site Data Is Used
The calculation turns the site hazard into the design spectral acceleration \(S(T)\) of Article 4.1.8.4:
- It sets the reference peak ground acceleration: \(PGA_{ref} = 0.8\,PGA\) quando \(S_{a}(0.2)/PGA < 2.0\), e \(PGA_{ref} = PGA\) altrimenti.
- It reads the site coefficients \(F(T)\), \(F(PGA)\) e \(F(PGV)\) for the selected Site Class and \(PGA_{ref}\) from Tables 4.1.8.4-B to 4.1.8.4-I, interpolating between table values.
- Calcola \(S(T)\) at each period from \(F(T)\) e \(S_{a}(T)\), as in Article 4.1.8.4(9).
Dati della struttura
Selezionare Costruzione in Structure Data and enter its dimensions. The height from the ground to the top of the roof is used as the structure height \(h_{n}\) in the approximate fundamental period.

Figura 1. Structure Data for a building.
NBCC 2015 Parametri di carico sismico
Clicca il Carico sismico button to define the seismic parameters. When you confirm them with Confirm Seismic Parameters, the checkbox beside the button is ticked and the seismic load is included in the calculation:

Figura 2. Seismic Load button and checkbox.
The seismic parameters for NBCC 2015 sono:
| Ingresso | La resistenza alla compressione sarà considerata come da AS4600 | How it is used |
|---|---|---|
| Structure System | Concrete Moment-Resisting Frame | Sets the formula for the approximate period \(T_{a}\) and the type of system used for the higher mode factor \(M_{v}\) and the overturning moment reduction factor \(J\) (Tabella 4.1.8.11). It also selects the minimum base shear: a \(T = 4.0\,\text{s}\) for coupled walls and wall/wall-frame systems, a \(T = 2.0\,\text{s}\) for the others. |
| \(T_{a}\) (o \(T_{s}\)) | Filled in from the Structure System | Fundamental lateral period of vibration of the building (Article 4.1.8.1(7)), in secondi. Must be between 0 e 10. |
| \(R_{d}\) | 4.0 | Ductility-related force modification factor (Tabella 4.1.8.9). Must be between 0 e 10. |
| \(R_{o}\) | 1.0 | Overstrength-related force modification factor (Tabella 4.1.8.9). Must be between 0 e 10. |
| Pesi da pavimento | Nessuno | Livello, Elevation and Weight of each floor, used for the seismic weight \(W\), the vertical distribution of the base shear and the overturning moments. |

Figura 3. Seismic Load parameters (shared by NBCC 2015 e NBCC 2020).
Structure System and Approximate Period
When you select a Structure System, the Load Generator fills in \(T_{a}\) from the ground to top of roof height \(h_{n}\) (in m):
| Structure System | Approximate period |
|---|---|
| Steel Moment-Resisting Frame | \(T_{a} = 0.085\,h_{n}^{0.75}\) |
| Concrete Moment-Resisting Frame | \(T_{a} = 0.075\,h_{n}^{0.75}\) |
| Moment-Resisting Frame (Altri) | \(T_{a} = 0.1N\) |
| Braced Frame | \(T_{a} = 0.025\,h_{n}\) |
| Coupled Wall | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
| Wall/Wall-Frame | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
| All other structural systems | \(T_{a} = 0.05\,h_{n}^{0.75}\) |
Per Moment-Resisting Frame (Altri), \(T_{a}\) is not filled in: enter it yourself, con \(N\) the number of storeys above ground level. If the field is left empty, the calculation uses the number of rows in the Floor Weights table as \(N\). You can replace \(T_{a}\) with a period from a dynamic analysis within the limits of Article 4.1.8.11(3): it changes \(S(T_{a})\) and the base shear.
Pesi da pavimento
Fai clic su Add Floor Weights Data to add a row per level, e Chiari to empty the table. Each row needs a Level name, an Elevation above the base and a Weight, both greater than 0. The sum of the weights is the seismic weight \(W\) della costruzione (Article 4.1.4.1). At least one row is required to calculate.
Equivalent Static Force Procedure
The Load Generator calculates the specified lateral earthquake force \(V\) with the Equivalent Static Force Procedure of Article 4.1.8.11:
[math] V = \frac{S(T_{a})\,M_{v}\,I_{E}\,W}{R_{d}\,R_{o}} [math]
\(V\) is taken not less than the minimum base shear:
[math] V_{min} = \frac{S(2.0)\,M_{v}\,I_{E}\,W}{R_{d}\,R_{o}} [math]
for moment-resisting frames, braced frames and other systems (con \(S(4.0)\) e \(M_{v}\) a 4.0 s for walls, coupled walls and wall-frame systems). For an \(R_{d}\) di 1.5 o più, \(V\) need not be more than:
[math] V_{max} = \max\left(\frac{2}{3}\,\frac{S(0.2)\,I_{E}\,W}{R_{d}\,R_{o}},\ \frac{S(0.5)\,I_{E}\,W}{R_{d}\,R_{o}}\right) [math]
\(S(T_{a})\) is interpolated from the design spectrum, e \(M_{v}\) e \(J\) come from Table 4.1.8.11 with the ratio \(S(0.2)/S(5.0)\), \(T_{a}\) and the Structure System. The base shear is then distributed over the height of the building (Article 4.1.8.11(7)):
[math] F_{x} = \frac{(V – F_{t})\,W_{x}h_{x}}{\sum W_{i}h_{i}} [math]
dove \(F_{t} = 0.07\,T_{a}V \le 0.25V\) is a concentrated force added at the top level, e \(F_{t} = 0\) quando \(T_{a} < 0.7\,\text{s}\). The overturning moment at each level, \(M_{x}\), is reduced by the factor \(J_{x}\) of Article 4.1.8.11(8).
Risultati
Fai clic su Calcola i carichi in the menu bar to run the calculation. The results show:
- The summary of the seismic parameters, compresi \(I_{E}\), \(T_{a}\), \(M_{v}\), \(J\) and the base shear \(V\).
- The vertical distribution of seismic forces, \(F_{x}\) per livello.
- The overturning moments, \(M_{x}\) per livello.
- The design spectral acceleration \(S(T)\) table and chart, con \(S(T_{a})\) marked.
Free users see the seismic parameters only. Le forze, overturning moments and design spectral acceleration are shown to Professional account users and to users of the standalone Load Generator module. Fai clic su Scarica Rapporto beside Calcola i carichi for a summary report of the inputs and results.
Detailed Seismic Calculation Report
Il Detailed Seismic Calculation Report button in the results opens a step-by-step NBCC 2015 calcolo, available to Professional account users and to users of the modulo Load Generator autonomo. It shows every parameter, formula and code reference used: the site seismic parameters, il \(F(T)\) e \(S(T)\) tabella, \(M_{v}\) e \(J\), the base shear checks, the vertical distribution of forces with a diagram, the overturning moments and the design spectral acceleration chart. It is ready to attach to your design calculations.
Riferimenti
- Commissione canadese sui codici edilizi e antincendio. (2015). Carico ed effetti del terremoto. Nel National Building Code of Canada 2015 (Vol. 1, Divisione B, Parte 4, Sottosezione 4.1.8). Consiglio nazionale delle ricerche del Canada.