This page walks through the isolated footing design checks that SkyCiv Foundation performs to ACI 318-19: Bodentragend, einachsige Querkraft, punching shear and flexure, with the equations used, plus the stability checks (Abheben, overturning and sliding). Flexure is described with the default Strip average method, und das Peak wood-armer method is summarized for comparison.
Das Fundament ist ein wesentliches Bausystem, das Stützen- und Wandkräfte auf den tragenden Boden überträgt. Abhängig von den Bodeneigenschaften und den Gebäudelasten kann sich der Ingenieur für ein flaches oder tiefes Fundamentsystem entscheiden. SkyCiv Foundation designs isolated footings (Einzelfundamente) to the American code ACI 318-19. To use it, wählen Sie American Concrete Institute as the Design Code and ACI 318 (2019) as the Version when you start a new file, then pick Einzelfundament.

The example shown on this page is the default pad footing (1500 × 1500 × 500 mm footing, 300 × 300 mm column, #5 bars at 150 mm each way) with a dead load of 400 kN and a live load of 250 kN on the column.
Design Settings for ACI 318-19
The methods used for the checks are set in Edit Design Settings (Details tab). For ACI 318-19, der Moment Demand Calculation offers the Strip average method (Ursprünglich) und das Peak wood-armer method. The settings also hold the Perform One-Way Shear Check toggle and the Punching Shear Edge Factor (0.5 standardmäßig).

Eine Schritt-für-Schritt-Anleitung zur Bemessung eines Einzelfundaments
Abmessungsanforderungen
Zur Bestimmung der Abmessungen eines isolierten Fundaments, Service oder nicht faktorisierte Lasten, wie Dead (D.), Verkehrslast (L.), Wind (W.), Seismisch (E.), etc. are combined using the load combinations of ACI 318-19 (Tabelle 5.3.1). Whichever load combination governs is considered the design load, und wird mit dem zulässigen Bodendruck verglichen, wie in Gleichung . gezeigt 1, as required by Querschnitt 13.3.1.1 von ACI 318-19.
[math] q_{a} = \frac{P_{n}}{A} \quad \text{(Eq. 1)} [math]
qein = Zulässiger Bodendruck
P.n = Unberücksichtigte Auslegungslast
A = Fundamentfläche
Die Fundamentabmessungen können zunächst durch Lösen der Fundamentfläche abgeschätzt werden (Ein) unter Verwendung von Gleichung 1.
[math] A = \frac{P_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
In SkyCiv Foundation, the footing dimensions are inputs (Geometry tab). The software checks them with the soil pressures from the finite element analysis, as described in Bodendruck.
Querkraft in einer Richtung
Der Grenzzustand der Einwegscherung, auch als Balkenscherung bekannt, recognizes that the footing may fail in shear similar to a wide beam along a critical section located at a distance “d” von der Vorderseite der Säule (Abbildung 1). SkyCiv Foundation checks it in both directions (along x and along z). It can be turned off with Perform One-Way Shear Check in the design settings (standardmäßig aktiviert).

Abbildung 1. One-way shear diagram (Ergebnisse, Diagrams button)
Das One-way Shear Demand oder \( V_{u} \) is taken from the strip shear diagram of the footing: the shear forces of the finite element analysis are summed across the full width of the footing, along a strip through the column, and read at the two critical sections. The larger absolute value of the ultimate load combinations is used, in jede Richtung.
Das Einweg-Scherkapazität oder \( \phi V_{c} \) is calculated with Equation 2 (Tabelle 22.5.5.1(c), for members without shear reinforcement), with the full width of the footing perpendicular to the direction checked. The size effect factor \( \lambda_{s} \) is neglected for footings, as permitted by Querschnitt 13.2.6.2.
[math] \phi V_{c} = \phi_{\text{shear}} \times 8 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 2, Table 22.5.5.1(c), Imperial)} [math]
oder
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.66 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 2, Table 22.5.5.1(c), Metric)} [math]
[math] \rho_{w} = \frac{n \times A_{b}}{b_{w} \times d} [math]
φSchub- = Shear strength reduction factor, 0.75 (Tabelle 21.2.1)
λ = Modification factor for lightweight concrete
rw = Ratio of the bottom bars in the direction checked
n, Einb = Number and area of these bars
f’c = Angegebene Betonfestigkeit, (psi, MPa)
bw = Width of the footing perpendicular to the direction checked, (im, mm)
d = Effective depth of the bottom bars in the direction checked, (im, mm)
Scherbedarf und Scherkapazität müssen die folgende Gleichung erfüllen, um die Konstruktionsanforderungen von ACI . zu erfüllen 318-19:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 3, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, in Übereinstimmung mit der Gleichung 3, berechnet das Einweg-Schernutzenverhältnis (Gleichung 4) indem man den Scherbedarf über die Scherkapazität nimmt. The larger ratio of the two directions is listed as Einwegschere in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 4)} [math]
Durchstanzen (Stanzschere)
The two-way shear limit state, auch als Durchstanzschere bekannt, has its critical section at a distance “d/2” from the faces of the column, around the perimeter of the column (Abbildung 2). Its length is the critical perimeter \( b_{o} \).

Abbildung 2. Critical perimeter of two-way shear (Ergebnisse, Diagrams button)
When a column face is closer to a footing edge than the Punching Shear Edge Factor mal d (design settings, 0.5 standardmäßig), the perimeter on that side extends to the footing edge and is not counted in \( b_{o} \). The column is then classified as an interior, edge or corner column, which sets \( \alpha_{s} \) = 40, 30 oder 20 (Querschnitt 22.6.5.3). If the column is close to two opposite edges, the punching shear check is skipped, as one-way shear governs.
Das Two-way Shear Demand is calculated at the critical perimeter with the mesh-based method, from the finite element analysis of the footing. The upward force from the soil pressure inside the critical perimeter, \( F_{q} \), is the sum of the forces of the mesh elements in that area, and it is subtracted from the factored column load. The maximum shear stress \( v_{u} \) on the critical perimeter also includes the unbalanced moments transferred by eccentric shear (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 5)} [math]
P.u = Factored column load
γ v = Fraction of the unbalanced moment transferred by eccentric shear
M.u = Unbalanced moment: column moment, plus column shear times the column height and footing thickness, minus the column load times the offset of the centroid of the critical section (edge and corner columns)
c, J.c = Distance to the point considered and polar moment of inertia of the critical section
d = effektive Tiefe, the average of the effective depths of the bottom bars in both directions
Das Scherkapazität is the punching shear stress \( \phi v_{c} \), governed by the smallest value of Equations 6, 7 und 8 pro Querschnitt 22.6.5.2. Unlike ACI 318-14, der 2019 edition includes the size effect factor \( \lambda_{s} \) (Querschnitt 22.5.5.1.3), which reduces the capacity of footings with an effective depth over 10 im (250 mm).
[math] \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + d/10}} \right) \quad \text{(Imperial)} \qquad \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + 0.004\,d}} \right) \quad \text{(Metric)} [math]
[math] v_{c} = 4 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 6, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c} = \left( 2 + \frac{4}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 7, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(c), Imperial)} [math]
oder
[math] v_{c} = 0.33 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 6, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c} = \left( 0.17 + \frac{0.33}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 7, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c} = \left( 0.17 + \frac{0.083 \times \alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
Hinweis: β ist das Verhältnis der langen Seite zur kurzen Seite der Säule (1.0 for a round column, which is treated as an equivalent square), und \( \alpha_{s} \) is given by Section 22.6.5.3. φSchub- = 0.75 (Tabelle 21.2.1).
λs = Size effect modification factor
λ = Modifikationsfaktor, um die verringerten mechanischen Eigenschaften von Leichtbeton im Vergleich zu Normalbeton gleicher Druckfestigkeit widerzuspiegeln
f’c = Angegebene Betondruckfestigkeit (psi, MPa)
d = effektive Tiefe, the average of the effective depths of the bottom bars in both directions, (im, mm)
bDas = Critical perimeter (im, mm)
Scherbedarf und Scherkapazität müssen die folgende Gleichung erfüllen, um die Konstruktionsanforderungen von ACI . zu erfüllen 318-19:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 9, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, in Übereinstimmung mit der Gleichung 9, berechnet das Zwei-Wege-Schernutzenverhältnis (Gleichung 10) indem man den Scherbedarf über die Scherkapazität nimmt, both as stresses. The result is listed as Stanzschere in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 10)} [math]
Biegung
Moment Demand with the Strip Average Method
Das Biegebedarf oder \( M_{u} \) comes from the finite element analysis of the footing. Mit dem Strip average method (der Standard Moment Demand Calculation), the footing is treated like a wide beam in each direction: the Wood-Armer moments of the plate elements are summed across the full width of the footing, along a strip through the column, which gives the total moment carried by the whole width at each section (Abbildung 3). This is done for the top and bottom layers, along x and along z, under the ultimate load combinations.
- Bottom layer: \( M_{u} \) is the strip moment at the column faces, the larger of the two faces.
- Top layer: \( M_{u} \) is the largest hogging (negativ) strip moment along the strip.

Abbildung 3. Strip average moment diagram, bottom layer along X (Ergebnisse, Diagrams button)
The detailed report shows the same diagram for each layer and direction, with a table of the maximum moment, its coordinates and the governing load combination, followed by the utility ratio (Abbildung 4).

Abbildung 4. Moment demand and utility ratio in the design report (Detaillierter Bericht anzeigen)
Peak Wood-Armer Method
Mit dem Peak wood-armer method, \( M_{u} \) is instead the maximum Wood-Armer moment per unit width found anywhere over the footing, for the top and bottom layers in both directions, and the capacity is calculated per unit width (12 in or 1000 mm). Because it uses the peak moment, usually at the column, rather than the moment spread over the full width, it gives a more conservative design. It is described in the Schritt-für-Schritt-Bemessung eines Einzelfundaments nach ACI 318-14, where it is the only method available.
Biegekapazität
With the strip average method, der Biegekapazität oder \( \phi M_{n} \) is calculated for the full width of the footing, with all the bars of the layer across that width, unter Verwendung von Gleichung 11.
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 11)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
φBiegung = flexural strength reduction factor (Tabelle 21.2.2)
Eins = area of the bars of the layer across the width of the footing (im2, mm2)
fj = reinforcement strength, (psi, MPa)
d = Abstand von der Extremdruckfaser zum Schwerpunkt der Längszugbewehrung (im, mm)
a = Tiefe des äquivalenten rechteckigen Spannungsblocks (im, mm)
b = width of the footing perpendicular to the bars (im, mm)
The strength reduction factor depends on the net tensile strain \( \varepsilon_{t} \), found from the neutral axis depth \( c = a/\beta_{1} \) (b1 aus der Tabelle 22.2.2.4.3) and a concrete strain of 0.003. ACI 318-19 compares it with the yield strain of the reinforcement \( \varepsilon_{ty} = f_{y}/E_{s} \):
[math] \phi_{\text{flexure}} = 0.65 + 0.25 \times \frac{\varepsilon_{t} – \varepsilon_{ty}}{0.003} \quad \text{(Table 21.2.2)} [math]
with ϕ = 0.90 Wann \( \varepsilon_{t} \geq \varepsilon_{ty} + 0.003 \) (tension-controlled) and ϕ = 0.65 Wann \( \varepsilon_{t} \leq \varepsilon_{ty} \) (compression-controlled). The report shows a warning when the section is not tension-controlled. When top bars are provided and the tension steel ratio exceeds the balanced ratio, the section is checked as doubly reinforced.
The provided reinforcement is also compared to the minimum area of 0.0018 EinG (Querschnitt 8.6.1.1), in each direction and for each layer. Without top bars, the top face is checked as plain concrete (Querschnitt 14.5.2.1):
[math] \phi M_{n} = \phi \times 5 \lambda \sqrt{f’_{c}} \times S \quad \text{(Imperial)} \qquad \phi M_{n} = \phi \times 0.42 \lambda \sqrt{f’_{c}} \times S \quad \text{(Metric)} [math]
ϕ = 0.60 for plain concrete
S = section modulus of the full width of the footing (b × h2/6)
Momentenbedarf und Momentenkapazität müssen die folgende Gleichung erfüllen, um die Konstruktionsanforderungen von ACI . zu erfüllen 318-19:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 12, Section 7.5.1.1(a))} [math]
SkyCiv Foundation, in Übereinstimmung mit der Gleichung 12, berechnet das Biegenutzenverhältnis (Gleichung 13) indem die Biegenachfrage der Biegekapazität gegenübergestellt wird. The Flexure ratio in the Design Checks Summary is the largest of the top, bottom and minimum reinforcement ratios. In the example, the bottom layer along X has a ratio of 121.5/203.01 = 0.598, and the Flexure ratio of 0.671 comes from the minimum reinforcement check.
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 13)} [math]
Zusätzliche Nachweise
Andere Überprüfungen, die im Code nicht erwähnt werden, einschließlich Bodendruckprüfungen, Abheben, und andere Stabilitätsprüfungen werden ebenfalls überprüft. The Design Checks Summary also lists Lastübertragung (bearing at the column base), Entwicklungslänge und Konstruktive Durchbildung. The development length checks are explained in the ACI 318 (2019) Leitfaden zum Nachweis der Verankerungslänge.
Bodendruck
Die Bestimmung des Sockeldrucks bzw. der Wechselwirkung zwischen Boden und Fundament beruht in erster Linie auf den Abmessungen des Fundaments und der daraus resultierenden Exzentrizität der aufgebrachten Lasten. Je nach Positionierung ergibt sich daraus eine Exzentrizität, Der Grunddruck kann zu einer vollständigen oder teilweisen Kompression des Fundaments führen. Mit dieser Bewertung können wir bestätigen, ob der darunter liegende Boden die gesamten vom Fundament übertragenen Lasten tragen kann. SkyCiv Foundation takes the soil pressures from the finite element analysis of the footing.

Eine ausführliche Anleitung zur manuellen Berechnung des Bodendrucks finden Sie hier, Bitte beachten Sie diesen Link: Druckverteilung unter einem rechteckigen Betonfundament
Das Nutzenverhältnis wird durch Vergleich des maximalen Bodendrucks ermittelt (Zustand der Gebrauchstauglichkeit) mit dem Bruttozulässige Bodentragfähigkeit entered in the Soil tab. It is listed as Bodenlager in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Max. Soil Pressure}}{\text{Gross Allowable Soil Bearing Capacity}} \quad \text{(Eq. 14)} [math]
Abheben
Überprüft die maßgebende Axiallast, die auf das Fundament wirkt, considering axial loads only. Summiert alle vertikalen Lasten einschließlich der Benutzerlast und des Eigengewichts der Säule, Bodenplatte, Bodenlast, und Auftriebskraft. Wenn die Säule eine nach oben gerichtete Kraft erfährt, Die angegebenen Eigengewichte müssen die Auftriebskraft ausgleichen; Andernfalls, Bei der Konstruktion besteht die Gefahr, dass sie aufgrund von Instabilität versagt. When no service load combination produces uplift, the check is not needed.
Kippen
Overturning of the footing is checked by summing up all moments about the toe and the heel of the footing in each direction, including all the forces acting on it. All service load combinations are considered to find the governing overturning moment. The factor of safety (stabilising moment over overturning moment) is compared with the Kippen factor of safety in the Designfaktoren Tab (2.0 standardmäßig). If the applied loads produce no overturning moment, the check is not needed.
Gleiten
To check for sliding in each direction, the sum of the horizontal resisting forces is divided by the horizontal force applied to the footing, taken from the governing service load combination.
- Resisting forces:
- Friction between the footing base and the soil (coefficient of friction times the axial force on the base; none under net uplift)
- Passiver Bodendruck
- Cohesion of the soil
- Gleitkraft:
- The horizontal (Schub-) load applied to the column
The resulting factor of safety is compared with the Gleiten factor of safety in the Designfaktoren Tab (1.5 standardmäßig). Wenn keine horizontale Kraft auf den Untergrund einwirkt, Eine Prüfung auf Gleiten ist nicht erforderlich.
SkyCiv Foundation Design-Modul
Das Foundation Design Module von SkyCiv ist in die Finite-Elemente-Analyse integriert (HÄSSLICH), delivering more accurate soil pressure analysis and Wood-Armer moments for the flexural design checks.
Shear and moment diagrams are generated directly from the FEA results using the strip average method, Bereitstellung eines klareren Bildes der internen Kräfte im gesamten Fundament. Open them with the Diagrams button of the Results tab, and pick the Fall, der Diagram (Querkraft in einer Richtung, Punching Shear or Moment), der Lastkombination, der Schicht und das Richtung.
Das Modul unterstützt erweiterte Fundamentkonfigurationen, einschließlich Stützenversätzen in jeder Richtung für isolierte und kombinierte Fundamente. Lasten und Momente können auch in jede beliebige Richtung eingeleitet werden, Dies ermöglicht eine genaue Modellierung realer Fundamentbedingungen.
Kein SkyCiv-Benutzer? Melden Sie sich für a . an kostenloses 14 Tagesversuch um loszulegen!
Produktentwickler
BSc (Bauingenieurwesen), MSc (Bauingenieurwesen)
Quellen
- Bauvorschriften für Tragwerksbeton (ACI 318-19) und Kommentar (ACI 318R-19). American Concrete Institute, 2019.
- ACI Committee 421. Guide to Shear Reinforcement for Slabs (ACI 421.1R-20). American Concrete Institute, 2020.