This page explains how SkyCiv Foundation designs a combined footing to ACI 318-19: 土壌支持力, 一方向せん断, punching shear and flexure, with the equations used and the results shown in the software and the calculation report, followed by the other design checks (隆起, 転覆, スライディング, 荷重移動, development length and detailing). Flexure is described with the default Strip average method, そしてその Peak wood-armer method is summarized for comparison.
あ 複合基礎 is a single footing supporting two columns. It is commonly used when the columns are too close to each other, or a column is too close to a property line, for two separate isolated footings. SkyCiv Foundation meshes the footing into plate elements supported on the soil (modeled with the subgrade modulus) and analyzes it with finite element analysis (醜い). The soil pressures, shears and moments used in the design checks below come from these FEA results. To design to the 2019 版, 選択する アメリカコンクリート学会 as the Design Code and ACI 318 (2019) as the Version when you start a new file, then pick 複合基礎. The same checks to the 2014 edition are described in ACIに基づく組み合わせフーチング設計 318-14.

The example shown on this page is a 3000 × 1500 × 500 mm combined footing with two 300 × 300 mm columns placed 250 mm from the ends of the footing (X-edge Distance), #5 bars at 200 mm in both directions at the top and bottom, と 75 mm cover. カラム 1 carries a dead load of 200 kN and a live load of 100 kN, とコラム 2 a dead load of 250 kN and a live load of 120 kN. The x-direction is the direction joining the two columns.
Design Settings for ACI 318-19
The methods used for the checks are set in Edit Design Settings (Details tab). For ACI 318-19, の Moment Demand Calculation offers the Strip average method (デフォルト) そしてその Peak wood-armer method. The settings also hold the Perform One-Way Shear Check toggle and the Punching Shear Edge Factor (0.5 デフォルトでは), as well as the switches of the load transfer and development length checks.

Combined Footing Design Checks to ACI 318-19
Dimension Requirements and Soil Bearing
To size a combined footing, サービス (因数分解されていない) loads such as Dead (D), 住む (L), 風 (W) and Seismic (E) are combined with the service load combinations. The governing combination is the design load, and the base area is proportioned so that the allowable soil pressure is not exceeded (ACI 318-19, 断面 13.3.1.1):
[math] q_{a} = \frac{P1_{n} + P2_{n}}{A} \quad \text{(Eq. 1)} [math]
qa = 許容土圧
P1ん, P2ん = Unfactored loads at Column 1 (左) とコラム 2 (正しい)
A =基礎エリア
Solving Equation 1 for the area gives a first estimate of the footing dimensions:
[math] A = \frac{P1_{n} + P2_{n}}{q_{a}} \quad \text{(Eq. 1a)} [math]
SkyCiv Foundation does not size the footing from Equation 1a: the dimensions are inputs (Geometry tab), and the software checks them. 土のベアリング ratio is the maximum soil pressure from the FEA results of the service load combinations (envelope), which includes the effect of the column moments and of the eccentricity of the loads, divided by the allowable soil bearing capacity entered in the Soil tab:
[math] \text{Utility Ratio} = \frac{q_{sls,max}}{q_{a}} \quad \text{(Eq. 2)} [math]
In the example, the maximum service soil pressure is 224.1 kPa, under Column 2, which carries the larger load, and the Soil Bearing ratio is 0.448. The soil pressure contour and the ratio of every check are shown in the 結果 タブ:

一方向せん断
一方向せん断限界状態, ビームシアとも呼ばれる, treats the footing like a wide beam that may fail in shear along a critical section located at a distance "d" 柱の表面から. It is checked when Perform One-Way Shear Check is enabled in the design settings (デフォルトでオン).
One-way Shear Demand または \( V_{u} \) is taken from the strip average shear diagrams of the FEA (ultimate load combinations): the shear forces of the plate elements are summed across the width of the footing, and the diagram is read at the critical sections, located at the effective depth of the bottom bars in that direction from each column face (or at the edge of the footing when that distance falls outside it). The largest absolute shear at these sections is the demand.
- Along x (the direction joining the columns), one diagram covers the whole footing, with the critical sections on both sides of both columns.
- Along z, each column has its own diagram, through that column.
The diagrams can be viewed in the 結果 tab by opening Diagrams and choosing 一方向せん断 の中に ダイアグラム リスト. In the example, the critical sections along x are 417 んん (the effective depth of the bottom x-bars) from the inner faces of the columns, and the demand is 158.70 kN, next to Column 2:

図 1. Critical sections and shear diagram of one-way shear along x (結果, Diagrams button)
一方向せん断耐力 または \( \phi V_{c} \) is calculated with Equation 3 (テーブル 22.5.5.1(c), for members without shear reinforcement). The size effect factor \( \lambda_{s} \) is neglected for footings, as permitted by 断面 13.2.6.2.
[math] \phi V_{c} = \phi_{\text{shear}} \times 8 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Imperial)} [math]
または
[math] \phi V_{c} = \phi_{\text{shear}} \times 0.66 \lambda \left( \rho_{w} \right)^{1/3} \sqrt{f’_{c}} \times b_{w} \times d \quad \text{(Eq. 3, Table 22.5.5.1(c), Metric)} [math]
[math] \rho_{w} = \frac{n \times A_{b}}{L \times d} [math]
ϕせん断 = Shear strength reduction factor, 0.75 (テーブル 21.2.1)
λ = Modification factor for lightweight concrete
rw = Ratio of the bottom bars in the direction checked
ん, あb = Number and area of these bars, across the footing dimension L perpendicular to them
f’c = 規定のコンクリート強度 (psi, MPa)
bw = Width resisting the shear (に, んん)
d = Effective depth of the bottom bars in the direction checked (に, んん)
Along x, \( b_{w} \) is the full width of the footing (its dimension along z). Along z, the footing is divided into two design strips at the midpoint between the two column centres, and each column’s shear is checked against the capacity of its own strip, と \( b_{w} \) equal to the strip width. In the example, both strips are 1500 幅 mm.
The calculation report shows the shear diagram of each direction, followed by the demand, the capacity and the ratio. Along x, \( \phi V_{c} \) = 192.9 kN and the ratio is 158.7/192.9 = 0.823:

ACIの設計要件を満たすには、せん断需要とせん断容量が次の式を満たす必要があります。 318-19:
[math] V_{u} \leq \phi V_{c} \quad \text{(Eq. 4, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, 方程式に従って 4, calculates the one-way shear utility ratio by taking Shear Demand over Shear Capacity, along x and for each column along z. The largest ratio is listed as 一方向せん断 in the Design Checks Summary.
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 5)} [math]
二方向せん断 (パンチングシャー)
The two-way shear limit state, パンチングシャーとも呼ばれます, has its critical section at a distance "d/2" from the faces of the column, around the perimeter of the column (断面 22.6.4.1). Its length is the critical perimeter \( b_{o} \). The check is done for each column. The critical perimeters can be viewed in the 結果 tab by opening Diagrams and choosing パンチングシャー の中に ダイアグラム リスト:

図 2. Critical perimeters of two-way shear (結果, Diagrams button)
The effective depth d is the average of the effective depths of the bottom bars in both directions (409 mm in the example). When a column face is closer to a footing edge than the Punching Shear Edge Factor 倍d, the perimeter on that side extends to the footing edge and is not counted in \( b_{o} \). The column is then classified as an interior, edge or corner column, which sets \( \alpha_{s} \) = 40, 30 または 20 (断面 22.6.5.3). If the column is close to two opposite edges, the punching shear check is skipped for that column, as one-way shear governs. A round column is taken as an equivalent square column with sides equal to its diameter. In the example, both columns are interior columns, と \( b_{o} \) = 4 × 709 = 2836 んん.
Two-way Shear Demand is calculated at the critical perimeter with the mesh-based method, from the finite element analysis of the footing. The upward force from the soil pressure inside the critical perimeter, \( F_{q} \), is the sum of the forces of the mesh elements in that area (the average pressure on each element times its area inside the perimeter, listed in a table of the report), and it is subtracted from the factored column load. The maximum shear stress \( v_{u} \) on the critical perimeter also includes the unbalanced moments transferred by eccentric shear (ACI 421.1R-20):
[math] v_{u} = \frac{P_{u} – F_{q}}{b_{o} \times d} + \frac{\gamma_{v,x} \times M_{u,x} \times c_{x}}{J_{c,x}} – \frac{\gamma_{v,z} \times M_{u,z} \times c_{z}}{J_{c,z}} \quad \text{(Eq. 6)} [math]
[math] \gamma_{v} = 1 – \frac{1}{1 + \frac{2}{3}\sqrt{b_{1}/b_{2}}} \quad \text{(Eq. 7)} [math]
Pあなた = Factored column load
Fq = Resultant of the factored soil pressure inside the critical perimeter, summed over the FEA mesh elements
cv = Fraction of the unbalanced moment transferred by eccentric shear
Mあなた = Unbalanced moment: column moment, plus column shear times the column height and footing thickness, minus the column load times the offset of the centroid of the critical section (edge and corner columns)
b1, b2 = Dimensions of the critical section perpendicular and parallel to the direction considered
c, Jc = Distance to the point considered and polar moment of inertia of the critical section
For edge and corner columns, \( \gamma_{v} \) and the stresses are calculated following ACI 421.1R-20. The maximum stress around the critical section is taken as the demand.
せん断耐力 is the punching shear stress \( \phi v_{c} \), governed by the smallest value of Equations 8, 9 と 10 あたり 断面 22.6.5.2. Unlike ACI 318-14, の 2019 edition includes the size effect factor \( \lambda_{s} \) (断面 22.5.5.1.3), which reduces the capacity of footings with an effective depth over 10 に (250 んん). In the example, \( \lambda_{s} \) = 0.871 for d = 409 んん.
[math] \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + d/10}} \right) \quad \text{(Imperial)} \qquad \lambda_{s} = \min \left( 1, \sqrt{\frac{2}{1 + 0.004\,d}} \right) \quad \text{(Metric)} [math]
[math] v_{c,a} = 4 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Imperial)} [math]
[math] v_{c,b} = \left( 2 + \frac{4}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Imperial)} [math]
[math] v_{c,c} = \left( 2 + \frac{\alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Imperial)} [math]
または
[math] v_{c,a} = 0.33 \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 8, Section 22.6.5.2(a), Metric)} [math]
[math] v_{c,b} = \left( 0.17 + \frac{0.33}{\beta} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 9, Section 22.6.5.2(b), Metric)} [math]
[math] v_{c,c} = \left( 0.17 + \frac{0.083 \times \alpha_{s} \times d}{b_{o}} \right) \lambda_{s} \lambda \sqrt{f’_{c}} \quad \text{(Eq. 10, Section 22.6.5.2(c), Metric)} [math]
[math] \phi v_{c} = \phi_{\text{shear}} \times \min \left( v_{c,a}, v_{c,b}, v_{c,c} \right) [math]
注意: β は柱の長辺と短辺の比です。 (1.0 for a round column), と \( \alpha_{s} \) is given by Section 22.6.5.3. ϕせん断 = 0.75 (テーブル 21.2.1).
λs = Size effect modification factor
λ = Modification factor for lightweight concrete
f’c = 規定のコンクリート強度 (psi, MPa)
D =効果的な深さ, the average of the effective depths of the bottom bars in both directions (に, んん)
bの = Critical perimeter (に, んん)
The calculation report shows, for each column, the plan of the critical shear area, the soil pressure force \( F_{q} \), the stresses around the perimeter, and the capacity. コラム用 1 of the example, \( v_{u} \) = 0.261 MPa and \( \phi v_{c} \) = 0.980 MPa:

ACIの設計要件を満たすには、せん断需要とせん断容量が次の式を満たす必要があります。 318-19:
[math] v_{u} \leq \phi v_{c} \quad \text{(Eq. 11, Section 7.5.1.1(b))} [math]
SkyCiv Foundation, 方程式に従って 11, calculates the two-way shear utility ratio of each column by taking Shear Demand over Shear Capacity, both as stresses. The larger ratio of the two columns is listed as パンチングシャー in the Design Checks Summary (0.318 in the example, from Column 2).
[math] \text{Utility Ratio} = \frac{\text{Shear Demand}}{\text{Shear Capacity}} \quad \text{(Eq. 12)} [math]
曲げ
SkyCiv Foundation checks the top and bottom reinforcement in both directions against the moments of the whole footing from the FEA, rather than at a single critical section. In a combined footing, the top bars along x resist the hogging moment between the columns, and the bottom bars resist the sagging moments under the columns and in the transverse direction.
Moment Demand with the Strip Average Method
とともに Strip average method (デフォルト Moment Demand Calculation), the footing is treated like a wide beam in each direction: the Wood-Armer moments of the plate elements are summed across the width of the footing, which gives the total moment carried by that width at each section. This is done for the top and bottom layers, along x and along z, under the ultimate load combinations (envelope).
- Along x, the strip covers the full width of the footing, and one moment diagram covers both columns.
- Along z, the footing is divided into two design strips at the midpoint between the column centres, and each column has its own diagram.
- Bottom layer: \( M_{u} \) is the largest strip moment at the column faces.
- Top layer: \( M_{u} \) is the largest hogging (ネガティブ) strip moment anywhere along the strip.
The moment diagrams can be viewed in the 結果 tab by opening Diagrams, choosing 瞬間 の中に ダイアグラム リスト, and picking the 層 と 方向. In the example, the top layer along x has a maximum hogging moment of 154.65 kN-m, near midway between the columns:

図 3. Strip average moment diagram, top layer along x (結果, Diagrams button)
The calculation report shows the same diagram for each layer and direction, with a table of the maximum moment, its coordinates and the governing load combination, followed by the utility ratio:

Peak Wood-Armer Method
とともに Peak wood-armer method, \( M_{u} \) is instead the maximum Wood-Armer moment per unit width found anywhere over the footing, for the top and bottom layers in both directions, and the capacity is calculated per unit width (12 in or 1000 んん). Because it uses the peak moment rather than the moment spread over the width, it is usually more conservative. The Wood-Armer moments can be viewed in the 結果 tab with the Wood Armer ボタン, by picking the 場合, 層 と 方向 の中に View Options. In the example, the peak top moment along x is 105.17 kN-m / m, while the strip average moment of 154.65 kN-m over the 1.5 m width of the footing is 103.1 kN-m / m. This method is described in ACIに基づく組み合わせフーチング設計 318-14.

曲げ能力
With the strip average method, の 曲げ能力 または \( \phi M_{n} \) is calculated for the width of the strip, with the bars of the layer across that width (along z, the share of the bars in each strip, in proportion to its width), 式を使用する 13:
[math] \phi M_{n} = \phi_{\text{flexure}} \times A_{s} \times f_{y} \times \left( d – \frac{a}{2} \right) \quad \text{(Eq. 13)} [math]
[math] a = \frac{A_{s} \times f_{y}}{0.85 \times f’_{c} \times b} [math]
ϕたわみ = Flexural strength reduction factor (テーブル 21.2.2)
あs = Area of the tension bars of the layer across the strip width (に2, んん2)
fそして = Reinforcement strength (psi, MPa)
d = Distance from the extreme compression fiber to the centroid of the tension reinforcement (に, んん)
a = Depth of the equivalent rectangular stress block (に, んん)
b = Strip width: the full width of the footing along x, the strip of each column along z (に, んん)
The strength reduction factor depends on the net tensile strain \( \varepsilon_{t} \), found from the neutral axis depth \( c = a/\beta_{1} \) (b1 表から 22.2.2.4.3) and a concrete strain of 0.003. ACI 318-19 compares it with the yield strain of the reinforcement \( \varepsilon_{ty} = f_{y}/E_{s} \):
[math] \phi_{\text{flexure}} = 0.65 + 0.25 \times \frac{\varepsilon_{t} – \varepsilon_{ty}}{0.003} \quad \text{(Table 21.2.2)} [math]
with ϕ = 0.90 いつ \( \varepsilon_{t} \geq \varepsilon_{ty} + 0.003 \) (tension-controlled) and ϕ = 0.65 いつ \( \varepsilon_{t} \leq \varepsilon_{ty} \) (compression-controlled). The report shows a warning when the section is not tension-controlled. When the tension steel ratio exceeds the balanced ratio, the section is checked as doubly reinforced, with the other layer as compression steel.
In the example, の 8 top bars along x (1608.5 mm²) with d = 417 mm give \( \phi M_{n} \) = 163.25 kN-m, and the top layer ratio along x is 154.65/163.25 = 0.947.
The provided reinforcement of each layer, それぞれの方向に, is also compared to the minimum area of 0.0018 あg (断面 8.6.1.1), where Ag is the gross area of the footing section perpendicular to the bars.
ACIの設計要件を満たすには、モーメント需要とモーメント容量が次の式を満たす必要があります。 318-19:
[math] M_{u} \leq \phi M_{n} \quad \text{(Eq. 14, Section 7.5.1.1(a))} [math]
SkyCiv Foundation, 方程式に従って 14, calculates the flexural utility ratio by taking Flexural Demand over Flexural Capacity, for the top and bottom layers along x and for each strip along z. 曲げ ratio in the Design Checks Summary is the largest of the top, bottom and minimum reinforcement ratios (0.947 in the example).
[math] \text{Utility Ratio} = \frac{\text{Flexure Demand}}{\text{Flexure Capacity}} \quad \text{(Eq. 15)} [math]
Other Design Checks
Besides the checks above, the calculation report of a combined footing designed to ACI 318-19 includes the stability checks, the load transfer at the column bases, the development length of the bars and a detailing check. Each one gives a utilization ratio in the デザインチェックの要約 の 結果 タブ. The largest ratio governs the design, and the footing fails when it is greater than 1.0. A check that does not apply to the loads (for example sliding without horizontal loads) is shown with a dash.
引抜き
The uplift check compares the upward forces with the forces holding the footing down, considering axial loads only: the column loads, the self-weights of the columns, footing and soil, and the buoyant force. When no service load combination produces uplift, the check is not needed.
転倒
Overturning is checked by summing the moments of all the forces about the toe and the heel of the footing, それぞれの方向に, for all the service load combinations. 統治者 (smallest) 安全率, stabilising moment over overturning moment, is compared with the 転倒 factor of safety in the 設計要素 tab of the Loads. If the loads produce no overturning moment, the check is not needed.
滑動
Sliding is checked in each direction by dividing the horizontal resisting forces by the horizontal force applied to the footing, with both taken from the same service load combination (the one with the lowest factor of safety). The resisting forces are the friction between the footing base and the soil (none under net uplift), the passive soil pressure and the cohesion of the soil. The factor of safety is compared with the 滑動 factor of safety in the 設計要素 タブ. If no horizontal force acts on the footing, the check is not needed.
荷重伝達
荷重伝達 check verifies the bearing of each column on the footing (断面 22.8.3.2). The factored axial load of the column is compared with the design bearing strength, with ϕ = 0.65:
[math] \phi B_{n} = \min \left( \phi \times 0.85 f’_{c} A_{1} \sqrt{\frac{A_{2}}{A_{1}}}, \; \phi \times 2 \times 0.85 f’_{c} A_{1} \right) \quad \text{(Eq. 16)} [math]
あ1 = Loaded area (the column area)
あ2 = Base of the frustum with 1 垂直に 2 horizontal side slopes under the column, wholly within the footing: its projection beyond the column is limited by the nearest footing edge and by 2 times the footing thickness
The larger ratio of the two columns is listed as 荷重伝達 (0.560 in the example). The report also compares the area of the dowel bars of each column with the minimum of 0.005 times the column area (断面 16.3.4.1).
開発期間
開発期間 check covers the column dowel bars and the flexural bars of the footing:
- Column dowel bars: the compression development length (断面 25.4.9), plus the bend of the dowel, must fit in the footing thickness.
- Flexural bars: at each column face, the force in the bars must be developed on each side of the section (断面 13.2.8.2). The tension development length of straight bars (断面 25.4.2) or hooked bars (断面 25.4.3, depending on the bar ends chosen in the Reinforcement tab) is compared with the anchorage length available from the column face to the end of the bar.
The checks can be turned on or off in the design settings (Perform dowel bars check, Perform top bars check と Perform bottom bars check). In the example, the Development Length ratio of 1.231 comes from the bottom bars along x at the outer face of Column 1: のみ 175 mm is available (の 250 mm X-edge Distance minus the 75 mm cover), while the hooked bars need 215.35 んん. Increasing the X-edge Distance of the columns gives the bars the anchorage they need. The development length checks are explained in more detail in the ACI 318 (2019) 定着長さチェックガイド, written for isolated footings.