This page explains how SkyCiv Foundation designs a combined footing to ACI 318-19: toprak yatağı, tek yönlü kesme, punching shear and flexure, with the equations used and the results shown in the software and the calculation report, followed by the other design checks (yükselme, devirme, sürgülü, yük aktarımı, development length and detailing). Flexure is described with the default Strip average method, ve Peak wood-armer method is summarized for comparison.
Bir birleşik temel is a single footing supporting two columns. It is commonly used when the columns are too close to each other, or a column is too close to a property line, for two separate isolated footings. SkyCiv Foundation meshes the footing into plate elements supported on the soil (modeled with the subgrade modulus) and analyzes it with finite element analysis (ÇİRKİN). The soil pressures, shears and moments used in the design checks below come from these FEA results. To design to the 2019 baskı, seçin Amerikan Beton Enstitüsü as the Design Code and ACI 318 (2019) as the Version when you start a new file, then pick Kombine Temel. The same checks to the 2014 edition are described in ACI'ye Uygun Birleşik Temel Tasarımı 318-14.

The example shown on this page is a 3000 × 1500 × 500 mm combined footing with two 300 × 300 mm columns placed 250 mm from the ends of the footing (X-edge Distance), #5 bars at 200 mm in both directions at the top and bottom, ve bir 75 mm cover. Sütun 1 carries a dead load of 200 kN and a live load of 100 kN, ve Sütun 2 a dead load of 250 kN and a live load of 120 kN. The x-direction is the direction joining the two columns.
Design Settings for ACI 318-19
The methods used for the checks are set in Edit Design Settings (Details tab). ACI için 318-19, NS Moment Demand Calculation offers the Strip average method (varsayılan) ve Peak wood-armer method. The settings also hold the Perform One-Way Shear Check toggle and the Punching Shear Edge Factor (0.5 varsayılan olarak), as well as the switches of the load transfer and development length checks.

Combined Footing Design Checks to ACI 318-19
Dimension Requirements and Soil Bearing
To size a combined footing, hizmet (Yayılmış Temel Tasarım İş Akışı Süreci) loads such as Dead (D), Canlı (L), Rüzgar (W) and Seismic (E) are combined with the service load combinations. The governing combination is the design load, and the base area is proportioned so that the allowable soil pressure is not exceeded (ACI 318-19, Kesit 13.3.1.1):
[math] q_{a} = \frac{P1_{n} + P2_{n}}{A} \quad \text{(Eq. 1)} [math]
qa = İzin verilen toprak basıncı
kilo kaybı hikayeleri.netn, kilo kaybı hikayeleri.netn = Unfactored loads at Column 1 (ayrıldı) ve Sütun 2 (sağ)
A = Temel alanı
Solving Equation 1 for the area gives a first estimate of the footing dimensions:
[math] A = \frac{P1_{n} + P2_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
SkyCiv Foundation does not size the footing from Equation 1a: the dimensions are inputs (Geometry tab), and the software checks them. bu Yayılmış Temel Tasarım İş Akışı Süreci ratio is the maximum soil pressure from the FEA results of the service load combinations (zarf), which includes the effect of the column moments and of the eccentricity of the loads, divided by the allowable soil bearing capacity entered in the Soil tab:
[math] \text{Utility Ratio} = \frac{q_{sls,max}}{q_{a}} \quad \text{(Eq. 2)} [math]
In the example, the maximum service soil pressure is 224.1 kPa, under Column 2, which carries the larger load, and the Soil Bearing ratio is 0.448. The soil pressure contour and the ratio of every check are shown in the Sonuçlar sekme:

Tek Yönlü Kesme
Tek yönlü kayma sınırı durumu, kiriş kesme olarak da bilinir, treats the footing like a wide beam that may fail in shear along a critical section located at a distance "d" bir sütunun yüzünden. It is checked when Perform One-Way Shear Check is enabled in the design settings (varsayılan olarak açık).
bu One-way Shear Demand veya \( V_{u} \) is taken from the strip average shear diagrams of the FEA (ultimate load combinations): the shear forces of the plate elements are summed across the width of the footing, and the diagram is read at the critical sections, located at the effective depth of the bottom bars in that direction from each column face (or at the edge of the footing when that distance falls outside it). The largest absolute shear at these sections is the demand.
- Along x (the direction joining the columns), one diagram covers the whole footing, with the critical sections on both sides of both columns.
- Along z, each column has its own diagram, through that column.
The diagrams can be viewed in the Sonuçlar tab by opening Diagrams and choosing Tek Yönlü Kesme içinde Diagram liste. In the example, the critical sections along x are 417 mm (the effective depth of the bottom x-bars) from the inner faces of the columns, and the demand is 158.70 kN, next to Column 2:

Figür 1. Critical sections and shear diagram of one-way shear along x (Sonuçlar, Diagrams button)
bu Tek Yönlü Kesme Kapasitesi veya \( \phi V_{c} \) is calculated with Equation 3 (Tablo 22.5.5.1(c), for members without shear reinforcement). The size effect factor \( \lambda_{s} \) is neglected for footings, as permitted by Kesit 13.2.6.2.
[math] \phi V_{c} = \phi_{\text{shear}} \times 8 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Imperial)} [math]
veya
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.66 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Metric)} [math]
[math] \rho_{w} = \frac{n \times A_{b}}{L \times d} [math]
ϕkesme = Shear strength reduction factor, 0.75 (Tablo 21.2.1)
λ = Modification factor for lightweight concrete
rw = Ratio of the bottom bars in the direction checked
n, Birb = Number and area of these bars, across the footing dimension L perpendicular to them
f’c = Belirtilen beton dayanımı (psi, MPa)
bw = Width resisting the shear (içinde, mm)
d = Effective depth of the bottom bars in the direction checked (içinde, mm)
Along x, \( b_{w} \) is the full width of the footing (its dimension along z). Along z, the footing is divided into two design strips at the midpoint between the two column centres, and each column’s shear is checked against the capacity of its own strip, ile \( b_{w} \) equal to the strip width. In the example, both strips are 1500 mm genişliğinde.
The calculation report shows the shear diagram of each direction, followed by the demand, the capacity and the ratio. Along x, \( \phi V_{c} \) = 192.9 kN and the ratio is 158.7/192.9 = 0.823:

Kesme Talebi ve Kesme Kapasitesi, ACI tasarım gereksinimlerini karşılamak için aşağıdaki denklemi karşılamalıdır 318-19:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 4, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, Denklem ile uyumlu 4, calculates the one-way shear utility ratio by taking Shear Demand over Shear Capacity, along x and for each column along z. The largest ratio is listed as Tek Yönlü Kesme in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 5)} [math]
İki Yönlü Kesme (Delme Makası)
The two-way shear limit state, delme makası olarak da bilinir, has its critical section at a distance "d/2" from the faces of the column, around the perimeter of the column (Kesit 22.6.4.1). Its length is the critical perimeter \( b_{o} \). The check is done for each column. The critical perimeters can be viewed in the Sonuçlar tab by opening Diagrams and choosing Delme Makası içinde Diagram liste:

Figür 2. Critical perimeters of two-way shear (Sonuçlar, Diagrams button)
The effective depth d is the average of the effective depths of the bottom bars in both directions (409 mm in the example). When a column face is closer to a footing edge than the Punching Shear Edge Factor kere d, the perimeter on that side extends to the footing edge and is not counted in \( b_{o} \). The column is then classified as an interior, edge or corner column, which sets \( \alpha_{s} \) = 40, 30 veya 20 (Kesit 22.6.5.3). If the column is close to two opposite edges, the punching shear check is skipped for that column, as one-way shear governs. A round column is taken as an equivalent square column with sides equal to its diameter. In the example, both columns are interior columns, ile \( b_{o} \) = 4 × 709 = 2836 mm.
bu Two-way Shear Demand is calculated at the critical perimeter with the mesh-based method, from the finite element analysis of the footing. The upward force from the soil pressure inside the critical perimeter, \( F_{q} \), is the sum of the forces of the mesh elements in that area (the average pressure on each element times its area inside the perimeter, listed in a table of the report), and it is subtracted from the factored column load. The maximum shear stress \( v_{u} \) on the critical perimeter also includes the unbalanced moments transferred by eccentric shear (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 6)} [math]
[math] \gamma_{v} = 1 – \frac{1}{1 + \frac{2}{3}\sqrt{b_{1}/b_{2}}} \quad \text{(Eq. 7)} [math]
Psen = Factored column load
Fq = Resultant of the factored soil pressure inside the critical perimeter, summed over the FEA mesh elements
cv = Fraction of the unbalanced moment transferred by eccentric shear
Msen = Unbalanced moment: column moment, plus column shear times the column height and footing thickness, minus the column load times the offset of the centroid of the critical section (edge and corner columns)
b1, b2 = Dimensions of the critical section perpendicular and parallel to the direction considered
c, Jc = Distance to the point considered and polar moment of inertia of the critical section
For edge and corner columns, \( \gamma_{v} \) and the stresses are calculated following ACI 421.1R-20. The maximum stress around the critical section is taken as the demand.
bu Kesme Kapasitesi is the punching shear stress \( \phi v_{c} \), governed by the smallest value of Equations 8, 9 ve 10 başına Kesit 22.6.5.2. Unlike ACI 318-14, NS 2019 edition includes the size effect factor \( \lambda_{s} \) (Kesit 22.5.5.1.3), which reduces the capacity of footings with an effective depth over 10 içinde (250 mm). In the example, \( \lambda_{s} \) = 0.871 for d = 409 mm.
[math] \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + d/10}} \right) \quad \text{(Imperial)} \qquad \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + 0.004\,d}} \right) \quad \text{(Metric)} [math]
[math] v_{c,a} = 4 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c,b} = \left( 2 + \frac{4}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c,c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Imperial)} [math]
veya
[math] v_{c,a} = 0.33 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c,b} = \left( 0.17 + \frac{0.33}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c,c} = \left( 0.17 + \frac{0.083 \times \alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
Not: β sütunun uzun kenarının kısa kenarına oranıdır (1.0 for a round column), ve \( \alpha_{s} \) is given by Section 22.6.5.3. ϕkesme = 0.75 (Tablo 21.2.1).
λs = Size effect modification factor
λ = Modification factor for lightweight concrete
f’c = Belirtilen beton dayanımı (psi, MPa)
d = Etkili derinlik, the average of the effective depths of the bottom bars in both directions (içinde, mm)
bÖ = Critical perimeter (içinde, mm)
The calculation report shows, for each column, the plan of the critical shear area, the soil pressure force \( F_{q} \), the stresses around the perimeter, and the capacity. Sütun için 1 of the example, \( v_{u} \) = 0.261 MPa and \( \phi v_{c} \) = 0.980 MPa:

Kesme Talebi ve Kesme Kapasitesi, ACI tasarım gereksinimlerini karşılamak için aşağıdaki denklemi karşılamalıdır 318-19:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 11, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, Denklem ile uyumlu 11, calculates the two-way shear utility ratio of each column by taking Shear Demand over Shear Capacity, both as stresses. The larger ratio of the two columns is listed as Delme Makası in the Design Checks Summary (0.318 in the example, from Column 2).
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 12)} [math]
Eğilme
SkyCiv Foundation checks the top and bottom reinforcement in both directions against the moments of the whole footing from the FEA, rather than at a single critical section. In a combined footing, the top bars along x resist the hogging moment between the columns, and the bottom bars resist the sagging moments under the columns and in the transverse direction.
Moment Demand with the Strip Average Method
İle Strip average method (varsayılan Moment Demand Calculation), the footing is treated like a wide beam in each direction: the Wood-Armer moments of the plate elements are summed across the width of the footing, which gives the total moment carried by that width at each section. This is done for the top and bottom layers, along x and along z, under the ultimate load combinations (zarf).
- Along x, the strip covers the full width of the footing, and one moment diagram covers both columns.
- Along z, the footing is divided into two design strips at the midpoint between the column centres, and each column has its own diagram.
- Bottom layer: \( M_{u} \) is the largest strip moment at the column faces.
- Top layer: \( M_{u} \) is the largest hogging (olumsuz) strip moment anywhere along the strip.
The moment diagrams can be viewed in the Sonuçlar tab by opening Diagrams, choosing An içinde Diagram liste, and picking the ACI-Doğrulama-Kitaplar-Önizleme ve yön. In the example, the top layer along x has a maximum hogging moment of 154.65 kN-m, near midway between the columns:

Figür 3. Strip average moment diagram, top layer along x (Sonuçlar, Diagrams button)
The calculation report shows the same diagram for each layer and direction, with a table of the maximum moment, its coordinates and the governing load combination, followed by the utility ratio:

Peak Wood-Armer Method
İle Peak wood-armer method, \( M_{u} \) is instead the maximum Wood-Armer moment per unit width found anywhere over the footing, for the top and bottom layers in both directions, and the capacity is calculated per unit width (12 in or 1000 mm). Because it uses the peak moment rather than the moment spread over the width, it is usually more conservative. The Wood-Armer moments can be viewed in the Sonuçlar tab with the Wood Armer buton, by picking the Durum, ACI-Doğrulama-Kitaplar-Önizleme ve yön içinde View Options. In the example, the peak top moment along x is 105.17 kN-m/m, while the strip average moment of 154.65 kN-m over the 1.5 m width of the footing is 103.1 kN-m/m. This method is described in ACI'ye Uygun Birleşik Temel Tasarımı 318-14.

Eğilme Kapasitesi
With the strip average method, NS Eğilme Kapasitesi veya \( \phi M_{n} \) is calculated for the width of the strip, with the bars of the layer across that width (along z, the share of the bars in each strip, in proportion to its width), Denklem kullanarak 13:
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 13)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
ϕeğilme = Flexural strength reduction factor (Tablo 21.2.2)
Birs = Area of the tension bars of the layer across the strip width (içinde2, mm2)
fY = Reinforcement strength (psi, MPa)
d = Distance from the extreme compression fiber to the centroid of the tension reinforcement (içinde, mm)
a = Depth of the equivalent rectangular stress block (içinde, mm)
b = Strip width: the full width of the footing along x, the strip of each column along z (içinde, mm)
The strength reduction factor depends on the net tensile strain \( \varepsilon_{t} \), found from the neutral axis depth \( c = a/\beta_{1} \) (b1 Tablodan 22.2.2.4.3) and a concrete strain of 0.003. ACI 318-19 compares it with the yield strain of the reinforcement \( \varepsilon_{ty} = f_{y}/E_{s} \):
[math] \phi_{\text{flexure}} = 0.65 + 0.25 \times \frac{\varepsilon_{t} – \varepsilon_{ty}}{0.003} \quad \text{(Table 21.2.2)} [math]
with ϕ = 0.90 Ne zaman \( \varepsilon_{t} \geq \varepsilon_{ty} + 0.003 \) (tension-controlled) and ϕ = 0.65 Ne zaman \( \varepsilon_{t} \leq \varepsilon_{ty} \) (compression-controlled). The report shows a warning when the section is not tension-controlled. When the tension steel ratio exceeds the balanced ratio, the section is checked as doubly reinforced, with the other layer as compression steel.
In the example, NS 8 top bars along x (1608.5 mm²) with d = 417 mm give \( \phi M_{n} \) = 163.25 kN-m, and the top layer ratio along x is 154.65/163.25 = 0.947.
The provided reinforcement of each layer, her yönde, is also compared to the minimum area of 0.0018 Birg (Kesit 8.6.1.1), where Ag is the gross area of the footing section perpendicular to the bars.
Moment Demand and Moment Capacity, ACI tasarım gereksinimlerini karşılamak için aşağıdaki denklemi karşılamalıdır 318-19:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 14, Section 7.5.1.1(a))} [math]
SkyCiv Foundation, Denklem ile uyumlu 14, calculates the flexural utility ratio by taking Flexural Demand over Flexural Capacity, for the top and bottom layers along x and for each strip along z. bu Eğilme ratio in the Design Checks Summary is the largest of the top, bottom and minimum reinforcement ratios (0.947 in the example).
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 15)} [math]
Other Design Checks
Besides the checks above, the calculation report of a combined footing designed to ACI 318-19 includes the stability checks, the load transfer at the column bases, the development length of the bars and a detailing check. Each one gives a utilization ratio in the Tasarım Kontrolleri Özeti of Sonuçlar sekme. The largest ratio governs the design, and the footing fails when it is greater than 1.0. A check that does not apply to the loads (for example sliding without horizontal loads) is shown with a dash.
Yukarı çekme
The uplift check compares the upward forces with the forces holding the footing down, considering axial loads only: the column loads, the self-weights of the columns, footing and soil, and the buoyant force. When no service load combination produces uplift, the check is not needed.
Devrilme
Overturning is checked by summing the moments of all the forces about the toe and the heel of the footing, her yönde, for all the service load combinations. yönetim (smallest) Güvenlik faktörü, stabilising moment over overturning moment, is compared with the Devrilme factor of safety in the Analiz sonuçlarınızın solundaki sekmesi, yukarıda listelenen tüm tasarım kodlarının bir açılır listesini getirecektir. tab of the Loads. If the loads produce no overturning moment, the check is not needed.
Kayma
Sliding is checked in each direction by dividing the horizontal resisting forces by the horizontal force applied to the footing, with both taken from the same service load combination (the one with the lowest factor of safety). The resisting forces are the friction between the footing base and the soil (none under net uplift), the passive soil pressure and the cohesion of the soil. The factor of safety is compared with the Kayma factor of safety in the Analiz sonuçlarınızın solundaki sekmesi, yukarıda listelenen tüm tasarım kodlarının bir açılır listesini getirecektir. sekme. If no horizontal force acts on the footing, the check is not needed.
Çelik Taban Plakası Tasarımı, Beton mesnedi kontrol eder
bu Çelik Taban Plakası Tasarımı, Beton mesnedi kontrol eder check verifies the bearing of each column on the footing (Kesit 22.8.3.2). The factored axial load of the column is compared with the design bearing strength, with ϕ = 0.65:
[math] \phi B_{n} = \min \left( \phi \times 0.85 f’_{c} A_{1} \sqrt{\frac{A_{2}}{A_{1}}}, \; \phi \times 2 \times 0.85 f’_{c} A_{1} \right) \quad \text{(Eq. 16)} [math]
Bir1 = Loaded area (the column area)
Bir2 = Base of the frustum with 1 dikey 2 horizontal side slopes under the column, wholly within the footing: its projection beyond the column is limited by the nearest footing edge and by 2 times the footing thickness
The larger ratio of the two columns is listed as Çelik Taban Plakası Tasarımı, Beton mesnedi kontrol eder (0.560 in the example). The report also compares the area of the dowel bars of each column with the minimum of 0.005 times the column area (Kesit 16.3.4.1).
Yayılmış Temel Tasarım İş Akışı Süreci
bu Yayılmış Temel Tasarım İş Akışı Süreci check covers the column dowel bars and the flexural bars of the footing:
- Column dowel bars: the compression development length (Kesit 25.4.9), plus the bend of the dowel, must fit in the footing thickness.
- Flexural bars: at each column face, the force in the bars must be developed on each side of the section (Kesit 13.2.8.2). The tension development length of straight bars (Kesit 25.4.2) or hooked bars (Kesit 25.4.3, depending on the bar ends chosen in the Reinforcement tab) is compared with the anchorage length available from the column face to the end of the bar.
The checks can be turned on or off in the design settings (Perform dowel bars check, Perform top bars check ve Perform bottom bars check). In the example, the Development Length ratio of 1.231 comes from the bottom bars along x at the outer face of Column 1: sadece 175 mm is available (NS 250 mm X-edge Distance minus the 75 mm cover), while the hooked bars need 215.35 mm. Increasing the X-edge Distance of the columns gives the bars the anchorage they need. The development length checks are explained in more detail in the ACI 318 (2019) Kenetlenme Boyu Kontrol Kılavuzu, written for isolated footings.
Detaylandırma
bu Detaylandırma check verifies that the footing thickness can hold the hooked ends of the top and bottom bars (90° or 180° hooks), with their bend and extension and the top and bottom covers.
Ürün geliştirici
lisans (Sivil), Yüksek Lisans (Sivil)
Referanslar
- Yapısal Beton için Bina Kodu Gereklilikleri (ACI 318-19) ve Yorum (ACI 318R-19). Amerikan Beton Enstitüsü, 2019.
- ACI Committee 421. Guide to Shear Reinforcement for Slabs (ACI 421.1R-20). Amerikan Beton Enstitüsü, 2020.